files?p_File_Id=29797963&p_File_Name=Premset---13.8-kV
files?p_File_Id=29797963&p_File_Name=Premset---13.8-kV
files?p_File_Id=29797963&p_File_Name=Premset---13.8-kV
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
General characteristics<br />
Characteristics<br />
Standards<br />
Main electrical characteristics<br />
Voltage<br />
Rated voltage Ur (<strong>kV</strong> r ms) 7.2 12 <strong>13.8</strong><br />
Rated frequency fr (Hz) 50/60<br />
Insulation level (1)<br />
Rated short-duration power-frequency withstand voltage<br />
Common value Ud 50/60 Hz 1 min (<strong>kV</strong> r ms) 38<br />
Across the isolating Ud 50/60 Hz 1 min (<strong>kV</strong> r ms) 48<br />
distance<br />
Rated lightning impulse withstand voltage<br />
Common value Up 1.2/50 ms (<strong>kV</strong> peak) 95<br />
Across the isolating Up 1.2/50 ms (<strong>kV</strong> peak) 110<br />
distance<br />
Current<br />
Busbar current Ir (A r ms) 630<br />
Rated short-time<br />
withstand current<br />
and duration<br />
Ik x tk (kA r ms) 21 kA x 3 s<br />
PM100599<br />
1500 mm<br />
Dimensions<br />
Uniform dimensions for the entire system<br />
bbWidth: 375 mm for all solid-insulated units: switch, circuit breaker and<br />
metering units<br />
bbBus section: 750mm wide<br />
bbCircuit breaker with metering (incomer or feeder): 750mm wide<br />
bbDepth:1150 mm<br />
bbHeight: 1804 mm<br />
bbCable connections: 700 mm high front-aligned connections.<br />
1150 mm<br />
375 mm<br />
700 mm<br />
front cabling<br />
IEC Standards<br />
Premset units meet all the following recommendations, standards and specifications:<br />
bbIEC 62271-1: High-voltage switchgear and controlgear - Part 1: Common<br />
specifications<br />
bbIEC 62271-200: High-voltage switchgear and controlgear - Part 200: A.C. metalenclosed<br />
switchgear and controlgear for rated voltage above 1 <strong>kV</strong><br />
and up to and including 52 <strong>kV</strong><br />
bbIEC 62271-103 (replaces IEC 60265-1): Switches for rated voltages above 1 <strong>kV</strong><br />
and less than 52 <strong>kV</strong><br />
bbIEC 62271-100: High-voltage switchgear and controlgear - Part 100: High-voltage<br />
alternating current circuit breakers<br />
bbIEC 62271-102: High-voltage switchgear and controlgear - Part 102: High-voltage<br />
alternating current disconnectors and earthing switches<br />
bbIEC 61958: High-voltage prefabricated switchgear and controlgear assemblies -<br />
Voltage presence indicating systems<br />
bbIEC 60529: Degrees of protection provided by enclosures (IP Code)<br />
bbIEC 60044-8: Instrument transformers - Part 8: Low Power Current Transducers<br />
bbIEC 60044-1: Instrument transformers - Part 1: Current transformers<br />
bbIEC 60044-2: Instrument transformers - Part 2: Voltage transformers<br />
bbIEC 60255: Electrical relays.<br />
Other Specifications<br />
bbENA TS 41-36: Distribution switchgear for service up to 36<strong>kV</strong><br />
bbENA TS 50-18: Ancillary electrical equipment<br />
36