Core units<br />
Disconnecting switch<br />
SV6 - General purpose<br />
PM100011<br />
The SV6 core unit is a “3 in 1” device combining<br />
the functions of a load break switch, disconnector<br />
and associated earthing switch. It can be used in<br />
various functional units.<br />
bb3 positions (closed, open & disconnected,<br />
earthed) with direct earthing of cables<br />
bbIntuitive operation and clear mimic panel<br />
indications<br />
bbBuilt-in positive interlocks between main switch<br />
and earthing switch.<br />
Basic equipment<br />
bbTotally insulated and screened core unit integrating load breaking, disconnection<br />
and earthing functions.<br />
bbMain switch<br />
vvvacuum disconnecting load-break switch providing both load breaking and<br />
disconnection functions<br />
vvanti-reflex lever-operated mechanism (CIT type), independent of operator action.<br />
bbEarthing switch<br />
vvcombined with the main switch<br />
vvfully and positively interlocked with the main switch<br />
vvair technology in sealed-for-life tank at atmospheric pressure<br />
bbTotally SF6-free solution based on vacuum and air breaking technologies.<br />
Accessories<br />
Locking<br />
bbStandard built-in padlocking facility for main switch, earthing switch and interlock<br />
(shackle diameter < 9 mm)<br />
bbOptional keylocking facilities with flat or tubular key types:<br />
vv1 or 2 keylocks for main switch in “open & disconnected” position<br />
vv1 or 2 keylocks for earthing switch in “cables earthed” position<br />
Interlocking<br />
bbStandard built-in interlock between main switch and earthing switch<br />
bbOptional interlock between cable box door and earthing switch (prevents opening<br />
of the door unless the earthing switch is in “cables earthed” position) (*)<br />
bbOptional interlock between main switch and cable box door (prevents closing of<br />
the main switch when the door is open) (*) .<br />
Auxiliary switches<br />
bbFor main switch:<br />
vvstandard: 2 changeover contacts (1 when electrical operation)<br />
vvoptional: up to 2 additional blocks of 4 changeover contacts.<br />
bbFor earthing switch:<br />
vvoptional: 1 changeover contact.<br />
Operation counter<br />
bbOptional for main switch.<br />
DM100011<br />
Technical characteristics<br />
Rated voltage Ur (<strong>kV</strong>) <strong>13.8</strong><br />
Rated current Ir (A r ms) 630<br />
Rated short-time withstand current Ik (kA r ms) 21<br />
and duration<br />
tk (s) 3<br />
Rated making capacity of main and Icm (kA peak) 54<br />
earthing switches<br />
No-load mechanical endurance<br />
of main switch<br />
M1 class<br />
(IEC 62271-103)<br />
Number of<br />
operations<br />
1000<br />
Electrical endurance of main switch<br />
Making capacity endurance<br />
of main switch<br />
No-load mechanical endurance<br />
of earthing switch<br />
Making capacity endurance<br />
of earthing switch<br />
E3 class<br />
(IEC 62271-103)<br />
E3 class<br />
(IEC 62271-103)<br />
M0 class<br />
(IEC 62271-102)<br />
E2 class<br />
(IEC 62271-102)<br />
Number of<br />
operations<br />
Number of<br />
operations<br />
Number of<br />
operations<br />
Number of<br />
operations<br />
100<br />
5<br />
1000<br />
5<br />
(*) Consult us for availability<br />
40