Cross Sensitivities<br />

The table shows the response of the sensor to other gases than target gas (cross sensitivities). The values are typical and apply to new sensors.<br />

The table does not claim to be complete. Gas mixtures can be displayed as the sum of all components. Gases with negative cross sensitivity may<br />

displace a positive reading of the sensor.<br />

Gas / Vapor Chemical Symbol Gas concentration Displayed value in ppm <strong>COCl</strong> 2<br />

without selective filter K2F with selective filter K2F<br />

Carbon dioxide CO 2 5 000 ppm ≤ 0.01 no effect<br />

Carbon monoxide CO 1 000 ppm ≤ 0.01 no effect<br />

Chlorine Cl 2 0.1 ppm ≤ 0.05 ≤ 0.05<br />

Chloro-formic acid methl ester CH 3 O<strong>COCl</strong> 1 ppm ≤ 0.01 no effect<br />

Ethanol C 2 H 5 OH 5.8 % by vol ≤ 0.01 no effect<br />

Hydrogen H 2 1 000 ppm ≤ 0.01 no effect<br />

Hydrogen chloride HCl 1 ppm ≤ 0.5 no effect<br />

Hydrogen cyanide HCN 1 ppm ≤ 0.2 ≤ 0.2<br />

Hydrogen peroxide H 2 O 2 1 ppm ≤ 0.01 no effect<br />

Hydrogen sulfide H 2 S 1 ppm ≤ 1.0 no effect<br />

Hydrocarbons – – – % by vol. range ≤ 0.01 no effect<br />

Nitrogen dioxide NO 2 1 ppm ≤ 0.02 (–) * ≤ 0.02 (–) *<br />

Ozone O 3 1 ppm ≤ 0.01 (–) * no effect<br />

Phosphine PH 3 0.5 ppm ≤ 0.1 ≤ 0.1<br />

i-Propanol (CH 3 ) 2 CHOH 4.5 % by vol. ≤ 0.01 no effect<br />

Sulfur dioxide SO 2 1 ppm ≤ 0.01 no effect<br />

(–) * negative display.<br />

Order List<br />

DrägerSensor ® <strong>COCl</strong> 2 ....................................................... <strong>68</strong> <strong>09</strong> <strong>930</strong><br />

Selective filter K2F .............................................................. <strong>68</strong> <strong>09</strong> 933<br />

For calibration:<br />

Calibration adapter .............................................................. <strong>68</strong> 06 978<br />

Pressure reducer ................................................................ on request<br />

Test gas cylinder 99.9 % N 2 (zero gas), 4 L, 200 bar .......... <strong>68</strong> 05 113<br />

67 mm (2.64")<br />

00123456<br />

Ø 27.6 mm (1.08")<br />

Ø 50 mm (1.97")<br />

Dräger Safety AG & Co. KGaA – < Revalstraße 1, D-23560 Lübeck, Germany – y +49 451 8 82 - 27 94 – FAX +49 451 8 82 - 49 91<br />

! http://www.draeger.com/gds<br />

9th edition - September 2001<br />

Subject to alteration<br />

90 23 515 - TD 4<strong>68</strong>1.460 en/de<br />

© Dräger Safety AG & Co. KGaA