General Specifications<br />
Options and Accessories<br />
• Matching valve-regulated lead-acid<br />
battery packs<br />
• Matching maintenance bypass cabinet<br />
• Matching bolt-on power distribution<br />
unit, with one or two 42-pole panels<br />
• Input filter/power factor correction<br />
• Internally mounted input<br />
isolation transformer<br />
• Load Bus Sync Systems<br />
• Flooded rack-mounted battery systems<br />
• SNMP, SiteScan and other<br />
communications interfaces:<br />
See sidebar “Communications Options”<br />
• Remote monitor panel<br />
• Alarm status contacts<br />
• Customer alarm inputs<br />
Input<br />
Voltage: 208, 220, 240, 480 or 600 VAC,<br />
60 Hz. 3-phase, 3-or 4-wire plus ground<br />
Voltage Range: +10, -15% (no battery<br />
discharge at -20%)<br />
Frequency Range: 60 Hz, ± 5 Hz<br />
Current Distortion: 10% maximum<br />
reflected THD at full load with optional<br />
input filter. 30% THD without filter.<br />
Current Limit: 115% of full load<br />
input current<br />
Current Walk-in: 20 seconds to full load.<br />
<strong>Power</strong> Factor: Up to 0.96 lagging at full<br />
load with optional input filter. 0.80<br />
lagging minimum at full load without<br />
optional input filter.<br />
Surge Protection: Sustains input surges<br />
without damage, per criteria listed in ANSI<br />
C62.41-1980, A & B (IEEE 587).<br />
Output<br />
Voltage: 208, 220, 240, 480 or 600 VAC,<br />
60 Hz, 3-phase, 4-wire plus ground.<br />
Voltage Adjustment Range: ±5%.<br />
Voltage Regulation:<br />
±0.5% for balanced load<br />
±1.0% for 100% unbalanced load.<br />
Dynamic Regulation: ± 2.5% deviation<br />
for 100% load step. ±1% for loss or return<br />
of AC input.<br />
Transient Response Time: Recover to<br />
steady state within 1 cycle.<br />
Voltage Distortion: For linear loads,<br />
1% THD. Less than 2.5% THD for 100%<br />
nonlinear loads (3:1 crest factor) without<br />
kVA/kW derating.<br />
Phasing Balance: 120° ±0.5° for balanced<br />
load. 120° ±1° for 100% unbalanced load.<br />
Frequency Regulation: ±0.1%.<br />
Load <strong>Power</strong> Factor Range: 1.0 to 0.7<br />
lagging without derating.<br />
Overload: 125% of full load for ten<br />
minutes. 150% for one minute with<br />
true sinusoidal waveform.<br />
Environmental<br />
Operating Temperature: 0° to 40°C<br />
(UPS), 20° to 30°C (battery)<br />
Non-Operating Temperature:<br />
-20°C to 70°C.<br />
Relative Humidity:<br />
0-95% non-condensing<br />
Operating Altitude: Up to 6,600 feet<br />
(2000 meters) without derating.<br />
Acoustical Noise: Less than<br />
65 dBA typical, measured 1 meter<br />
from the unit.<br />
Standards<br />
ETL Listed to UL 1778 and UL 924 UPS<br />
standards, and CSA certified.<br />
Meets current requirements for safe<br />
high-performance UPS operation.<br />
11<br />
Communications Options<br />
The <strong>Npower</strong> will support any communications strategy.<br />
The OpenComms family of products help you get the<br />
most from your existing network. The OpenComms<br />
Network Interface Card (NIC) supports three interfaces:<br />
• Web browser, via HTML,<br />
• SNMP interface for use with OpenComms Nform <br />
or another Network Management System, and<br />
• Modbus, to interface with your existing building<br />
management system.<br />
The OpenComms Nform software is a versatile<br />
SNMP package. It provides:<br />
• Centralized monitoring of all Liebert<br />
SNMP-enabled devices,<br />
• Event and alarm management,<br />
• Adaptable and configurable viewer,<br />
• Integration of third-party SNMP devices<br />
through custom Liebert services.<br />
<strong>Npower</strong> is also compatible with Liebert’s SiteScan family<br />
of enterprise monitoring systems. In particular, SiteScan<br />
WEB allows users easy access from nearly anywhere, with:<br />
• Single and multi-site applications,<br />
• Full-featured graphical user interface via the Web,<br />
• Event management trending and reporting,<br />
• User authentication and unit control,<br />
• Full ASHRAE BACnet compatibility.<br />
<strong>Npower</strong> can be used with a variety of other<br />
communications products including MultiLink <br />
shutdown software, SiteLink integrator modules,<br />
Site TPI (to integrate signals from non-Liebert<br />
equipment), Site I/O (to integrate sensors and contacts),<br />
contact-closure alarm panels, and more. Contact your<br />
Liebert sales representative for details.