Core units<br />

Metering and circuit breaker<br />

CV2 or CV6 circuit breaker with<br />

integrated metering<br />

DM100018<br />

The CV2-Sx1 or CV6-Sx2 dedicated core unit<br />

includes an incoming unit with a cable-connected<br />

circuit breaker and integrated tariff metering.<br />

bbDouble width (750 mm), but compatible with<br />

the Premset connection system.<br />

Basic equipment<br />

Combination of CV2 or CV6 circuit breaker (pages 42 or 43)<br />

and metering unit.<br />

CV2 or CV6 circuit breaker<br />

bbTotally insulated and screened “3 in 1” core unit integrating circuit breaker,<br />

disconnection and earthing functions.<br />

bbDisconnecting circuit breaker<br />

vvvacuum disconnecting circuit breaker providing both current breaking and<br />

disconnection functions<br />

vvCI1 type operating mechanism featuring push button opening and anti-reflex<br />

lever-operating closing, both independent of operator action.<br />

bbEarthing switch<br />

vvcombined with the circuit breaker<br />

vvfully and positively interlocked with the circuit breaker<br />

vvair technology in sealed-for-life tank at atmospheric pressure<br />

bbTotally SF6-free solution based on vacuum and air breaking technologies.<br />

Accessories and technical characteristics<br />

See page 42 or 43<br />

MV6 2SIS metering unit<br />

bbTotally insulated and screened design, composed of:<br />

vvIP54 metal housing<br />

vvlow-voltage cabinet<br />

vvCT block comprising of 3 ring-type current transformers (type ARU1 see page 68)<br />

vv3 phase-to-earth voltage transformers, solid-insultated and screened, located in<br />

the front compartment: easy access for maintenance and easy disconection for<br />

commissioning (type VRU1, see page 52).<br />

(*) Consult us for availability<br />

48