Troubleshooting Tips<br />
Problem # 4: Main Burner Does Not Shut Off When Thermostat<br />
is Satisfied<br />
Possible Causes:<br />
• Faulty <strong>Gas</strong> <strong>Valve</strong><br />
• Faulty Ignition Control<br />
Troubleshooting:<br />
• Check thermostat to make sure contacts are open, check for 24 Volts<br />
between “TH” and “TR”.<br />
– Should be Zero, if gas valve is stuck open, replace valve<br />
• Check for 24 Volts between “PV/MV” and “GND” .<br />
– If 24 Volts present, replace ignition control<br />
– If 24 Volts not present, replace gas valve