22.04.2015 Views

files?p_File_Id=29797963&p_File_Name=Premset---13.8-kV

files?p_File_Id=29797963&p_File_Name=Premset---13.8-kV

files?p_File_Id=29797963&p_File_Name=Premset---13.8-kV

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

General characteristics<br />

Characteristics<br />

Standards<br />

Main electrical characteristics<br />

Voltage<br />

Rated voltage Ur (<strong>kV</strong> r ms) 7.2 12 <strong>13.8</strong><br />

Rated frequency fr (Hz) 50/60<br />

Insulation level (1)<br />

Rated short-duration power-frequency withstand voltage<br />

Common value Ud 50/60 Hz 1 min (<strong>kV</strong> r ms) 38<br />

Across the isolating Ud 50/60 Hz 1 min (<strong>kV</strong> r ms) 48<br />

distance<br />

Rated lightning impulse withstand voltage<br />

Common value Up 1.2/50 ms (<strong>kV</strong> peak) 95<br />

Across the isolating Up 1.2/50 ms (<strong>kV</strong> peak) 110<br />

distance<br />

Current<br />

Busbar current Ir (A r ms) 630<br />

Rated short-time<br />

withstand current<br />

and duration<br />

Ik x tk (kA r ms) 21 kA x 3 s<br />

PM100599<br />

1500 mm<br />

Dimensions<br />

Uniform dimensions for the entire system<br />

bbWidth: 375 mm for all solid-insulated units: switch, circuit breaker and<br />

metering units<br />

bbBus section: 750mm wide<br />

bbCircuit breaker with metering (incomer or feeder): 750mm wide<br />

bbDepth:1150 mm<br />

bbHeight: 1804 mm<br />

bbCable connections: 700 mm high front-aligned connections.<br />

1150 mm<br />

375 mm<br />

700 mm<br />

front cabling<br />

IEC Standards<br />

Premset units meet all the following recommendations, standards and specifications:<br />

bbIEC 62271-1: High-voltage switchgear and controlgear - Part 1: Common<br />

specifications<br />

bbIEC 62271-200: High-voltage switchgear and controlgear - Part 200: A.C. metalenclosed<br />

switchgear and controlgear for rated voltage above 1 <strong>kV</strong><br />

and up to and including 52 <strong>kV</strong><br />

bbIEC 62271-103 (replaces IEC 60265-1): Switches for rated voltages above 1 <strong>kV</strong><br />

and less than 52 <strong>kV</strong><br />

bbIEC 62271-100: High-voltage switchgear and controlgear - Part 100: High-voltage<br />

alternating current circuit breakers<br />

bbIEC 62271-102: High-voltage switchgear and controlgear - Part 102: High-voltage<br />

alternating current disconnectors and earthing switches<br />

bbIEC 61958: High-voltage prefabricated switchgear and controlgear assemblies -<br />

Voltage presence indicating systems<br />

bbIEC 60529: Degrees of protection provided by enclosures (IP Code)<br />

bbIEC 60044-8: Instrument transformers - Part 8: Low Power Current Transducers<br />

bbIEC 60044-1: Instrument transformers - Part 1: Current transformers<br />

bbIEC 60044-2: Instrument transformers - Part 2: Voltage transformers<br />

bbIEC 60255: Electrical relays.<br />

Other Specifications<br />

bbENA TS 41-36: Distribution switchgear for service up to 36<strong>kV</strong><br />

bbENA TS 50-18: Ancillary electrical equipment<br />

36

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!