28.04.2015 Views

SAUTER EY-modulo 4. - sauter-controls.com sauter-controls.com

SAUTER EY-modulo 4. - sauter-controls.com sauter-controls.com

SAUTER EY-modulo 4. - sauter-controls.com sauter-controls.com

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong><br />

Catalogue 2009


The content.<br />

Solution <strong>com</strong>petence 4 5<br />

The new <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system 6 7<br />

Overall topology 8 9<br />

Introduction to <strong>EY</strong>-<strong>modulo</strong> 5 10 13<br />

Introduction to <strong>EY</strong>-<strong>modulo</strong> 4 14 15<br />

Introduction to <strong>EY</strong>-<strong>modulo</strong> 2 16 19<br />

Room management with <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 20 21<br />

Management level with <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 22 23<br />

Compatibility with <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 24 25<br />

Sample solutions 26 47<br />

Contents overview of the product section 48 49<br />

Overview <strong>EY</strong>-<strong>modulo</strong> 5 50 53<br />

Product selection <strong>EY</strong>-<strong>modulo</strong> 5 54 83<br />

Overview <strong>EY</strong>-<strong>modulo</strong> 4 84 87<br />

Product selection <strong>EY</strong>-<strong>modulo</strong> 4 88 111<br />

Overview <strong>EY</strong>-<strong>modulo</strong> 2 112 115<br />

Product selection <strong>EY</strong>-<strong>modulo</strong> 2 116 155<br />

Overview Software 156 157<br />

Software selection 158 161<br />

Type directory & symbols 162 169<br />

Training & certificates 170 171<br />

3


4 Right of amendment reserved © 2009 F r. Sauter AG


Solution <strong>com</strong>petence<br />

We have something more than a response to the<br />

highest requirements in building automation.<br />

We have the solution – <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong>.<br />

Your ideas know no bounds. And the same is true of our solutions. Especially<br />

when it <strong>com</strong>es to energy-ef ficient, environment-conscious building automation,<br />

<strong>SAUTER</strong> steers energy per formance along the right tracks. All over the world,<br />

and for almost 100 years, we have been providing good climate and <strong>com</strong>for t in<br />

living spaces. Starting in the development stage of our systems, <strong>com</strong>ponents and<br />

services, every one of our 1800 employees focuses on achieving the maximum<br />

economic benefit for our customers with the minimum use of energy. The results of<br />

this philosophy: integral solutions for buildings that are tailored to our customers‘<br />

requirements and matched to their construction projects – solutions that shoulder<br />

responsibility for protecting the environment for future generations.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

5


Technology the natural way –<br />

modular, growing, energy-efficient.<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong>.<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 – unlimited possibilities for b uilding automation.<br />

The <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 automation station is the flagship of <strong>SAUTER</strong>‘s control<br />

and automation technology. As an open, future-oriented native BACnet system, it<br />

allows integration of all functions, devices and applications (including third-par ty<br />

products) with no problems at all. Integrated WEB technologies and extended<br />

modular functions of fer the per fect solution for ever y challenge of control engineering.<br />

Intuitive operation and emergency functions, monitoring and remote<br />

maintenance via the Internet together with extensive solution libraries in our CASE<br />

engineering software round out the scope of this pioneering technology from<br />

<strong>SAUTER</strong>.<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 4 – Room and building automation with the<br />

LonMark standard.<br />

Our customers have varied structures, and building automation requirements.<br />

The LON protocol brings benef ts to countless planners, operators and users,<br />

so in addition to our BACnet and novaNet exper tise we now offer the <strong>SAUTER</strong><br />

<strong>EY</strong>-<strong>modulo</strong> with support for the key LonMark standard. This member of the family<br />

provides eff cient, noticeable control savings for energy-related room automation<br />

functions in particular.<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 – lo w-cost control unit for modernisation<br />

and integration.<br />

Thanks to <strong>SAUTER</strong> <strong>EY</strong> -<strong>modulo</strong> 2, you can conveniently and quickly add<br />

numerous functions, options and field devices to your existing system. Because<br />

these automation stations are backwards-<strong>com</strong>patible, non-Sauter systems can<br />

also be connected and integrated to ensure straightfor ward, energy-ef ficient<br />

operation based on the widespread novaNet <strong>com</strong>munication protocol.<br />

6 Right of amendment reserved © 2009 Fr. Sauter AG


Development <strong>com</strong>petence<br />

<strong>EY</strong>-<strong>modulo</strong> 5 <strong>EY</strong>-<strong>modulo</strong> 4 <strong>EY</strong>-<strong>modulo</strong> 2<br />

Communication protocol BACnet/IP<br />

Communication protocol LON<br />

Communication protocol novaNet (2-wire)<br />

Web operation on board<br />

Web operation with optional web ser ver<br />

E-mail transmission from automation stations<br />

Remote maintenance via web ser vices<br />

Local user control panels with display<br />

Universal inputs (Ni/Pt1000, V/I/R, DI)<br />

Modular extendibility with I/O modules<br />

Remote modules<br />

Indications and emergency operation at the I/O modules<br />

Remote indications with direct operation<br />

Labelling of the I/O modules<br />

Plug-in function modules<br />

Third-party system integration at the automation level<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

7


An end-to-end concept – <strong>com</strong>patibility,<br />

<strong>com</strong>fort and energy-efficiency<br />

at all levels of building automation.<br />

Alerting<br />

8<br />

Alerting<br />

12<br />

9<br />

Management<br />

level<br />

10<br />

Service portal<br />

11<br />

2<br />

Energy<br />

provision<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

3<br />

Integration<br />

from<br />

<strong>EY</strong>3600<br />

Specialist<br />

systems<br />

1<br />

Energy<br />

provision<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

7<br />

Communication<br />

Operation<br />

via web<br />

4<br />

Room<br />

management<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

5<br />

Room<br />

management<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

6<br />

Room<br />

management<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

Specialist systems<br />

Energy provision<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

novaNet<br />

Energy provision<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

2<br />

Integration from<br />

<strong>EY</strong>3600<br />

novaNet<br />

5<br />

8<br />

Right of amendment reserved © 2009 F r. Sauter AG


Overall topology<br />

Service portal<br />

Management level<br />

novaPro<br />

Operation via web<br />

Communication<br />

open<br />

versatile<br />

Room management<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

novaNet<br />

Communication<br />

simple<br />

centralised<br />

secure<br />

Room management<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

Room management<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

LON<br />

IRC<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

9


10 Right of amendment reserved © 2009 F r. Sauter AG


<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 – the high-end<br />

in modern building automation:<br />

open, eff cient and multifunctional.<br />

Integral building management to the v ery highest standard.<br />

<strong>SAUTER</strong>‘s <strong>EY</strong>-<strong>modulo</strong> 5 automation technology transforms the most <strong>com</strong>plex requirements<br />

into a <strong>com</strong>fortable and efficient building management system. Our intelligent<br />

functions and modules offering total forward and backward <strong>com</strong>patibility (also with<br />

non-Sauter and third-par ty systems) enable us to meet ever y challenge for open,<br />

modular, multi-platform building automation. This pioneering technology is entirely<br />

based on the open BACnet/IP <strong>com</strong>munication protocol via Ether net, and on any<br />

IT networks that might already be in place. <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 enables <strong>com</strong>plete<br />

data exchange for <strong>com</strong>plex building management functions, from precisely accurate<br />

climate control and alarm functions through to a <strong>com</strong>for table room data sheet<br />

application, with integral and boundless scalability in one system.<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 – a con vincing system from start to fi nish:<br />

• Networked building intelligence with BACnet/IP<br />

• Uses the existing network infrastructure<br />

• Energy efficiency thanks to intelligent function modules<br />

• Your investments are safe – with maximum availability<br />

• Total forward and backward <strong>com</strong>patibility for moder nisation and integration<br />

• System is vertically and horizontally open, so the overall concept is<br />

manufacturer-neutral<br />

• Web on board<br />

• Remote maintenance and operation via the Inter net<br />

• novaPro to optimize efficiency<br />

• Intelligence and functionality in the minimum of space<br />

• Installation outlay is minimal thanks to Plug`n Play<br />

• Planning freedom with radio and IR devices<br />

• Modern design<br />

• Needs-oriented, intuitive operation for ever y requirement,<br />

at every operating level<br />

• Adequate room for clear text labelling<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

11


Management level<br />

<strong>SAUTER</strong><br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

B<br />

modu840<br />

I/O modules<br />

modu630, 650, 670<br />

A<br />

modu525 with<br />

modu840<br />

modu525<br />

I/O modules<br />

modu530, 550, 551, 570<br />

F<br />

moduNet300<br />

Ethernet<br />

BACnet / IP<br />

C<br />

D<br />

I/O modules<br />

modu530, 550, 551, 570<br />

modu525<br />

modu525 with<br />

modu840<br />

Profibus<br />

Modbus-RTU<br />

E<br />

<strong>SAUTER</strong><br />

<strong>EY</strong>3600<br />

modu525 with<br />

modu840<br />

2x moduCom<br />

6x I/O module<br />

12<br />

Right of amendment reserved © 2009 F r. Sauter AG


<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5<br />

Room management<br />

8<br />

Alerting<br />

12<br />

9<br />

Management<br />

level<br />

10<br />

Service portal<br />

11<br />

2<br />

Energy<br />

provision<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

3<br />

Integration<br />

from<br />

<strong>EY</strong>3600<br />

Specialist<br />

systems<br />

1<br />

Energy<br />

provision<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

7<br />

Communication<br />

Operation<br />

via web<br />

4<br />

Room<br />

management<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

5<br />

Room<br />

management<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

6<br />

Room<br />

managment<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

modu710, 720<br />

Unlimited scalability<br />

in continuously open<br />

<strong>com</strong>munication.<br />

/ EIB<br />

A<br />

B<br />

C<br />

D<br />

E<br />

Operation:<br />

Operating elements can be BMKZ schematied<br />

directly on the station<br />

Separability:<br />

Operating elements can be BMKZ schematied<br />

in a separate frame a number of meters away<br />

Base station:<br />

Simplest variant of the automation station<br />

Third-party connection:<br />

Integration of third-party systems<br />

Scalability:<br />

The maximum amount of equipment<br />

F Integration of <strong>EY</strong>-<strong>modulo</strong> 2<br />

Integration <strong>EY</strong>3600<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

13


14 Right of amendment reserved © 2009 F r. Sauter AG


<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 4<br />

LonMark standard-based open<br />

solutions and room automation:<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> <strong>4.</strong><br />

The <strong>SAUTER</strong> range just grew more flexible.<br />

Our customers have varied structures, and building automation requirements.<br />

The LON protocol brings benefits to countless planners, operators and users,<br />

so we of fer products based on the key LonMark standard. Y ou stand to gain<br />

from great flexibility and individuality . The <strong>SAUTER</strong> <strong>EY</strong> -<strong>modulo</strong> 4 <strong>com</strong>pletely<br />

meets the advanced needs of modular , cross-platfor m building management.<br />

• Uses existing network links<br />

• Energy efficiency through room automation that addresses<br />

individual requirements<br />

• Adaptive algorithms and energy optimisation features<br />

• Web-enabled module implementation<br />

• Investment protection and maximum availability<br />

• Total <strong>com</strong>patibility for modernisation and integration tasks<br />

• Intelligence and functionality in a highly <strong>com</strong>pact package<br />

• Minimal effort required for assembly<br />

• State-of-the-art design<br />

• Intuitive, needs-oriented operation<br />

• Wireless-linked room control units, sensors and switches<br />

via integrated EnOcean ® interface<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

15


16 Right of amendment reserved © 2009 F r. Sauter AG


<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2<br />

Comfort for increasing requirements – modular,<br />

eff cient and <strong>com</strong>patible: <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2.<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 – the ne w generation of inte lligent building<br />

automation.<br />

The new <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 has been developed consistently from our<br />

successful building and room automation solutions based on <strong>EY</strong>3600 and<br />

novaNet – with intelligent automation stations, freely programmable intelligent<br />

unitary controllers and customized function modules. As well as a superb cost-tobenefit<br />

ratio, it is clear at first glance that the new system also offers an impressive<br />

range of solutions to meet ever y requirement in the varied world of building automation.<br />

One system, with consistent technology , from one single source. With a<br />

host of operating stations, control and field devices, <strong>SAUTER</strong> <strong>EY</strong> -<strong>modulo</strong> 2 of fers<br />

maximum flexibility and functionality for small and large installations alike, with no<br />

interface losses. Highly <strong>com</strong>fortable for users, this system utilizes energy efficiently<br />

and its excellent forward and backward <strong>com</strong>patibility ensures that your investment<br />

will be protected in the long ter m. Safety, reliability, wellbeing and sustainability<br />

– assets that are in demand throughout the world, assets that have been proven<br />

in countless installations.<br />

<strong>SAUTER</strong> <strong>EY</strong> -<strong>modulo</strong> 2 – consistent tec hnology, do wn to the<br />

smallest details.<br />

• Uses the existing network connections<br />

• Energy efficiency thanks to intelligent function modules<br />

• Your investments are safe – with maximum availability<br />

• Total forward and backward <strong>com</strong>patibility for moder nisation and integration<br />

• Web-<strong>com</strong>patible modules can be implemented<br />

• Remote maintenance and operation via the Inter net<br />

• novaPro to optimize efficiency<br />

• Intelligence and functionality in the minimum of space<br />

• Minimum outlay on installation<br />

• Planning freedom with radio and IR devices<br />

• Modern design<br />

• Needs-oriented, intuitive operation for ever y<br />

requirement, at every operating level<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

17


Management level<br />

E<br />

moduNet292<br />

<strong>SAUTER</strong><br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

/ EIB<br />

C<br />

Profibus<br />

Internet/PSTN<br />

Ethernet<br />

A<br />

F<br />

moduNet300<br />

novaWeb<br />

modu250<br />

moduNet292/291<br />

novaNet<br />

modu210<br />

B<br />

modu225<br />

modu240<br />

moduLink<br />

164<br />

moduLink<br />

165<br />

moduLink<br />

170<br />

moduLink<br />

174<br />

<strong>SAUTER</strong><br />

<strong>EY</strong>3600<br />

18<br />

Right of amendment reserved © 2009 F r. Sauter AG


<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2<br />

Room management<br />

8<br />

Alerting<br />

12<br />

9<br />

Management<br />

level<br />

10<br />

Service portal<br />

11<br />

Modbus-RTU<br />

D<br />

2<br />

Energy<br />

provision<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

3<br />

Integration<br />

from<br />

<strong>EY</strong>3600<br />

Specialist<br />

systems<br />

1<br />

Energy<br />

provision<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

7<br />

Communication<br />

Operation<br />

via web<br />

4<br />

Room<br />

management<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

5<br />

Room<br />

management<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

6<br />

Room<br />

management<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

modu230<br />

Networked facility<br />

automation – intelligent and<br />

eff cient at every point.<br />

A<br />

Operation:<br />

Separate LCD operating unit or Touch Panel<br />

B Separability:<br />

I/O modules can be separated from the<br />

station<br />

C<br />

Telephone dial-up operation<br />

D Third-par ty connection:<br />

Integration of third-party systems<br />

E<br />

Connection to management level<br />

F Integration in <strong>EY</strong>-<strong>modulo</strong> 5<br />

Integration <strong>EY</strong>3600<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

19


8<br />

Alerting<br />

12<br />

9<br />

Management<br />

level<br />

10<br />

Service portal<br />

11<br />

2<br />

Energy<br />

provision<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

3<br />

Integration<br />

from<br />

<strong>EY</strong>3600<br />

Specialist<br />

systems<br />

1<br />

Energy<br />

provision<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

7<br />

Communication<br />

Operation<br />

via web<br />

4<br />

Room<br />

management<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

5<br />

Room<br />

management<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

6<br />

Room<br />

management<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

When rooms really <strong>com</strong>e alive, <strong>SAUTER</strong>‘s<br />

intelligent room management ensures individual<br />

<strong>com</strong>fort with maximum energy efficiency.<br />

<strong>SAUTER</strong> for every room requirement.<br />

Ultramodern technology makes <strong>SAUTER</strong> one of the leading providers of building<br />

and room automation systems. Our automation stations, controllers, sensors and<br />

operating units satisfy every individual requirement for <strong>com</strong>fort, function, design<br />

and energy efficiency. In hotel rooms, laboratories, hospitals or open-plan offices:<br />

wherever <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> and <strong>SAUTER</strong> ecos are used, they <strong>com</strong>bine <strong>com</strong>plex<br />

room functions such as precise temperature, lighting and shade control, etc.<br />

to create an intuitive and precisely accurate solution for your individual room<br />

requirements.<br />

<strong>SAUTER</strong> room management solutions are based on a consistent technology that<br />

is per fectly har monised with standardised protocols, from field level and room<br />

automation through to management level, offering the ideal solution for every room<br />

requirement. Our standard Ethernet network <strong>com</strong>ponents also ensure high availability,<br />

needs-oriented scalability and ideal interfaces to ac<strong>com</strong>modate future ideas.<br />

20 Right of amendment reserved © 2009 F r. Sauter AG


Room management<br />

Operation via web<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

A<br />

novaNet<br />

ecos209<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

B<br />

Ethernet BACnet/IP<br />

ecoUnit214<br />

ecoUnit210<br />

ecoUnit346<br />

ecoUnit306<br />

ecos502<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

ecoUnit346<br />

ecoUnit146<br />

C<br />

ecoUnit316<br />

ecoUnit306<br />

ecoUnit346<br />

ecoUnit306<br />

modu490<br />

LON<br />

FanCoil<br />

VAV<br />

ecos402 ecos402<br />

ecos415 ecos416<br />

A<br />

ecos209:<br />

For temperature, lights and blinds<br />

B<br />

C<br />

ecos502 for two rooms,<br />

Temperature, lights and blinds<br />

ecos4:<br />

LON room automation<br />

ecoUnit482<br />

ecoUnit146<br />

ecoUnit106<br />

ecoUnit146<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

21


Integration in<br />

higher-level systems<br />

ERP (Enterprise Resource Planning)<br />

Web operation<br />

Benchmark<br />

<strong>com</strong>parison analysis<br />

IP Network/<br />

Web<br />

Notif cation<br />

Centralisation and networking of data<br />

Initiate measure<br />

Specialist<br />

systems<br />

BACnet/IP<br />

novaNet<br />

LON<br />

OPC<br />

22<br />

Energy provision <strong>EY</strong>-<strong>modulo</strong> 5


Management level<br />

8<br />

10<br />

Service portal<br />

2<br />

Energy<br />

provision<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

3<br />

Integration<br />

from<br />

<strong>EY</strong>3600<br />

Alerting<br />

12<br />

Specialist<br />

systems<br />

1<br />

Energy<br />

provision<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

9<br />

Management<br />

level<br />

7<br />

Communication<br />

Service portal<br />

11<br />

Operation<br />

via web<br />

4<br />

Room<br />

management<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

5<br />

Room<br />

management<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

6<br />

Room<br />

management<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

Building management tuned<br />

for efficiency – as individual and<br />

<strong>com</strong>plex as your own needs.<br />

Evaluation<br />

Limit values for offices buildings<br />

Green Building<br />

Energy improved<br />

New Building Standard (partly airconditioned)<br />

Management-level intelligence – with <strong>SAUTER</strong> novaPro.<br />

<strong>SAUTER</strong> gives you a <strong>com</strong>plete picture of your building management system’s parameters.<br />

The <strong>SAUTER</strong> novaPro open management system <strong>com</strong>bines all your <strong>SAUTER</strong><br />

and third-party subsystems into one seamless bundle, regardless of operating protocol.<br />

That means you can log system data for a <strong>com</strong>parative analysis of setpoint<br />

vs. actual values. Whether your installation is large, small, new, or existing – the<br />

focus is on individual requirements and optimal use of energy.<br />

0 50 100 150 200 250 300 350 400 450 500 550 kWh/m 2 a<br />

actual state<br />

Room<br />

management<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

23


Solutions<br />

Solutions<br />

Heating<br />

28<br />

31<br />

Ventilation/air conditioning<br />

32<br />

35<br />

Refrigeration/cooling<br />

36<br />

39<br />

Solutions<br />

Electricity<br />

40<br />

43<br />

Room automation<br />

44<br />

47


Maximum <strong>com</strong>patibility<br />

to protect your investment.<br />

100 % <strong>com</strong>patible – for cost-effective, end-to-end migration.<br />

All the <strong>EY</strong> -<strong>modulo</strong> 2 building automation modules of fer total backwards <strong>com</strong>patibility<br />

with all plants in the <strong>EY</strong>3600 generation. No matter whether you want to<br />

equip an existing <strong>EY</strong>3600 plant with additional functions, or whether you are<br />

looking for a low-cost automation solution for a construction project. <strong>SAUTER</strong><br />

<strong>EY</strong>-<strong>modulo</strong> 2 gives you guaranteed flexibility in ever y phase of the product lifecycle,<br />

so you can expand your system consistently with the functional scope from<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 4 to <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5.<br />

<strong>SAUTER</strong> moduCom – the universal interface for extensions<br />

with non-Sauter systems.<br />

<strong>EY</strong>-<strong>modulo</strong> 2 also gives you the openness to integrate subsystems. <strong>SAUTER</strong><br />

moduCom allows decentral data exchange here. Free programmability means<br />

that direct functional links with extended functional areas can be optimally incorporated<br />

into an integrated building management solution.<br />

<strong>SAUTER</strong> moduCom supports these systems:<br />

LON | EIB | M-Bus | Modbus R TU | <strong>SAUTER</strong> System <strong>EY</strong>2400 | Siemens ® Simantic<br />

<strong>controls</strong> | Hazard detection systems and security detection systems such as Securiton,<br />

Cerberus, fire detection systems, e.g. Esser | Air conditioning equipment, e.g. Toshiba<br />

| Light control systems, e.g. Zumtobel Luxmate | Pump management systems, e.g.<br />

Grundfos, Wilo | Frequency conver ters, e.g. Danfos VLT.<br />

24<br />

Right of amendment reserved © 2009 Fr. Sauter AG


1<br />

3<br />

5<br />

2<br />

4<br />

6<br />

7<br />

9,10<br />

12,14,16<br />

8<br />

11,13,15<br />

Energy-eff cient solution <strong>com</strong>petence for heating:<br />

Example 1 – moduTherm1310.<br />

Nr. Description Position Type PDS Page<br />

1 Local control unit <strong>EY</strong>-OP840F001 93.015 66<br />

2 modu525 <strong>EY</strong>-AS525F001 92.016 54<br />

3 Outdoor temperature detector (wall-mounted) B1 EGT301F101 36.016<br />

4 Stem-type detector Heating circuit flow temperature B2-B4 EGT346F101 36.036<br />

5 Clamp-on detector Heating circuit flow temperature B2-B4 EGT311F101 36.021<br />

6 Boiler temperature stem-type detector B6 EGT347F101 36.036<br />

7 Boiler temperature stem-type detector B6 EGT348F101 36.036<br />

8 Boiler temperature cable detector B7 EGT356F101 36.044<br />

9 Boiler temperature safety monitor S1 RAK82.4/3728M 21.610<br />

10 Underfloor heating circuit temperature safety monitor S2-S4 RAK82.4/3728M 21.610<br />

11 HC regulating valve (3-way) Y1 BXN……F…… 56.456<br />

DN…………; Kvs…………; PN………<br />

12 Actuator for heating circuit regulating valve Y1 AVM114SF132 51.362<br />

13 HC regulating valve (3-way) Y2 BXN……F…… 56.456<br />

DN…………; Kvs…………; PN………<br />

14 Actuator for heating circuit regulating valve Y2 AVM114SF132 51.362<br />

15 HC regulating valve (3-way) Y3 BXN……F…… 56.456<br />

DN…………; Kvs…………; PN………<br />

16 Actuator for heating circuit regulating valve Y3 AVM114SF132 51.362<br />

Parts list excludes required accessories<br />

28 Right of amendment reserved © 2009 F r. Sauter AG


Specimen solution heating<br />

System design:<br />

• Outdoor temperature detector<br />

• 2x regulated heating circuits (radiators/remote block<br />

heating) with pump, 3-point continuous regulating<br />

valve, STB (remote block heating), flow temperature<br />

detector<br />

• Boiler with charge pump, circulation pump, STB,<br />

upper and lower temperature detectors<br />

• Solar collectors with pump, STB, collector detector<br />

Caution – note frost protection!<br />

• District heating system (indirect) with continuous<br />

regulating valve, STB, temperature detector in return<br />

flow (primary side) and in flow (secondary side)<br />

Regulating functions:<br />

• AT-dependent flow temperature regulation<br />

• Heat exchanger secondary flow temperature<br />

regulation<br />

• Hot water regulation incl. Solar regulation<br />

Control functions:<br />

• Detector monitoring<br />

• Pump-blocking protection<br />

• Switching of 3x external fault signals<br />

• Control of 1x external switching output<br />

• External heat demand (e.g. from RLT)<br />

• Collective alarm<br />

• Time-controlled daytime/night time setpoints<br />

• Heating limit release<br />

• Frost protection feature<br />

• Party override function<br />

• Remote switch-on (mobile or landline telephone)<br />

• FBH high-temperature limit<br />

• Functional attic heating DIN EN1264-4<br />

• Hot water priority switching<br />

• Anti-legionella function<br />

• Anti-scald protection at boiler outlet<br />

• Solar charging of boiler<br />

• Solar collector high-temperature limit<br />

• Circulation pump control<br />

• Heat exchanger return temperature max. limiting<br />

• Heat exchanger flow rate min. Limiting (ext. contact)<br />

Brief Description:<br />

The moduTher m3220 system is a weather-controlled heating group<br />

regulator supplying domestic hot water through district heat and a solar<br />

energy coupling. The two heating circuits are switched on and off in<br />

automatic mode by timer programs, enabled time limits and the frost<br />

protection function. The flow temperature of the heating circuits is regulated<br />

to the daytime or night-time setpoint in dependence on the outside<br />

temperature and time of day. The party function enables a <strong>com</strong>fortable<br />

extension of the daytime setpoint. Overheating protection and floordrying<br />

function are available for under floor heating. It is possible to<br />

signal a collective external alarm. Water heating, circulation pump and<br />

anti-legionella function are controlled by timer programs. The circulation<br />

pump switch contact can be used for a collective alarm or for the circulation<br />

pump. The anti-scalding protection on the boiler output is able<br />

to block the boiler heating process. The hot water priority switch is able<br />

to reduce heating circuit output in favour of hot water preparation. The<br />

best possible use of solar energy is achieved by blocking the boilers<br />

heating function for the heating circuits and changing the setpoint.<br />

Boiler heating using solar energy is enabled by the solar panels› overheating<br />

protection. Heat exchange regulation is blocked by primar y<br />

restriction functions. Heating circuits and hot water preparation are<br />

controllable remotely by mobile or telephone in conjunction with other<br />

optional accessories.<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

31


1<br />

3<br />

5<br />

2<br />

4 6<br />

7<br />

9, 12<br />

11<br />

8<br />

10<br />

13<br />

14 15<br />

Energy-eff cient solution <strong>com</strong>petence for heating and<br />

air-conditioning: Example 1 – moduClim2210.<br />

Nr. Description Position Type PDS Page<br />

1 Local control unit <strong>EY</strong>-OP840F001 93.015 66<br />

2 modu525 <strong>EY</strong>-AS525F001 54<br />

3 Outdoor temperature detector (wall-mounted) B1 EGT301F101 36.016<br />

4 Exhaust and supply air detector (air duct) B2, B3 EGT347F101 36.036<br />

5 Air heater return stem-type detector B4 EGT346F101 36.036<br />

6 Air heater return clamp-on detector B4 EGT311F101 36.021<br />

7 Room temperature detector, RAL9010 B5 EGT330F101 36.027<br />

8 Outside-/ exhaust-air damper valve actuator M1, M2 ASM124F122 51.025<br />

9 Filter monitor fine differential pressure controller S1-S3 DDL103F001 23.901<br />

20…300Pa<br />

10 Fan airflow monitor fine differential pressure controller S4, S5 DDL105F001 23.901<br />

50…500Pa<br />

11 Frost protection monitor, continuous S8 TFL611F200 22.040<br />

12 Fine differential pressure controller for HRec anti-icing facility S9 DDL103F001 23.901<br />

13 Air heater valve (3-way) Y1 BXN……F…… 56.456<br />

DN…………; Kvs…………; PN………<br />

14 Air heater valve actuator Y1 AVM114SF132 51.362<br />

15 HRec bypass valve actuator Y3 ASM124SF132 51.023<br />

Parts list excludes required accessories<br />

32 Right of amendment reserved © 2009 F r. Sauter AG


Migration<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

modu525<br />

I/O modules<br />

modu530, 550,<br />

551, 570<br />

BACnet/IP<br />

modu525<br />

with modu840<br />

I/O modules<br />

modu530, 550,<br />

551, 570<br />

moduNet300<br />

<strong>EY</strong>3600<br />

novaNet<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

nova220<br />

nova225<br />

modu225<br />

modu210<br />

novaLink164<br />

moduLink164<br />

Field modules<br />

Field modules<br />

novaLink165<br />

moduLink165<br />

Extend your site step by step with <strong>EY</strong>-<strong>modulo</strong> –<br />

exactly as you want.<br />

25


Specimen solution heating<br />

System design:<br />

• Outdoor temperature detector<br />

• 3x regulated heating circuits (radiators/remote block<br />

heating) with pump, continuous regulating valve,<br />

positioning value (remote block heating),<br />

flow temperature detector<br />

• Boiler with charge pump, circulation pump, positioning<br />

value, boiler temperature detector (switching)<br />

Regulating functions:<br />

• Outdoor temperature dependent flow temperature<br />

regulation<br />

• Hot water regulating<br />

Control functions:<br />

• Detector monitoring<br />

• Pump-blocking protection<br />

• Switching of 3x external fault signals<br />

• Collective alarm<br />

• Time-controlled daytime/night time setpoints<br />

• Heating limit release<br />

• Frost protection feature<br />

• Party override function<br />

• Remote switch-on (mobile or landline telephone)<br />

• Remote block heating high-temperature limit<br />

• Functional attic heating DIN EN1264-4<br />

• Boiler control (switching)<br />

• Hot water priority switching<br />

• Anti-legionella function<br />

• Anti-scald protection at boiler outlet<br />

• Circulation pump control<br />

Brief Description:<br />

The moduTher m1310 system is a weather-controlled heating group<br />

regulator supplying domestic hot water through the independent generation<br />

of energy by an oil burner. The three heating circuits are switched<br />

on and off in automatic mode by timer programs, enabled time limits<br />

and the frost protection function. The flow temperature of the heating<br />

circuits is regulated to the daytime or night-time setpoint in dependence<br />

on the outside temperature and time of day. The party function enables<br />

a <strong>com</strong>for table extension of the daytime setpoint. Overheating protection<br />

and automatic floor-drying function are available for underfloor<br />

heating. It is possible to signal a collective external alarm. The boiler is<br />

controlled by the moduTher m regulator as an enabling switch.Water<br />

heating, circulation pump and anti-legionella function are controlled by<br />

timer programs. The circulation pump switch contact can be used for a<br />

collective alarm or for the circulation pump. The anti-scalding protection<br />

on the boiler output is able to block the boiler heating process. The hot<br />

water priority switch is able to reduce heating circuit output in favour of<br />

hot water preparation. eating circuits and hot water preparation are<br />

controllable remotely by mobile or telephone in conjunction with other<br />

optional accessories.<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

29


Specimen solution heating and air-conditioning<br />

System design:<br />

• Outside and exhaust air valve<br />

• Air filter<br />

• 1/2-speed fans/FU release<br />

• Air heater with pump, regulating valve,<br />

frost protection monitor, optional return detector<br />

• Plate heat exchanger for HRec<br />

• Supply air detector<br />

• Outdoor & exhaust air detectors,<br />

optional: room detector<br />

Regulating functions:<br />

• Temperature control<br />

- exhaust/supply air cascade<br />

- room supply air cascade<br />

- supply air constant<br />

Control functions:<br />

• Starting circuit<br />

• Cooling protection<br />

• Fire switch-off<br />

• Filter monitoring<br />

• Free outdoor air cooling<br />

• Frost-protection monitoring<br />

• Detector monitoring/change-over<br />

• Blow-in temperature min./max. limiting<br />

• Motor/air flow monitoring<br />

• Pump-blocking protection<br />

• Maintenance switch monitoring<br />

• Collective alarm<br />

• Standstill regulation<br />

• External heat demand<br />

• Summer/winter HRec and anti-icing facility<br />

Brief Description:<br />

The moduClim2210 system is a 2-stage ventilation system with a heating,<br />

cooling and heat recovery sequence. Outside air is sucked in by<br />

the supply air ventilator and cleaned by filters with differential pressure<br />

control. Supply air is heated depending on the dif ference between<br />

outside and ambient air temperature. If the external temperature is low<br />

the supply air is first heated by a heat exchanger using exhaust ambient<br />

air. Independent exter nal air heating or cooling can be switched on<br />

and of f using the system‘s timer program. In addition, the system is<br />

always shut down in the event of a malfunction message from the motor,<br />

air flow control, fire, etc. It is possible to signal a collective external<br />

alarm in this context. The filter monitor will trigger a maintenance alarm<br />

if filters be<strong>com</strong>e contaminated. The system will also react to a broken<br />

sensor wire and activate error control; this is followed by a regulator<br />

sensor switchover and a switchover from cascade supply air to constant<br />

supply air control, whereby minimum and maximum supply temperatures<br />

are liwithed. The star ting circuit in conjunction with an outside<br />

temperature sensor reduces the danger of malfunction due to frost and<br />

low external temperatures. The standstill controller protects the air heater<br />

in frost hazard areas.<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

33


Specimen solution heating and air-conditioning<br />

System design:<br />

• Outside and exhaust air valve<br />

• Air filter<br />

• 1/2-speed fans/FU release<br />

• Air heater with pump, regulating valve,<br />

frost protection monitor, optional return detector<br />

• Air cooler with regulating valve<br />

• Caution – note frost protection!!<br />

• Plate heat exchanger for HRec<br />

• Supply air detector<br />

• Outdoor & exhaust air detectors, optional:<br />

room detector<br />

Regulating functions:<br />

• Temperature control<br />

- exhaust/supply air cascade<br />

- room supply air cascade<br />

- supply air constant<br />

Control functions:<br />

•Starting circuit<br />

• Cooling protection<br />

• Fire switch-off<br />

• Filter monitoring<br />

• Free outdoor air cooling<br />

• Frost-protection monitoring<br />

• Detector monitoring/change-over<br />

• Blow-in temperature min./max. limiting<br />

• Motor/air flow monitoring<br />

• Pump-blocking protection<br />

• Maintenance switch monitoring<br />

• Collective alarm<br />

• Summer <strong>com</strong>pensation<br />

• Standstill regulation<br />

• External heat demand<br />

• Summer/winter HRec and anti-icing facility<br />

Brief Description:<br />

The moduClim2230 is a 2-stage ventilation system with a heating, cooling<br />

and heat recovery sequence. Outside air is sucked in by the supply<br />

air ventilator and cleaned by filters with dif ferential pressure control.<br />

Supply air is either heated by heat recovery and air heater or cooled<br />

by the cooling coil, depending on the difference between supply air<br />

and ambient air. Ambient air is then transported back to the external<br />

environment by an exhaust air fan. The system can be switched on and<br />

off via a timer program. Independent external cooling can be activated<br />

if necessary. The system is always shut down in the event of a malfunction<br />

message from the motor, air flow control, fire, etc. It is possible to<br />

signal a collective external alarm in this context. The filter monitor will<br />

trigger a maintenance alarm if filters be<strong>com</strong>e contaminated. The system<br />

will also react to a broken sensor wire and activate error control; this<br />

is followed by a regulator sensor switchover and a switchover from<br />

cascade supply air to constant supply air control, whereby minimum<br />

and maximum supply temperatures are liwithed. The starting circuit in<br />

conjunction with an outside temperature sensor reduces the danger of<br />

malfunction due to frost and low exter nal temperatures. The standstill<br />

controller protects the air heater in frost hazard areas. A summer <strong>com</strong>pensation<br />

function propor tionally increases the temperature setpoints<br />

for exhaust air, ambient air and supply air in the event of high external<br />

temperatures.<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

35


1<br />

4<br />

7<br />

2, 3, 5<br />

6<br />

8, 9<br />

11<br />

10<br />

12<br />

Energy-eff cient solution <strong>com</strong>petence for cooling:<br />

Example 1 – <strong>EY</strong>-<strong>modulo</strong> 5.<br />

Nr. Description Position Type PDS Page<br />

1 Outdoor temperature detector B101 EGT301F101 36.016<br />

2 Stem-type temperature detector B301 EGT346F101 36.036<br />

3 Stem-type temperature detector B201 EGT346F101 36.036<br />

4 Universal thermostat F001 RAK82.4/3773M 21.610<br />

5 Stem-type temperature detector B303 EGT346F101 36.036<br />

6 Valve actuator, position controller Y002 AVM234SF132 51.377<br />

7 3-way flanged valve Y002 BU.. 56.111<br />

8 Stem-type temperature detector B001 EGT347F101 36.036<br />

9 Stem-type temperature detector B003 EGT347F101 36.036<br />

10 Automation Station modular 26-154 I/O, BACnet/IP, Web <strong>EY</strong>-AS525F001 92.016 54<br />

11 I/O: Input module 8UI/8DI(Universal/Digital) <strong>EY</strong>-IO530F001 92.031 56<br />

12 Local control unit for <strong>EY</strong>-<strong>modulo</strong> 5 AS <strong>EY</strong>-OP840F001 93.015 66<br />

Parts list excludes required accessories<br />

36 Right of amendment reserved © 2009 F r. Sauter AG


Specimen solution cooling<br />

System design:<br />

• External temperature sensor<br />

• Refrigeration unit with 2 <strong>com</strong>pressor networks<br />

• Temperature sensor Entry temperature Refrigeration<br />

unit (cold water)<br />

• Temperature sensor Exit temperature Refrigeration<br />

unit (cold water)<br />

• Cooling tower fan 1-stage<br />

• Cooling tower inspection switch<br />

• Buffer storage temperature sensor (top)<br />

• Buffer storage temperature sensor (bottom)<br />

Control functions:<br />

• Time-dependent activation/deactivation of the<br />

refrigeration unit<br />

• Temperature-dependent activation/deactivation<br />

of the cooling tower fan<br />

• Buffer storage charging<br />

Regulating functions:<br />

• External temperature liwith value<br />

• Time delay<br />

<strong>EY</strong>-<strong>modulo</strong> 5 Cooling plant<br />

M003<br />

T<br />

B301<br />

1<br />

A002<br />

A003<br />

1 1<br />

B001<br />

T<br />

A Y002<br />

T<br />

B101<br />

B201<br />

T<br />

B003<br />

S003<br />

B<br />

M002<br />

AB<br />

T<br />

F001<br />

T<br />

T<br />

B303<br />

VL<br />

RL<br />

A - 0 - 1<br />

AI<br />

AO<br />

DI<br />

DO<br />

CI<br />

1 1<br />

1 1 1<br />

2<br />

2<br />

3 1 3<br />

1 1<br />

1<br />

1<br />

1<br />

AI<br />

AO<br />

DI<br />

DO<br />

CI<br />

Brief Description:<br />

This system is a weather-controlled refrigeration plant whose buf fer<br />

storage is cooled by a refrigeration unit and distributed to the cooling<br />

networks. The exhaust heat created in the refrigeration unit is passed<br />

on to the environment via the cooling unit and cooling tower. However,<br />

energy efficiency can be increased by coupling the cooling unit to a<br />

domestic hot water system to heat the water via a heat exchanger ,<br />

thereby increasing the efficiency of the entire plant. The entire refrigeration<br />

plant is activated in dependence on an exter nal temperature<br />

liwith value and a time constant. The refrigeration unit is enabled by a<br />

normal-operation signal from the corresponding cold water pump. The<br />

refrigeration unit is activated via the buffer storage. Each <strong>com</strong>pressor is<br />

protected by a mandator y minimum operating time. Subsequent deactivation<br />

occurs under consideration of a minimum operating time with a<br />

switch-off delay followed by a time-limited activation block. The singlestage<br />

cooling tower fan is activated in dependence on the cooling<br />

water temperature control. The cooling tower fan is enabled by a normal-operation<br />

signal from the cold water pump or refrigeration unit. A<br />

malfunction message is generated in the event of a malfunction and the<br />

plant switched of f if necessar y. The plant is equipped with inspection<br />

<strong>controls</strong> for servicing and maintenance work.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

37


Specimen solution cooling<br />

System design:<br />

• Outdoor temperature detector<br />

• External temperature sensor<br />

• Refrigeration unit with 2 <strong>com</strong>pressor networks<br />

• Temperature sensor Entry temperature Refrigeration<br />

unit (cold water)<br />

• Temperature sensor Exit temperature Refrigeration<br />

unit (cold water)<br />

• Cooling tower fan 1-stage<br />

• Cooling tower inspection switch<br />

• Buffer storage temperature sensor (top)<br />

• Buffer storage temperature sensor (bottom)<br />

Control functions:<br />

• Time-dependent activation/deactivation of the<br />

refrigeration unit<br />

• Temperature-dependent activation/deactivation<br />

of the cooling tower fan<br />

• Buffer storage charging<br />

Regulating functions:<br />

• External temperature liwith value<br />

• Time delay<br />

<strong>EY</strong>-<strong>modulo</strong> 2 Cooling plant<br />

M003<br />

T<br />

B301<br />

1<br />

A002<br />

A003<br />

1 1<br />

B001<br />

T<br />

A Y002<br />

T<br />

B101<br />

B201<br />

T<br />

B003<br />

S003<br />

B<br />

M002<br />

AB<br />

T<br />

F001<br />

T<br />

T<br />

B303<br />

VL<br />

RL<br />

A - 0 - 1<br />

AI<br />

AO<br />

DI<br />

DO<br />

CI<br />

1 1<br />

1 1 1<br />

2<br />

2<br />

3 1 3<br />

1 1<br />

1<br />

1<br />

1<br />

AI<br />

AO<br />

DI<br />

DO<br />

CI<br />

Brief Description:<br />

This system is a weather-controlled refrigeration plant whose buf fer<br />

storage is cooled by a refrigeration unit and distributed to the cooling<br />

networks. The exhaust heat created in the refrigeration unit is passed<br />

on to the environment via the cooling unit and cooling tower. However,<br />

energy efficiency can be increased by coupling the cooling unit to a<br />

domestic hot water system to heat the water via a heat exchanger ,<br />

thereby increasing the efficiency of the entire plant. The entire refrigeration<br />

plant is activated in dependence on an exter nal temperature<br />

liwith value and a time constant. The refrigeration unit is enabled by a<br />

normal-operation signal from the corresponding cold water pump. The<br />

refrigeration unit is activated via the buffer storage. Each <strong>com</strong>pressor is<br />

protected by a mandator y minimum operating time. Subsequent deactivation<br />

occurs under consideration of a minimum operating time with a<br />

switch-off delay followed by a time-limited activation block. The singlestage<br />

cooling tower fan is activated in dependence on the cooling<br />

water temperature control. The cooling tower fan is enabled by a normal-operation<br />

signal from the cold water pump or refrigeration unit. A<br />

malfunction message is generated in the event of a malfunction and the<br />

plant switched of f if necessar y. The plant is equipped with inspection<br />

<strong>controls</strong> for servicing and maintenance work.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

39


1<br />

3<br />

2<br />

4<br />

5<br />

7<br />

6<br />

8<br />

9 11<br />

10<br />

Energy-eff cient solution <strong>com</strong>petence for electrical:<br />

Example 1 – <strong>EY</strong>-<strong>modulo</strong> 5.<br />

Nr. Description Type PDS Page<br />

1 Automation station <strong>EY</strong>-AS525F001 92.016 54<br />

2 COM: Communication module <strong>EY</strong>-CM720F010 97.011 80<br />

3 I/O: Input module <strong>EY</strong>-IO530F001 92.031 56<br />

4 I/O: Output module <strong>EY</strong>-IO550F001 92.051 58<br />

5 I/O: Output module <strong>EY</strong>-IO551F001 92.056 60<br />

6 I/O: Input/output module <strong>EY</strong>-IO570F001 92.061 62<br />

7 LO: LED signalling <strong>EY</strong>-LO630F001 92.081 64<br />

8 LO: Control unit with LED <strong>EY</strong>-LO650F001 92.081 64<br />

9 LO: Control unit with LED <strong>EY</strong>-LO650F002 92.081 64<br />

10 LO: Control unit with LED <strong>EY</strong>-LO670F001 92.081 64<br />

11 Local control unit <strong>EY</strong>-OP840F001 93.015 66<br />

Parts list excludes required accessories<br />

40 Right of amendment reserved © 2009 F r. Sauter AG


Specimen solution electrical<br />

System design:<br />

• Access and locking control<br />

for entire building<br />

• Equipment alarm display<br />

Electrical:<br />

- Emergency lighting<br />

- Power factor correction<br />

- FI alarm<br />

- Emergency power<br />

- Fire enunciation<br />

Medicinal gases lift:<br />

- Vacuum<br />

- Oxygen<br />

Control functions:<br />

• Time program<br />

• Manual override<br />

• Slat blind control<br />

• Safety functions<br />

(wind, rain…)<br />

• Lighting control<br />

Building 1<br />

Building 2<br />

Building 3<br />

Brief Description:<br />

The system registers, signals and <strong>controls</strong> lighting conditions in an Automation<br />

Station via change-over switches for On/Of f functions. Other<br />

functions activated by light sensors, timer settings and other dependencies<br />

are also definable. The signal from light sensors, one each of which<br />

are preferably installed on the east and west facing facades, will trigger<br />

a change in BMKZ schemati, for instance to provide shade, as soon as<br />

the detected light value exceeds or falls below a specified threshold<br />

value set in the automation station. All operable rooms can remain<br />

unaffected by the light sensors and have their shading BMKZ schematis<br />

set independently of a <strong>com</strong>mand variable signal from the light sensor .<br />

Smoke and heat extraction are controlled by valves depending on safety<br />

functions (wind/rain). A time program can activate all control functions.<br />

Many additional data points may be integrated and processed<br />

by connecting a third-par ty bus system (Modbus, M-Bus), which can<br />

contribute significantly to energy-efficiency.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

41


Decades of expertise in solutions<br />

and software that offers maximum<br />

eff ciency.<br />

Benefit from the specialist‘s successes.<br />

Heating, ventilation, air conditioning, cooling, electricity and room automation<br />

– <strong>SAUTER</strong> is ready to of fer its exper tise in the for m of optimised solutions for<br />

every challenge in building automation. All our past projects and development<br />

experience enrich the extensive knowledge database for our <strong>SAUTER</strong> CASE<br />

Suite engineering software. By drawing on this focused solution exper tise, it<br />

is a simple task for us to develop automation processes and <strong>com</strong>ponents that<br />

achieve the best possible result for your individual terms of reference. As well<br />

as standardised solutions for HVAC, electricity and room automation, <strong>SAUTER</strong><br />

also integrates the sanitary, smoke clearance and fire protection sectors with the<br />

help of our vast stock of experience. From Day 1 of the planning phase, <strong>SAUTER</strong><br />

is your experienced solution provider whenever you need energy-efficient and<br />

cost-effective building automation that will reliably cope with the challenges of<br />

the future.<br />

<strong>SAUTER</strong> CASE Suite<br />

26


1, 2<br />

3<br />

5, 8, 11<br />

9, 12<br />

4 6<br />

7<br />

10, 13<br />

15,16<br />

17, 19<br />

14<br />

18, 20, 22 21<br />

Energy-eff cient solution <strong>com</strong>petence for heating:<br />

Example 2 – moduTherm3220.<br />

Nr. Description Position Type PDS Page<br />

1 Touch Panel (colour) - moduNet <strong>EY</strong>-OP250F001 132<br />

2 Touch Panel (b/w) - moduNet <strong>EY</strong>-OP250F002 132<br />

3 modu200 <strong>EY</strong>-AS200F001 120<br />

4 Outdoor temperature detector (wall-mounted) B1 EGT301F101 36.016<br />

5 Stem-type detector Heating circuit flow temperature B2, B3 EGT346F101 36.036<br />

6 Clamp-on detector Heating circuit flow temperature B2, B3 EGT311F101 36.021<br />

7 Solar collector temperature cable detector B4 EGT356F101 36.044<br />

8 Heat exchanger primary return temperature stem-type detector B5 EGT346F101 36.036<br />

9 Boiler temperature upper stem-type detector B6 EGT347F101 36.036<br />

10 Boiler temperature upper stem-type detector B6 EGT348F101 36.036<br />

11 Heat exchanger secondary flow temperature stem-type detector B7 EGT346F101 36.036<br />

12 Boiler temperature lower stem-type detector B8 EGT347F101 36.036<br />

13 Boiler temperature lower stem-type detector B8 EGT348F101 36.036<br />

14 Return flow safety temperature limiter max. limit S1 RAK… 21.610<br />

15 Boiler temperature safety monitor S2 RAK82.4/3728M 21.610<br />

16 Underfloor heating circuit temperature safety monitor S3, S4 RAK82.4/3728M 21.610<br />

17 HC regulating valve (3-way) Y1 BXN……F…… 56.456<br />

18 Actuator for heating circuit regulating valve Y1 AVM114SF132 51.362<br />

19 HC regulating valve (3-way) Y2 BXN……F…… 56.456<br />

20 Actuator for heating circuit regulating valve Y2 AVM114SF132 51.362<br />

21 Heat exchanger regulating valve (2-way) Y4 VXN……F…… 56.455<br />

22 Actuator for heat exchanger regulating valve Y4 AVM114SF132 51.362<br />

Parts list excludes required accessories<br />

30 Right of amendment reserved © 2009 F r. Sauter AG


1, 2<br />

5<br />

3 4 6<br />

7<br />

9<br />

11<br />

8<br />

10, 13<br />

12<br />

14 15, 17<br />

16<br />

Energy-eff cient solution <strong>com</strong>petence for heating<br />

and air-conditioning: Example 2 – moduClim2230.<br />

18<br />

Nr. Description Position Type PDS Page<br />

1 Touch Panel (colour) - moduNet <strong>EY</strong>-OP250F001 93.070 132<br />

2 Touch Panel (b/w) - moduNet <strong>EY</strong>-OP250F002 93.070 132<br />

3 modu200 <strong>EY</strong>-AS200F001 92.825 120<br />

4 Outdoor temperature detector (wall-mounted) B1 EGT301F101 36.016<br />

5 Exhaust and supply air detector (air duct) B2, B3 EGT347F101 36.036<br />

6 Air heater return stem-type detector B4 EGT346F101 36.036<br />

7 Air heater return clamp-on detector B4 EGT311F101 36.021<br />

8 Room temperature detector, RAL9010 B5 EGT330F101 36.027<br />

9 Outside-/ exhaust-air damper valve actuator M1, M2 ASM124F122 51.025<br />

10 Filter monitor fine differential pressure controller S1-S3 DDL103F001 23.901<br />

20…300Pa<br />

11 Fan airflow monitor fine differential pressure controller S4, S5 DDL105F001 23.901<br />

50…500Pa<br />

12 Frost protection monitor, continuous S8 TFL611F200 22.040<br />

13 Fine differential pressure controller for HRec anti-icing facility S9 DDL103F001 23.901<br />

20…300Pa<br />

14 Air heater valve (3-way) Y1 BXN……F…… 56.456<br />

15 Air heater valve actuator Y1 AVM114SF132 51.362<br />

16 Air cooler valve (2-way) Y2 VXN……F…… 56.455<br />

17 Air heater valve actuator Y2 AVM114SF132 51.362<br />

18 HRec bypass valve actuator Y3 ASM124SF132 51.023<br />

Parts list excludes required accessories<br />

34 Right of amendment reserved © 2009 F r. Sauter AG


1<br />

4<br />

7<br />

2, 3, 5<br />

6<br />

8, 9<br />

11<br />

10<br />

12, 13<br />

Energy-eff cient solution <strong>com</strong>petence for cooling:<br />

Example 2 – <strong>EY</strong>-<strong>modulo</strong> 2.<br />

Nr. Description Position Type PDS Page<br />

1 Outdoor temperature detector B101 EGT301F101 36.013<br />

2 Stem-type temperature detector B301 EGT346F101 36.036<br />

3 Stem-type temperature detector B201 EGT346F101 36.036<br />

4 Universal thermostat F001 RAK82.4/3773M 21.610<br />

5 Stem-type temperature detector B303 EGT346F101 36.036<br />

6 Valve actuator, position controller Y002 AVM234SF132 51.377<br />

7 3-way flanged valve Y002 BU.. 56.111<br />

8 Stem-type temperature detector B001 EGT347F101 36.036<br />

9 Stem-type temperature detector B003 EGT347F101 36.036<br />

10 Compact Automation Station 42 I/O <strong>EY</strong>-AS210F001 92.815 118<br />

11 Local control unit for <strong>EY</strong>-<strong>modulo</strong> 2 AS <strong>EY</strong>-OP240F001 93.075 134<br />

12 Touch panel colour, 5.7“, for novaNet <strong>EY</strong>-OP250F001 93.070 132<br />

13 Touch panel b/w, 5.7“, for novaNet <strong>EY</strong>-OP250F002 93.070 132<br />

Parts list excludes required accessories<br />

38 Right of amendment reserved © 2009 F r. Sauter AG


1<br />

3<br />

2<br />

4<br />

5<br />

7, 8<br />

6<br />

Energy-eff cient solution <strong>com</strong>petence for electrical:<br />

Example 2 – <strong>EY</strong>-<strong>modulo</strong> 2.<br />

Nr. Description Type PDS Page<br />

1 Automation station, <strong>com</strong>pact <strong>EY</strong>-AS225F001 92.810 116<br />

2 Field module, remote <strong>EY</strong>-FM164F001 92.845 130<br />

3 Field module, remote <strong>EY</strong>-FM165F001 92.840 128<br />

4 Field module, remote <strong>EY</strong>-FM170F001 92.835 126<br />

5 Field module, remote <strong>EY</strong>-FM174F001 92.830 124<br />

6 Local operating unit <strong>EY</strong>-OP240F001 93.075 134<br />

7 T ouch Panel <strong>EY</strong>-OP250F001 93.070 132<br />

8 T ouch Panel <strong>EY</strong>-OP250F002 93.070 132<br />

Parts list excludes required accessories<br />

42 Right of amendment reserved © 2009 F r. Sauter AG


Specimen solution electrical<br />

System design:<br />

• Access and locking control<br />

for entire building<br />

• Equipment alarm display<br />

Electrical:<br />

- Emergency lighting<br />

- Power factor correction<br />

- FI alarm<br />

- Emergency power<br />

- Fire enunciation<br />

Medicinal gases lift:<br />

- Vacuum<br />

- Oxygen<br />

Control functions:<br />

• Time program<br />

• Manual override<br />

• Slat blind control<br />

• Safety functions<br />

(wind, rain…)<br />

• Lighting control<br />

Building 1<br />

Building 2<br />

Building 3<br />

Brief Description:<br />

The system registers, signals and <strong>controls</strong> lighting conditions in an Automation<br />

Station via change-over switches for On/Of f functions. Other<br />

functions activated by light sensors, timer settings and other dependencies<br />

are also definable. The signal from light sensors, one each of which<br />

are preferably installed on the east and west facing facades, will trigger<br />

a change in BMKZ schemati, for instance to provide shade, as soon as<br />

the detected light value exceeds or falls below a specified threshold<br />

value set in the automation station. All operable rooms can remain<br />

unaffected by the light sensors and have their shading BMKZ schematis<br />

set independently of a <strong>com</strong>mand variable signal from the light sensor .<br />

Smoke and heat extraction are controlled by valves depending on safety<br />

functions (wind/rain). A time program can activate all control functions.<br />

Many additional data points may be integrated and processed<br />

by connecting a third-par ty bus system (Modbus, M-Bus, EIB, LON),<br />

which can contribute significantly to energy-ef ficiency.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

43


Specimen solution room automation<br />

Room automation for light and blind control, integrated direct control of lights and blinds by ecos.<br />

The ecos station described here can regulate and control one room unit.<br />

System design:<br />

• Room operating device<br />

• Fancoil Unit (4 wire system),<br />

integrated in the facade<br />

• Dew-point monitor<br />

• Lights<br />

• Blind<br />

• Motion detector<br />

• Window contact<br />

Control functions:<br />

• Presence functions via motion detector<br />

• Switch/dim lights via 0/1-10V<br />

• Blind control (up/ down/shade)<br />

• Window control (open/closed)<br />

• Dew-point monitoring<br />

Regulating functions:<br />

• Temperature control:<br />

- Heating/cooling via fancoil unit<br />

- Supply air temperature via rod sensor<br />

<strong>EY</strong>-<strong>modulo</strong> 2 ecos for 1 room<br />

External Aussenfassade façade<br />

1)<br />

A)<br />

2)<br />

4)<br />

3)<br />

5)<br />

3n 6)<br />

7)<br />

EVG<br />

8)<br />

9)<br />

EVG<br />

8)<br />

LCD<br />

T<br />

10)<br />

Corridor<br />

Flurbereicharea<br />

novaNet<br />

11)<br />

<strong>EY</strong>-<strong>modulo</strong> 2 ecos<br />

A) Fancoll-Unit<br />

Fancoil-Unit<br />

Brief Description:<br />

The system adjusts to the required setpoint (<strong>com</strong>for t, reduced, night)<br />

according to the current operating mode. The motion detector influences<br />

the operating mode (<strong>com</strong>for t/reduced) and room lighting. It<br />

blocks and unblocks automated shading functionality . The supply<br />

air drawn in via the fancoil unit (air intake) is heated or cooled as<br />

required. In addition, an integrated sensor monitors the temperature<br />

and switches the system to frost protection mode if a certain minimum<br />

value is reached. If the window is opened (window contact) whilst the<br />

heating is on, the system will close the heating valve and activate frost<br />

control. The same applies if cooling is activated. The cooling valve in<br />

the fancoil unit closes if dew-point monitoring is switched on and activated.<br />

Lights are switched and dimmed using the operating <strong>controls</strong>.<br />

The lights are activated via an ESC (electronic signal converter) with a<br />

0/1-10V connection. The blinds are closed and opened automatically<br />

according to room conditions; the operating device is equipped with a<br />

manual override function. Blinds are opened and blocked from further<br />

use in the event of a storm hazard or fire. The operating device displays<br />

the following operating situations: operating mode, setpoint correction,<br />

frost monitoring, dew-point hazard, window open. Additionally, the<br />

device can also display the room temperature or the setpoint.<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

47


4<br />

7<br />

12<br />

5, 9<br />

4<br />

13<br />

14<br />

Energy-eff cient solution <strong>com</strong>petence for room automation:<br />

Example 1 – <strong>EY</strong>-<strong>modulo</strong> 5 ecos.<br />

Nr. Description Position Type PDS Page<br />

1 Slat blind actuator (up / down / shade) 1<br />

2 Window motor (open / close) 2<br />

3 Window contact 3<br />

4 Unit valve actuator (continuous) 4 AXS111F… 55.014<br />

5 Unit valve 4 VUL/BUL 55.008/55.009<br />

6 Fan control (3-speed) 5<br />

7 Dew-point monitor 6 EGH102F001 3<strong>4.</strong>042<br />

8 Unit valve actuator (thermal) 7 AXT111F… 55.014<br />

9 Unit valve 7 VUL/BUL 55.008/55.009<br />

10 Lighting control via DALI ballast (EVG) 8<br />

11 Movement detector 9<br />

12 LCD control unit, 4 switching operations 10 <strong>EY</strong>-RU346F001 9<strong>4.</strong>040 74<br />

13 Button unit for control unit, 6 buttons 10 <strong>EY</strong>-SU306F001 9<strong>4.</strong>035 72,140<br />

14 <strong>EY</strong>-<strong>modulo</strong> 5 ecos 11 <strong>EY</strong>-RC502F001 9<strong>4.</strong>110 78<br />

15 BACnet/DALI Gateway 12<br />

16 Light sensor 13<br />

Parts list excludes required accessories.<br />

44 Right of amendment reserved © 2009 F r. Sauter AG


Those who use energy to provide<br />

quality of life and well-being truly deserve<br />

the cachet „Quality – Made in Switzerland“.<br />

<strong>SAUTER</strong>: when the site is clearly an advantage.<br />

We have our heart in the right place. Headquarters, research and development, production<br />

facilities – all are concentrated in Basle in Switzerland. Loyalty to our location, and<br />

solidarity with Swiss virtues are a vital part of what makes <strong>SAUTER</strong> successful. Because<br />

the research, development and production facilities are close together, our products<br />

attain a consistently high quality and we can improve efficiency for our customers.<br />

<strong>SAUTER</strong>: values from Switzerland are taking hold in international markets.<br />

We take natural pride in the ‚Made in Switzerland‘ label on <strong>SAUTER</strong> products and<br />

services. They meet all the relevant standards and are cer tified for use in our target<br />

markets. The label sums up <strong>SAUTER</strong> products and ser vices ver y well: most of our<br />

<strong>com</strong>prehensive range of field equipment is developed and manufactured in Basle. Swiss<br />

quality: helping to achieve maximum efficiency, economy and well-being throughout<br />

the world of building automation.<br />

Every <strong>SAUTER</strong> product helps to care for the environment in some way.<br />

Sustainability and responsibility: these are the key propositions behind our products and<br />

services. All our <strong>com</strong>ponents are made from environmentally-<strong>com</strong>patible raw materials,<br />

using eco-friendly processes. For example, we use only materials that can be readily<br />

recycled at the end a long service life. Needless to say, our prime motivators are high<br />

product quality and dependability, plus satisfied customers. This is why ever y item we<br />

make undergoes extensive load and functional tests.<br />

Products<br />

48 Right of amendment reserved © 2009 F r. Sauter AG


Overview <strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 – the highest standard<br />

of functional building management.<br />

I/O modules<br />

Typ<br />

<strong>EY</strong> -IO530F001 <strong>EY</strong>-IO550F001 <strong>EY</strong>-IO551F001 <strong>EY</strong>-IO570F001<br />

Name modu530 modu550 modu551 modu570<br />

Page # 56 58 60 62<br />

Device I/O-Modul Digital/ I/O-Modul Digital I/O-Modul Digital I/O-Modul Analogue<br />

Universal Inputs Outputs (Relays) Outputs (Open-Collector) Outputs, Universal Inputs<br />

For the stations modu525 modu525 modu525 modu525<br />

Inputs digital 8<br />

Inputs universal 8 8<br />

analogue Ni/Pt1000 U/I/Pot Ni/Pt1000 U/I/Pot<br />

digital DI DI<br />

Operation unit optional modu630 modu650 modu630/modu650 modu670<br />

Outputs digital 6 relays (230 V, 2A) 16 (0-I)<br />

dif ferent phases Open-Collector<br />

non-floating<br />

Outputs analogue<br />

4 (0...10 V, push pull<br />

up to 5 mA)<br />

Connection type AS plug-in plug-in plug-in plug-in<br />

Voltage supply from modu525 from modu525 from modu525 from modu525<br />

Control panels<br />

Typ<br />

<strong>EY</strong> -OP840F001 <strong>EY</strong>-LO630F001 <strong>EY</strong>-LO650F001 <strong>EY</strong>-LO650F002 <strong>EY</strong>-LO670F001<br />

Name modu840 modu630 modu650 modu650 modu670<br />

Page # 66 64 64 64 64<br />

Device Operating Unit LED signalling Operating Unit with LED Operating Unit with LED Operating Unit with LED<br />

Function visualization, operation status/alarm 6 HA switch 3 HA switch 4 gate valve<br />

Display plant structure 16 LED 6 DO (A-0-I), incl. LED 3 DO (A-0-I-II), incl. LED AO (A-0...100%), incl. LED<br />

4 LED event/alarm 4 LED event/alarm 8 LED event/alarm<br />

For stations modu525 modu525 modu525 modu525 modu525<br />

For I/O modules – modu530, modu550, modu550, modu551 modu550, modu551 modu570<br />

modu551, modu570<br />

Interfaces I/O-Bus I/O-Bus I/O-Bus I/O-Bus I/O-Bus<br />

Voltage supply from AS from AS od. I/O-Modul from AS od. I/O-Modul from AS od. I/O-Modul from AS od. I/O-Modul<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

51


Freely programmable, individual<br />

room climate with the <strong>SAUTER</strong> ecos.<br />

Room control units<br />

Typ<br />

<strong>EY</strong> -RU310F001 <strong>EY</strong>-RU311F001 <strong>EY</strong>-RU314F001 <strong>EY</strong>-RU316F001<br />

Name ecoUnit310 ecoUnit311 ecoUnit314 ecoUnit316<br />

Page # 76 76 76 76<br />

Use Temperature Temperature Temperature, fan, presence Temperature, fan,<br />

presence, blinds<br />

or light<br />

Display LED LED LED LED<br />

Key functions – Rotary knob Rotary knob + 2 buttons Rotary knob + 4 buttons<br />

Fan stages – – auto - 0 - 1 - 2 - 3 auto - 0 - 1 - 2 - 3<br />

Setpoint correction ±2 K – adjustable adjustable adjustable<br />

Room occupancy – – 3 modes 3 modes<br />

Fan – – 5 modes 5 modes<br />

Sensor NTC <br />

Supply voltage from ecos 5 from ecos 5 from ecos 5 from ecos 5<br />

Room control units<br />

Typ<br />

<strong>EY</strong> -RU110F001 1) <strong>EY</strong> -RU141F001 1) <strong>EY</strong>-RU144F001 1) <strong>EY</strong> -RU146F001 1)<br />

Name ecoUnit110 ecoUnit141 ecoUnit144 ecoUnit146<br />

Page # 68 68 68 68<br />

Use Temperature sensor Temperature sensor Temperature/fan, Temperature/fan,<br />

presence presence/blinds/light<br />

Display – LCD LCD LCD<br />

Data transmission Radio (868,3 MHz) Radio (868,3 MHz) Radio (868,3 MHz) Radio (868,3 MHz)<br />

Key functions – 2 4 6<br />

Fan stages – – auto - 0 - 1 - 2 - 3 auto - 0 - 1 - 2 - 3<br />

Setpoint correction – ±4 K ±4 K ±4 K<br />

Room occupancy – – 3 modes/5 modes 3 modes/5 modes<br />

Sensor NTC NTC NTC NTC<br />

Supply voltage Solar cell Solar cell Solar cell Solar cell<br />

1) Design may differ<br />

52 Right of amendment reserved © 2009 F r. Sauter AG


Specimen solution room automation<br />

Room automation for <strong>com</strong>plex tasks with flexible room partitioning and <strong>com</strong>munication with a<br />

DALI light control system. <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 ecos can control or regulate two functional axes.<br />

A number of functional axes can be <strong>com</strong>bined via further ecos systems to form one room.<br />

System design:<br />

• Room operating device<br />

• Floor convector<br />

• Chilled beams<br />

• Dew-point monitor<br />

• Lights<br />

• Blind<br />

• Motion detector<br />

• Window actuator/contact<br />

Control functions:<br />

• Presence functions via motion detector<br />

• Switch/dim lights via DALI<br />

• Blind control (up/down/shade)<br />

• Window (open/close)<br />

• Window control (open/closed)<br />

• Dew-point monitoring<br />

Regulating functions:<br />

• Temperature control<br />

- Heating via floor convector<br />

- Cooling via chilled beams<br />

<strong>EY</strong>-<strong>modulo</strong> 5 ecos for 2 functional axes<br />

External façade<br />

Aussenfassade<br />

1)<br />

1)<br />

2) 3)<br />

Funktionsachse<br />

Functional axis<br />

3)<br />

Funktionsachse<br />

Functional axis<br />

4) 5)<br />

3n<br />

A) A)<br />

5)<br />

4)<br />

3n<br />

DALI-Bus<br />

12)<br />

Interface<br />

6)<br />

B)<br />

8)<br />

EVG<br />

6)<br />

B)<br />

8)<br />

EVG<br />

13) 13)<br />

EVG<br />

EVG<br />

7)<br />

8)<br />

7)<br />

8)<br />

10)<br />

LCD<br />

T<br />

Corridor Flurbereich area<br />

11)<br />

<strong>EY</strong>-<strong>modulo</strong> 5 ecos<br />

BACnet IP over Ethernet<br />

A) A) Floor Bodenkonvektor convector mit with Gebläse fan B) Kühldeckenelement<br />

B) Chilled beam element<br />

Brief Description:<br />

The system adjusts to the required setpoint (<strong>com</strong>for t, reduced, night)<br />

according to the current operating mode. The motion detector influences<br />

the operating mode (<strong>com</strong>for t/reduced) and room lighting. It<br />

blocks and unblocks automated shading functionality. Heating occurs<br />

via a floor convector with an integrated 3-stage fan. Cooling occurs<br />

via chilled beams in the ceiling. The operating device can be used to<br />

open the window. If the window is opened (window contact) whilst the<br />

heating is on, the system will close the heating valve and activate frost<br />

control. The same applies if cooling is activated. The cooling valve in<br />

the chilled beam ceiling closes if dew-point monitoring is switched on<br />

and activated. Lights are switched and dimmed using the operating<br />

<strong>controls</strong>. A light sensor detects room brightness to enable the regulation<br />

of constant light. Control <strong>com</strong>mands are transferred to a DALI light<br />

control system. The blinds are closed and opened automatically according<br />

to room conditions; the operating device is equipped with a<br />

manual override function. Blinds are opened and blocked from further<br />

use in the event of a storm hazard or fire. The operating device displays<br />

the following operating situations: operating mode, setpoint correction,<br />

frost monitoring, dew-point hazard, window open, blind blocked. It<br />

can also display room temperature or time/date information.<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

45


Product index<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

Automation Station 54 67<br />

Individual room control 68 79<br />

Integration of non-Sauter systems 80 83<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

Automation Station 88 97<br />

Individual room control 98 111<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Automation Station 116 135<br />

Individual room control 136 149<br />

Communication 150 155<br />

Products<br />

Software Management level<br />

novaPro Web 158 159<br />

novaPro Open 160 161<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

49


Overview <strong>EY</strong>-<strong>modulo</strong> 5<br />

Individual room control<br />

<strong>EY</strong>-RU341F001 <strong>EY</strong> -RU344F001 <strong>EY</strong>-RU346F001 <strong>EY</strong>-SU306<br />

ecoUnit341 ecoUnit344 ecoUnit346 ecoUnit306<br />

74 74 74 72, 140<br />

Temperature Temperature, fan, presence Temperature, fan, Control system for lighting and<br />

presence, blinds/light<br />

window blinds<br />

(2 spare places)<br />

LCD LCD LCD –<br />

2 4 6 6<br />

– auto - 0 - 1 - 2 - 3 auto - 0 - 1 - 2 - 3 –<br />

adjustable adjustable adjustable –<br />

– 3 modes 3 modes –<br />

– 5 modes 5 modes –<br />

–<br />

from ecos 5 from ecos 5 from ecos 5 from ecoUnit31./3<strong>4.</strong><br />

Typ<br />

<strong>EY</strong>-RC502F001<br />

Name ecos502<br />

Page # 78<br />

Device<br />

Room Automation Station<br />

Bus BACnet/IP<br />

Room control units 4<br />

Inputs 12<br />

universal inputs 8<br />

Ni/Pt1000, U/R, DI<br />

Digital inputs 4<br />

Over-voltage protection (up to 24 V~)<br />

Objects 30<br />

analogue outputs 4 (0…10 V)<br />

digital outputs<br />

18 (Relay), 8 (Triac)<br />

Objects<br />

Data points up to 256<br />

thereof hardware up to 44<br />

Loop 32<br />

Calendar 16<br />

Schedule 64<br />

Notification Class 16<br />

Supply voltage 230 V~<br />

Dimensions (mm)<br />

299 x 120 x 73 (mm)<br />

553<br />

Right of amendment reserved © 2009 F r. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

Power consumption<br />

Dissipated power<br />

Start-up current<br />

Battery<br />

Capacity<br />

230 V~, ±10%, 50/60 Hz<br />

up to 12 VA (without acces.)<br />

up to 6 W (without acces.)<br />

Softstart<br />

CR2032 pluggable<br />

220 mAh<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Storage and transport -25...70 °C<br />

temperature<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Installation<br />

Mounting<br />

on top-hat rail<br />

Processor-Architektur<br />

Processor<br />

32 Bit, 400 MHz<br />

Dimensions B × H × T (mm) 160 × 170 × 115<br />

Weight (kg) 2,0<br />

SD-RAM (working memory) 32 MB<br />

S-RAM (static memory) 1 MB<br />

Flash<br />

16 MB<br />

Operating system Linux 2.6<br />

Embedded Web Server<br />

User data<br />

via CASE Engine<br />

Local restore data via local operating unit<br />

Interfaces, <strong>com</strong>munication<br />

BACnet-network<br />

1× RJ-45-socket<br />

10/100BASE-Tx 10/100 MBit/s<br />

Communication protocol BACnet/IP<br />

Connection modu840 Integrated interface<br />

Connection modu6 . . Integrated interface<br />

Standards, guidelines and directives<br />

Degree of protection IP 20 (EN 60529) 1)<br />

Protection class I (EN 60730-1)<br />

Environmental class IEC 60721 3K3<br />

CE conformity<br />

Electrical safety EN 60730-1<br />

Directive 2006/95/EG EN 60730-2-9<br />

EN 60950-1<br />

EMC Directive EN 61000-6-1<br />

2004/108/EG EN 61000-6-2<br />

EN 61000-6-4 2)<br />

Software Class A EN 60730-1 Appendix H<br />

Connection for I/O<br />

modules<br />

Integrated I/O bus plug<br />

Additional information<br />

Fitting instructions 0506062<br />

System extension<br />

BACnet objects up to 512<br />

thereof Hardware up to 154<br />

Product Datasheet PDS 92.016<br />

Declaration on materials MD 92.016<br />

and the environment<br />

COV-subscription 1500<br />

Schedule objects 64<br />

Calendar objects 16<br />

Notif cation class objects 16<br />

Loop objects 32<br />

1) only on front with terminal cover, blanking piece for LOI and swing cover (grey).<br />

2) Device of electromagnetic disturbance Class A.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

55


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-IO530: modu530<br />

PDS 92.031<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

I/O Module, Digital and Universal Inputs<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 technology: modular, fast and universal.<br />

Areas of application<br />

To record digital inputs (alarm/status) and analogue inputs (Ni/Pt1000, U/I/R, DI) in technical operat-ing<br />

installations, e.g. in HVAC engineering.<br />

Properties<br />

• Plug-in <strong>com</strong>ponent to extend<br />

automation station modu525<br />

• 16 inputs<br />

• Modular design (base/electronics)<br />

• Voltage supply from automation station modu525<br />

• Direct labelling on front<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

• Can be f tted with local signalling unit (bicolor LED)<br />

Technical description<br />

• 8 digital inputs (alarm/status)<br />

• 8 universal inputs<br />

(Ni/Pt1000, U/I/R (max. 2 I), DI)<br />

Product<br />

Type<br />

<strong>EY</strong>-IO530F001<br />

Designation<br />

I/O module, digital/universal inputs<br />

Accessories<br />

Type Designation Page<br />

Local operating/signalling units<br />

<strong>EY</strong>-LO630F001 16 LED LED signalling (bicolor) 64<br />

Printable front insert<br />

0920000 101 <strong>com</strong>prising 10 sheets of 6 front inserts, perforated, for <strong>EY</strong>-LO630...670<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

56<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Electrical supply<br />

Power consumption 1,6 VA<br />

Current consumption up to 40 mA<br />

Connections<br />

Digital inputs<br />

with f xed assignment<br />

Interface, <strong>com</strong>munication<br />

LO connection (modu6...) 6-pin integrated<br />

I/O bus connection 12-pin integrated<br />

Connection terminals 24<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Storage and transport -25...70 °C<br />

temperature<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Installation<br />

Mounting<br />

on top-hat rail<br />

Dimensions B × H × T (mm) 42 × 170 × 115<br />

Weight (kg) 0,3<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class I (EN 60730-1)<br />

Environmental class IEC 60721 3K3<br />

CE conformity<br />

Directive<br />

73/23/EG EN 60730-1<br />

EN 60730-2-9<br />

EN 60950-1<br />

EMC Directive EN 61000-6-1<br />

2004/108/EG EN 61000-6-2<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Software Class A EN 60730-1<br />

Additional information<br />

Fitting instructions<br />

P100001574<br />

P100001575<br />

Product Datasheet PDS 92.031<br />

Declaration on materials MD 92.031<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

57


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Electrical supply<br />

Power consumption 2,9 VA<br />

Current consumption up to 100 mA<br />

Outputs<br />

Type Relay<br />

Loading<br />

250 V~ / 2 A<br />

Switching operations up to 1 million cycles<br />

Interface, <strong>com</strong>munication<br />

LO connection<br />

6-pin integrated<br />

I/O bus connection 12-pin integrated<br />

Connection terminals 12<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Storage and transport -25...70 °C<br />

temperature<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Installation<br />

Mounting<br />

on top-hat rail<br />

Dimensions B × H × T (mm) 42 × 170 × 115<br />

Weight (kg) 0,3<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class I (EN 60730-1)<br />

Environmental class IEC 60721 3K3<br />

CE conformity<br />

Directive<br />

2006/95/EC EN 60730-1<br />

EN 60730-2-9<br />

2004/108/EC EN 61000-6-1<br />

EN 61000-6-2<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Software Class A EN 60730-1<br />

Additional information<br />

Fitting instructions<br />

P100001574<br />

P100001575<br />

Product Datasheet PDS 92.051<br />

Declaration on materials MD 92.051<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

59


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-IO551: modu551<br />

PDS 92.056<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

I/O Module, Digital Outputs (Open Collector)<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 technology: modular, fast and universal.<br />

Areas of application<br />

Control of actuators such as relays or displays for technical operating installations, e.g. in HVAC engineering.<br />

Properties<br />

• Plug-in <strong>com</strong>ponent to extend<br />

automation station, modu525<br />

• 16 outputs<br />

• Modular design (base/electronics)<br />

• Voltage supply from automation station modu525<br />

• Direct labelling on front<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

• Can be f tted with local signalling unit (bicolor LED)<br />

Technical description<br />

• 16 digital outputs (open collector)<br />

Product<br />

Type<br />

<strong>EY</strong>-IO551F001<br />

Designation<br />

I/O module, digital outputs<br />

Accessories<br />

Type Designation Page<br />

Local operating/signalling units<br />

<strong>EY</strong>-LO630F001 16 LED LED signalling 64<br />

<strong>EY</strong>-LO650F001 6 DO, 4 LED Operating/signalling with LED (auto-0-I) 64<br />

<strong>EY</strong>-LO650F002 3 DO, 4 LED Operating/signalling with LED (auto-0-I-II) 64<br />

Printable front insert<br />

0920000 101 10 sheets of 6 front inserts, perforated, for <strong>EY</strong>-LO630...670<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

60<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Electrical supply<br />

Power consumption<br />

Current consumption<br />

0,7 VA<br />

up to 20 mA<br />

Installation<br />

Mounting<br />

on top-hat rail<br />

Dimensions B × H × T (mm) 42 × 170 × 115<br />

Weight (kg) 0,3<br />

Outputs<br />

Type<br />

Open Collector<br />

Power supply external, positive 24 V=<br />

Loading<br />

up to 100 mA<br />

Outputs switched with respect to earth<br />

Interface, <strong>com</strong>munication<br />

LO connection<br />

6-pin integrated<br />

I/O bus connection 12-pin integrated<br />

Connection terminals 24<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Storage and transport -25...70 °C<br />

temperature<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class I (EN 60730-1)<br />

Environmental class IEC 60721 3K3<br />

CE conformity<br />

EMC Directive<br />

2004/108/EC EN 61000-6-1<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Software Class A EN 60730-1<br />

Additional information<br />

Fitting instructions<br />

P100001574<br />

P100001575<br />

Product Datasheet PDS 92.056<br />

Declaration on materials MD 92.056<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

61


3<br />

5, 7<br />

9<br />

4<br />

6<br />

12<br />

14<br />

Energy-eff cient solution <strong>com</strong>petence for room automation:<br />

Example 2 – <strong>EY</strong>-<strong>modulo</strong> 2 ecos.<br />

Nr. Description Position Type PDS Page<br />

1 Slat blind actuator (up / down / shade) 1<br />

2 Window contact 2<br />

3 Dew-point monitor 3 EGH102F001 3<strong>4.</strong>042<br />

4 Unit valveantrieb (3 Punkt) 4 AXM117F202 55.010<br />

5 Unit valve 4 VUL/BUL 55.006/55.007<br />

6 Unit valve actuator (thermal) 5 AXT111F202 55.014<br />

7 Unit valve 5 VUL/BUL 55.008/55.009<br />

8 Fan control (3-speed) 6<br />

9 Supply air cable-type temperature detector 7 EGT354F101 36.044<br />

10 Lighting control via electronic ballast (EVG) with 8<br />

0/1-10V connection (for dimming)<br />

11 Movement detector 9<br />

12 LCD control unit, 4 switching operations 10 <strong>EY</strong>-RU246 9<strong>4.</strong>170 138<br />

13 Button unit for control unit, 6 buttons 10 <strong>EY</strong>-SU306 9<strong>4.</strong>035 72/140<br />

14 <strong>EY</strong>-<strong>modulo</strong> 2 ecos 11 <strong>EY</strong>-RC209F001 9<strong>4.</strong>185 142<br />

Parts list excludes required accessories<br />

46 Right of amendment reserved © 2009 F r. Sauter AG


Automation station<br />

Typ<br />

<strong>EY</strong>-AS525F001<br />

Name modu525<br />

Page # 54<br />

Device<br />

Modular AS and Web Server<br />

modu 5<br />

Bus BACnet/IP<br />

Inputs<br />

universal inputs<br />

8 (Ni/Pt1000 U/I/R; Dl)<br />

digital inputs 8<br />

non-floating<br />

<br />

over-voltage protection up to 24 V~<br />

Outputs<br />

analogue outputs<br />

4 (0...10 V) (up to 5 mA)<br />

non-floating<br />

<br />

digital outputs 6 relays (230 V, 2 A)<br />

dif ferent phases<br />

<br />

non-floating<br />

<br />

Watchdog output<br />

1 (Open Collector pulsed)<br />

Objects<br />

Data points up to 512<br />

hardware up to 154<br />

non-Sauter systems up to 256<br />

Loop 32<br />

Calendar 16<br />

Schedule 64<br />

Notification Class 16<br />

Data processing<br />

Control loop scanning time<br />

Interfaces<br />

100 ms<br />

1 Ethernet RJ-45 (10/100 MBit/s)<br />

5<br />

Interfaces for non-Sauter bus<br />

modu710 - (RS232)<br />

Modbus RTU, M-Bus<br />

modu720 - (RS485)<br />

Modbus RTU<br />

Buffer battery period<br />

10 years<br />

Voltage supply 230 V~<br />

50 Right of amendment reserved © 2009 F r. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-AS525: modu525<br />

PDS 92.016<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Modular Automation Station with BACnet/IP and Web server<br />

Your benefit for increased energy efficiency<br />

For individual control and regulating strategies with maximum eff ciency.<br />

Areas of application<br />

Control, monitoring and optimisation of technical operating installations in sectors such as HVAC engineering.<br />

Properties<br />

• Modular automation station<br />

• 16 inputs<br />

• 10 outputs<br />

• Expandable with 8 I/O-modules<br />

for up to 154 inputs/outputs<br />

• Expandable with moduCom modules<br />

for integration of non-Sauter systems<br />

• Direct labelling on front<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

• Communication BACnet/IP (EN ISO 16484 5)<br />

• Integrated Web server<br />

• Programming/parameterisation via PC with<br />

CASE Suite (based on IEC 61131-3)<br />

• Control engineering libraries<br />

• Time and calendar function<br />

• Data recording<br />

• Can be equipped with local<br />

operating/signalling units<br />

Technical description<br />

• 230 V~ voltage supply<br />

• 8 digital inputs (alarm/status)<br />

• 8 universal inputs (Ni/Pt1000,<br />

U/I/R (max. 2 I), DI)<br />

• 4 analogue outputs (0...10 V, up to 5 mA)<br />

• 6 digital outputs (Relais, 230 V~, 2 A)<br />

Product<br />

Type<br />

<strong>EY</strong>-AS525F001<br />

Designation<br />

Automation station with BACnet/IP and integrated Web server<br />

Accessories<br />

Type Designation Page<br />

Plug-in I/O modules (I/O)<br />

<strong>EY</strong>-IO530F001 8 UI / 8 DI Universal-, digital inputs 56<br />

<strong>EY</strong>-IO550F001 6 DO Digital outputs (relays) 58<br />

<strong>EY</strong>-IO551F001 16 DO Digital outputs (open collector) 60<br />

<strong>EY</strong>-IO570F001 8 UI/4 AO Universal inputs/analogue outputs 62<br />

Plug-in <strong>com</strong>munication modules (COM)<br />

<strong>EY</strong>-CM710F… Connection of non-Sauter systems with EIA-232 82<br />

<strong>EY</strong>-CM720F… Connection of non-Sauter systems with EIA-485 80<br />

Local operating/signalling units (LOI)<br />

<strong>EY</strong>-LO630F001 16 LED LED-signalling (bicolor) 64<br />

<strong>EY</strong>-LO650F001 6 DO, 4 LED Operating/signalling with LED (auto-0-I) 64<br />

<strong>EY</strong>-LO650F002 3 DO, 4 LED Operating/signalling with LED (auto-0-I-II) 64<br />

<strong>EY</strong>-LO670F001 4 AO, 8 LED Operating/signalling with LED (A-min..max) 6 4<br />

Local Operating Unit (LOP)<br />

<strong>EY</strong>-OP840F001 Local operating and display unit, modu840 66<br />

54<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-IO550: modu550<br />

PDS 92.051<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

I/O Module, Digital Outputs (Relays)<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 technology: modular, fast and universal.<br />

Areas of application<br />

Control of actuators such as contactors, valve actuators or displays for technical operating installations, e.g.<br />

in HVAC engineering.<br />

Properties<br />

• Plug-in <strong>com</strong>ponent to extend<br />

automation station, modu525<br />

• 6 outputs<br />

• Modular design (base/electronics/relay print)<br />

• Voltage supply from automation station modu525<br />

• Direct labelling on front<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

• Can be equipped with local operating/signalling unit<br />

Technical description<br />

• 6 digital outputs (relays) differing phases,<br />

potential free<br />

Product<br />

Type<br />

<strong>EY</strong>-IO550F001<br />

Designation<br />

I/O module, digital outputs<br />

Accessories<br />

Type Designation Page<br />

Local operating/signalling units<br />

<strong>EY</strong>-LO650F001 6 DO, 4 LED Operating/signalling with LED (auto-0-I) 64<br />

<strong>EY</strong>-LO650F002 3 DO, 4 LED Operating/signalling with LED (auto-0-I-II) 64<br />

<strong>EY</strong>-LO630F001 16 LED LED signalling 64<br />

Printable front insert<br />

0920000 101 10 sheets of 6 front inserts, perforated, for <strong>EY</strong>-LO630...670<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

58<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-IO570: modu570<br />

PDS 92.061<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

I/O Module, Analogue Outputs and Universal Inputs<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 technology: modular, fast and universal.<br />

Areas of application<br />

Control with unit signal (0...10 V), recording of digital inputs (alarm/status), and analogue inputs<br />

(Ni/Pt1000, U/I/Pot) in technical operating installations, e.g. for HVAC engineering.<br />

Properties<br />

Technical description<br />

• Plug-in <strong>com</strong>ponent to extend<br />

• 8 universal inputs<br />

automation station, modu525<br />

(Ni/Pt1000, U/I/R (max. 2 I), DI)<br />

• 8 inputs<br />

• 4 analogue outputs (0...10 V)<br />

• 4 outputs<br />

• Modular design (base/electronics)<br />

• Voltage supply from automation station modu525<br />

• Direct labelling on front<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

• Can be equipped with local operating/signalling unit<br />

Product<br />

Type<br />

<strong>EY</strong>-IO570F001<br />

Designation<br />

I/O module, digital/universal inputs<br />

Accessories<br />

Type Designation Page<br />

Local operating/signalling units<br />

<strong>EY</strong>-LO670F001 4 AO Setpoint adjuster (A, 0...100%) 64<br />

Signalling of manual position<br />

8 LED LED signalling<br />

<strong>EY</strong>-LO630F001 16 LED LED signalling 64<br />

Printable front insert<br />

0920000 101 10 sheets of 6 front inserts, perforated, for <strong>EY</strong>-LO630...670<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

62<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Electrical supply<br />

Power consumption 1,5 VA<br />

Current consumption up to 50 mA<br />

Interface, <strong>com</strong>munication<br />

LO connection<br />

6-pin integrated<br />

I/O bus connection 12-pin integrated<br />

Connection terminals 24<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Storage and transport<br />

temperature -25...70 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Installation<br />

Mounting<br />

on top-hat rail<br />

Dimensions B × H × T (mm) 42 × 170 × 115<br />

Weight (kg) 0,3<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class I (EN 60730-1)<br />

Environmental class IEC 60721 3K3<br />

CE conformity<br />

EMC Directive<br />

2004/108/EC EN 61000-6-1<br />

EN 61000-6-2<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Software Class A EN 60730-1<br />

Additional information<br />

Fitting instructions<br />

P100001574<br />

P100001575<br />

Product Datasheet PDS 92.061<br />

Declaration on materials MD 92.061<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

63


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-LO630…670: modu630…670<br />

PDS 92.081<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Local Operating and Signalling Units<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 technology: modular, fast and universal.<br />

Areas of application<br />

Display for digital inputs (alarm/status), direct control for digital/analogue outputs for automation station<br />

and I/O modules.<br />

Properties<br />

• Plug-in <strong>com</strong>ponents for direct operation/<br />

signalling of automation station modu525<br />

and I/O modules<br />

• Direct switch/potentiometer operation<br />

• Signalling with bi-colour LED<br />

• Separate display for manual mode<br />

• Ready to operate with no parameterisation<br />

• Voltage supply from automation station<br />

modu525 or I/O modules<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

Technical description<br />

• <strong>EY</strong>-LO630, 16 LED (bicolor)<br />

• <strong>EY</strong>-LO650F001, 6 Hand-/Auto switches (A-0-I),<br />

4 LED (bicolour)<br />

• <strong>EY</strong>-LO650F002, 3 Hand-/Auto switches (A-0-I-II),<br />

4 LED (bicolour)<br />

• <strong>EY</strong>-LO670, 4 sliding potentiometers<br />

(A-0...100%), 8 LED (bicolor)<br />

Product<br />

Type<br />

<strong>EY</strong>-LO630F001<br />

<strong>EY</strong>-LO650F001<br />

<strong>EY</strong>-LO650F002<br />

<strong>EY</strong>-LO670F001<br />

Designation<br />

LED signalling (16 LED)<br />

Operating/signalling with LED (6x A-0-I; 4x LED)<br />

Operating/signalling with LED (3x A-0-I-II; 4x LED)<br />

Operating/signalling with LED (4x A-0...100%; 8x LED)<br />

Accessories<br />

Type Designation Page<br />

Printable front insert<br />

0920000 101 50 sheets of 6 front inserts, perforated, for <strong>EY</strong>-LO630…670<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

64<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Electrical supply<br />

Power consumption 1 VA<br />

Dissipated power up to 0,3 W<br />

Permissible ambient conditions<br />

Operating temperature 0…45 °C<br />

Storage and transport -25…70 °C<br />

temperature<br />

Humidity<br />

10…85% rh<br />

Non-condensing<br />

Installation<br />

Mounting<br />

direct frontal f tting on AS<br />

Dimensions B × H × T (mm) 42 × 92 × 13<br />

Weight (kg) 0,3...0,4<br />

Delivery<br />

Factory settings<br />

All switches to „A“ (Auto)<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Environmental class IEC 60721 3K3<br />

CE conformity<br />

EMC Directive<br />

2004/108/EC EN 61000-6-1<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Additional information<br />

Fitting instructions 0506057<br />

Product Datasheet PDS 92.081<br />

Declaration on materials MD 92.081<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

65


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-OP840: modu840<br />

PDS 93.015<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Local Operating Unit<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 – the latest technology.<br />

Areas of application<br />

Direct display, navigation and operation for automation stations on site.<br />

Properties<br />

• Plug-in <strong>com</strong>ponent to extend automation station modu525<br />

• Local operating and display unit for direct<br />

local and manual operation of AS modu525<br />

• Intuitive one-knob operation with ‚turn and press‘<br />

• Graphic display with various font sets and types<br />

• Menu-guided navigation with user logon to<br />

authorise operation<br />

• Information is visualised, with structural<br />

display of the installation<br />

• 2 LED indicators for installation alarm and function status<br />

• Display of objects, alarms and further information<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 family<br />

Technical description<br />

• Voltage supply direct from AS<br />

• LCD resolution: 160 x 100 pixels<br />

• 3 different font sizes<br />

• Language can be changed over, choice of<br />

up to 4 languages<br />

• Can be plugged directly onto the <strong>EY</strong>-<strong>modulo</strong><br />

5 automation station<br />

• Remote location possible, for installation in<br />

MCC with accessories<br />

Product<br />

Type<br />

<strong>EY</strong>-OP840F001<br />

Designation<br />

Local operating unit for <strong>EY</strong>-<strong>modulo</strong> 5 AS<br />

Accessories<br />

Type Designation Page<br />

Operating Instructions<br />

7001007 00x modu840 (languages: x=1 (German), x=2 (French), x=3 (English))<br />

1)<br />

Mounting<br />

0930240511 MCC installation kit with one RJ-11 cable (6 m) – quadruple,<br />

1)<br />

with 2 blanking pieces<br />

1) Please refer to product datasheet (PDS) for further information.<br />

66<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

Power consumption<br />

from AS<br />

up to 50 mA<br />

Installation<br />

Dimensions B × H × T (mm) 186 × 120 × 73<br />

Weight (kg) 0,11<br />

Display<br />

LCD (B x H)<br />

160 x 100 pixel<br />

Font types<br />

8 pt, 11 pt, 13 pt, 34 pt<br />

Operation<br />

„Turn & Press“<br />

Rotary knob<br />

+ / - ; down / up<br />

with conf rmation OK (short), Start (long >3 s)<br />

Interfaces, <strong>com</strong>munication<br />

direct connection to AS 5-pin spring pins<br />

for supply and<br />

data <strong>com</strong>munication<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Storage and transport -20...65 °C<br />

temperature<br />

Humidity<br />

10...85% rh<br />

Non-condensing<br />

Standards, guidelines and directives<br />

Degree of protection IP 20 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Environmental class IEC 60721 3K3<br />

CE conformity as per:<br />

EMC Directive<br />

2004/108/EC EN 61000-6-1<br />

EN 61000-6-2<br />

EN 61000-6-4 1)<br />

Additional information<br />

Fitting instructions<br />

P100002318<br />

Product Datasheet PDS 93.015<br />

Declaration on materials MD 93.015<br />

and the environment<br />

1) Device of electromagnetic disturbance Class A.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

67


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Functionality<br />

Transmission interval On keystroke<br />

Energy supply via <strong>EY</strong>-RU1 . .<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Installation<br />

Weight (kg) 0,1<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Environmental class IEC 60721 3K3<br />

Additional information<br />

Fitting instructions<br />

P100002472<br />

Product Datasheet PDS 9<strong>4.</strong>025<br />

Declaration on materials MD 9<strong>4.</strong>025<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

71


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-RU110...146: ecoUnit110...146<br />

PDS 9<strong>4.</strong>010<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

<strong>EY</strong>-RU110F001<br />

in Repro<br />

Room Control Unit<br />

Your benefit for increased energy efficiency<br />

Individual adjustment of presence and absence times as well as room setpoint correction, light and<br />

respectively blind control for optimising the room‘s energy consumption.<br />

Areas of application<br />

Operating unit for controlling and ensuring absolute room <strong>com</strong>fort. Temperature detection and control of differently<br />

equipped rooms through <strong>com</strong>municative ecos intelligent unitary controllers.<br />

Properties<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 system family<br />

• Expandable with keypad <strong>EY</strong>-SU106<br />

• Room control unit in many functional,<br />

design and colour variants<br />

• Individual room climate control<br />

• Set the operating mode for room occupancy<br />

and control of a three-stage fan<br />

• Light control, On/Off, dimmer<br />

• Blind control<br />

• Display<br />

• Expandable with keypad <strong>EY</strong>-SU106<br />

Technical description<br />

• Voltage supply from integrated solar cell<br />

• Battery option available<br />

• EnOcean ® radio protocol<br />

• Range approx. 30 m depending on<br />

building fabric<br />

Product<br />

Type Designation<br />

<strong>EY</strong>-RU110F001 2)<br />

<strong>EY</strong>-RU141F001 2)<br />

<strong>EY</strong>-RU144F001 2)<br />

<strong>EY</strong>-RU146F001 2)<br />

Operating unit, NTC sensor<br />

Operating unit with LCD, NTC, dXs setpoint adjuster, 2 keys<br />

Operating unit with LCD, NTC, dXs, fan, presence, 4 keys<br />

Operating unit with LCD, NTC, dXs, fan, presence, lighting/window blinds, 6 keys<br />

Accessories<br />

Type Designation Page<br />

Operation<br />

<strong>EY</strong>-SU106 Keypad without frame 70<br />

Mounting<br />

094 0240101 Frame, single, incl. f xing plate (for recessed junction box, 10 units)<br />

1)<br />

094 0240201 Frame, double, incl. f xing plate (for recessed junction box, 10 units)<br />

1)<br />

094 0240301 Plinth, single, (for wall mounting, 10 units)<br />

1)<br />

094 0240401 Plinth, double, (for wall mounting, 10 units)<br />

1)<br />

094 0240501 Cable cover, single, (for wall mountd cable feed, 10 units)<br />

1)<br />

094 0240601 Cable cover, double, (for wall mounted cable feed, 10 units)<br />

1)<br />

094 0240701 Fixing plate, single, (for non-Sauter frames, 10 units)<br />

1)<br />

094 0240801 Fixing plate, double, (for non-Sauter frames, 10 units)<br />

1)<br />

094 9241301 Cover, transparent, single (10 units)<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

2) Design may differ.<br />

68<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-SU306: ecoUnit306<br />

PDS 9<strong>4.</strong>035<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Switching Unit for Room Control Unit<br />

Your benefit for increased energy efficiency<br />

Control lights and blinds to optimise the room‘s energy consumption.<br />

<strong>EY</strong>-SU106F001<br />

01<br />

Areas of application<br />

Switching unit in conjunction with ecoUnit2 and ecoUnit3 for controlling lights, blinds, etc. via <strong>EY</strong>-<strong>modulo</strong> 2ecos/<br />

<strong>EY</strong>-<strong>modulo</strong> 5 ecos <strong>com</strong>municative intelligent unitary controllers.<br />

Properties<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 and 5 system family<br />

• Keypad for extending the ecoUnit3/ecoUnit2<br />

(<strong>EY</strong>-RU3 . . /<strong>EY</strong>-RU2 . . )<br />

• Switching unit in many functional,<br />

design and colour variants<br />

• Lamp control and dimming<br />

• Blind control<br />

Technical description<br />

• Voltage supply from ecoUnit3 or ecoUnit2<br />

• Connection 2-core<br />

• Keypad with 6 key functions<br />

Product<br />

Type<br />

<strong>EY</strong>-SU306F001<br />

Designation<br />

Keypad for 6 key functions<br />

Accessories<br />

Type Designation Page<br />

Mounting<br />

094 0240101 Frame, single, incl. f xing plate (for recessed junction box, 10 units)<br />

1)<br />

094 0240201 Frame, double, incl. f xing plate (for recessed junction box, 10 units)<br />

1)<br />

094 0240301 Plinth, single, (for wall mounting, 10 units)<br />

1)<br />

094 0240401 Plinth, double, (for wall mounting, 10 units)<br />

1)<br />

094 0240501 Cable cover, single, (for wall mounted cable feed, 10 units)<br />

1)<br />

094 0240601 Cable cover, double, (for wall mounted cable feed, 10 units)<br />

1)<br />

094 0240701 Fixing plate, single, (for non-Sauter frames, 10 units)<br />

1)<br />

094 0240801 Fixing plate, double, (for non-Sauter frames, 10 units)<br />

1)<br />

094 9241301 Plexiglas blind cover, single (10 units)<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

72<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Electrical supply<br />

Voltage supply from ecos 5<br />

Installation<br />

Weight (kg) 0,1<br />

Sensor<br />

Measurement range 0...40 °C<br />

Resolution<br />

0,1 K<br />

Functionality<br />

Setpoint correction Adjustable<br />

Room occupancy 3 modes<br />

Fan stages<br />

5 functions<br />

Position LED<br />

green<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Environmental class IEC 60721 3K3<br />

CE conformity as per:<br />

EMC directive<br />

2004/108/EC EN 61000-6-1<br />

EN 61000-6-2<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Connection<br />

Cable<br />

4-core<br />

Length (to <strong>EY</strong>-RU)<br />

up to 100 m<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Additional information<br />

Fitting instructions<br />

P100001966<br />

Product Datasheet PDS 9<strong>4.</strong>040<br />

Declaration on materials MD 9<strong>4.</strong>040<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

75


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-RU310...316: ecoUnit310…316<br />

PDS 9<strong>4.</strong>051<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Room Control Unit for ecos<br />

Your benefit for increased energy efficiency<br />

Individual adjustment of presence and absence times as well as room setpoint correction, light and blind<br />

control for optimising the room‘s energy consumption.<br />

<strong>EY</strong>-SU106F001<br />

01<br />

Areas of application<br />

Operating unit for controlling and ensuring absolute room <strong>com</strong>fort. Temperature detection and control of differently<br />

equipped rooms via <strong>EY</strong>-<strong>modulo</strong> 5 ecos <strong>com</strong>municative intelligent unitary controllers.<br />

Properties<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 system family<br />

• Room control unit in many functional,<br />

design and colour variants<br />

• Expandable with Keypad <strong>EY</strong>-SU306<br />

• Individual room climate control<br />

• Setting the operating mode for room<br />

occupancy and control of a three-stage fan<br />

• Lamp control and dimming<br />

• Blind control<br />

Technical description<br />

• Voltage supply from ecos 3<br />

• Sub bus RS485, Protocol SLC<br />

Product<br />

Type<br />

<strong>EY</strong>-RU310F001<br />

<strong>EY</strong>-RU311F001<br />

<strong>EY</strong>-RU314F001<br />

<strong>EY</strong>-RU316F001<br />

Designation<br />

Control unit, NTC sensor<br />

Control unit, NTC sensor, dXs setpoint adjuster (rotary knob)<br />

Control unit, NTC, dXs, fan, presence, rotary knob with 2 buttons<br />

Control unit, NTC, dXs, fan, presence, rotary knob with 4 buttons<br />

Accessories<br />

Type Designation Page<br />

Operating<br />

<strong>EY</strong>-SU306 Keypad, without frame 72<br />

Mounting<br />

094 0240101 Frame, single, incl. f xing plate (for recessed junction box, 10 units)<br />

1)<br />

094 0240201 Frame, double, incl. f xing plate (for recessed junction box, 10 units)<br />

1)<br />

094 0240301 Plinth, single, (for wall mounting, 10 units)<br />

1)<br />

094 0240401 Plinth, double, (for wall mounting, 10 units)<br />

1)<br />

094 0240501 Cable cover, single, (for wall mounted cable feed, 10 units)<br />

1)<br />

094 0240601 Cable cover, double, (for wall mounted cable feed, 10 units)<br />

1)<br />

094 0240701 Fixing plate, single, (for non-Sauter frames, 10 units)<br />

1)<br />

094 0240801 Fixing plate, double, (for non-Sauter frames, 10 units)<br />

1)<br />

094 9241301 Plexiglas blind cover, single (10 units)<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

76<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Functionality<br />

Radio technology<br />

Transmission frequency<br />

Range<br />

EnOcean ® (STM/PTM)<br />

868,3 MHz<br />

Appr. 30 m inside building<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Measurement value logging Every 100 seconds<br />

Transmission interval Every 100 seconds,<br />

if change > 0,8 K<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Electrical supply<br />

Solar cell, maintenance-free<br />

Installation<br />

Environmental class<br />

Additional information<br />

Fitting instructions<br />

IEC 60721 3K3<br />

P100002468<br />

Weight (kg) 0,1<br />

Product Datasheet PDS 9<strong>4.</strong>010<br />

Declaration on materials MD 9<strong>4.</strong>010<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

69


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Functionality<br />

Position LED<br />

green<br />

Installation<br />

Weight (kg) 0,1<br />

Connection<br />

Cable<br />

2-core<br />

Length (to <strong>EY</strong>-RU)<br />

up to 30 m<br />

Permissible ambient conditions<br />

Operating temperature 5...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Additional information<br />

Fitting instructions<br />

P100001963<br />

Product Datasheet PDS 9<strong>4.</strong>035<br />

Declaration on materials MD 9<strong>4.</strong>035<br />

and the environment<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Environmental class IEC 60721 3K3<br />

CE conformity as per:<br />

EMC directive<br />

2004/108/EC EN 61000-6-1<br />

EN 61000-6-2<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

73


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Electrical supply<br />

Voltage supply from ecos 5<br />

Installation<br />

Weight (kg) 0,1<br />

Sensor<br />

Measurement range 0...40 °C<br />

Resolution<br />

0,1 K<br />

Connection<br />

Cable<br />

4-core<br />

Length<br />

up to 30 m<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Environmental class IEC 60721 3K3<br />

CE conformity as per:<br />

EMC directive<br />

2004/108/EC EN 61000-6-1<br />

EN 61000-6-2<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Additional information<br />

Fitting instructions<br />

P100001964<br />

Product Datasheet PDS 9<strong>4.</strong>051<br />

Declaration on materials MD 9<strong>4.</strong>051<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

77


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Electrical supply<br />

Voltage supply 230 V~<br />

Power consumption 30 VA (incl. 24 VA external)<br />

Dissipated power 6 W<br />

Battery Lithium<br />

(Pufferung RTC)<br />

(CR2032 pluggable)<br />

Inputs<br />

Operating unit<br />

4 x <strong>EY</strong>-RU3…<br />

Universal inputs<br />

8 x Ni/Pt1000, U/(I)/R,<br />

DI, Pot<br />

Digital inputs<br />

4 x on/off<br />

Outputs<br />

Triac switching outputs 4x 0-I-II (24V~, 0,5 A)<br />

Relay switching outputs 2x NO (250 V~, 10 A)<br />

(start-up current 80 A) 4x NO (250 V~, 1 A)<br />

Relay switching outputs 10x NO (250 V~, 1 A)<br />

2x Change-over (250 V~, 1 A)<br />

Analogue<br />

4 x 0…10 V (load >5 kΩ)<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Installation<br />

Weight (kg) 2,5<br />

Standards, guidelines and directives<br />

Degree of protection IP 20 (EN 60730)<br />

Protection class I (EN 60730)<br />

Environmental class IEC 60731-3-3 3K3<br />

Electrical safety EN 60730-1<br />

CE conformity as per:<br />

Directive 2006/95/EC EN 60730-2-9<br />

EN 60950-1<br />

EMC Directive<br />

2004/108/EC EN61000-6-1<br />

EN61000-6-2<br />

EN61000-6-4 1)<br />

Software Class A EN 60730-1 Appendix H<br />

Additional information<br />

Fitting instructions<br />

P100002325<br />

Product Datasheet PDS 9<strong>4.</strong>110<br />

Declaration on materials MD 9<strong>4.</strong>110<br />

and the environment<br />

1) Device of electromagnetic disturbance Class A.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

79


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-CM720: modu720<br />

PDS 97.011<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Communication Module moduCom with EIA-485<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 Technology modular, fast and universal.<br />

Areas of application<br />

Inclusion of non-Sauter systems and third-party products at automation level on the basis of f eld bus protocols<br />

with EIA-485 such as Modbus/RTU and others.<br />

Integration of third-party products with AS modu525 for integrated control and optimised regulation and the<br />

option of BACnet/IP <strong>com</strong>munication with the management level.<br />

Properties<br />

• Communication module with EIA-485 interface<br />

• Pluggable extension element for the<br />

automation station modu525<br />

• Connection to non-Sauter systems<br />

(SPS, refrigeration plant, <strong>com</strong>pact controllers…)<br />

• Connection for f eld bus protocols on<br />

the basis of RS-485<br />

• Modular design (plinth/electronics)<br />

• Supply voltage provided by<br />

modu525 automation station<br />

• Direct labelling on front side<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

Technical description<br />

• 1 COM modules per AS modu525<br />

• Up to 256 non-Sauter system data points<br />

• 0,3 - 115,2 kBaud<br />

• 2-wire EIA-485 (half-duplex)<br />

• Electrical isolation up to max. 500 V<br />

• 4-pin plug for (A+, A-, GND)<br />

• Supported protocols:<br />

- Modbus/RTU (Master) - F010<br />

others on request<br />

Product<br />

Type<br />

<strong>EY</strong>-CM720F010<br />

Designation<br />

Communication module for Modbus/RTU (Master)<br />

80<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Architecture<br />

Protocol processor 32 Bit, 33 MHz<br />

Memory<br />

2 MBit Flash, 1Mbyte RAM<br />

Data points up to 256<br />

Update rate<br />

up to 100 ms<br />

Installation<br />

Mounting<br />

on top-hat rail<br />

slot 1 on AS<br />

Dimensions B x H x T (mm) 42 x 170 x 115<br />

Weight (kg) 0,1<br />

Electrical supply<br />

Voltage supply<br />

from AS<br />

Power consumption up to 150 mA<br />

(current consumption)<br />

Dissipated power 1,3 W<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Environmental class IEC 60721 3K3<br />

CE conformity as per:<br />

EMC Directive<br />

2004/108/EC EN 61000-6-1<br />

EN 61000-6-2<br />

EN 61000-6-4 1)<br />

Software Class A EN 60730-1 Appendix H<br />

Interfaces, <strong>com</strong>munication<br />

RS-485 interface<br />

4-pin plug terminals<br />

UART: Baud rate 0,3..115,2 kBaud<br />

Data bits 5; 6; 7; 8<br />

Stop bits 1; 1,5; 2<br />

Parity<br />

None, even, odd<br />

Jumper for RS-485 Pull-up, pull-down, line-end<br />

Insulation protect. RS-485 Electrically insulated,<br />

up to 500 V<br />

Connection I/O bus 12-pole, integrated<br />

I/O bus for <strong>EY</strong>-CM 2 MBit/s<br />

Protocol<br />

Modbus/RTU (Master)<br />

Additional information<br />

Fitting instructions<br />

P100002328<br />

Product Datasheet PDS 97.011<br />

Declaration on materials MD 97.011<br />

and the environment<br />

1) Device of electromagnetic disturbance Class A.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

81


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-SU106: ecoUnit106<br />

PDS 9<strong>4.</strong>025<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Keypad for Radio Room Control Unit<br />

Your benefit for increased energy efficiency<br />

Control lights and blinds to optimise the room‘s energy eff ciency.<br />

Areas of application<br />

In connection with ecoUnit1 Switching unit for controlling lights, blinds, etc., via ecos <strong>com</strong>municative<br />

intelligent unitary controllers.<br />

Properties<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 system family<br />

• Keypad for extending the ecoUnit1 (<strong>EY</strong>-RU1 . . )<br />

• Switching unit in many functional,<br />

design and colour variants<br />

• Light control, On/Off, dimmer<br />

• Blind control<br />

Technical description<br />

• Voltage supply from ecoUnit1 (<strong>EY</strong>-RU1 . . )<br />

• Key functions, 6 pcs<br />

Product<br />

Type Designation<br />

<strong>EY</strong>-SU106F001 2)<br />

Keypad for 6 key functions<br />

Accessories<br />

Type Designation Page<br />

Mounting<br />

094 0240101 Frame, single, incl. f xing plate (for recessed junction box, 10 units)<br />

1)<br />

094 0240201 Frame, double, incl. f xing plate (for recessed junction box, 10 units<br />

1)<br />

094 0240301 Plinth, single, (for wall mounting, 10 units)<br />

1)<br />

094 0240401 Plinth, double, (for wall mounting, 10 units)<br />

1)<br />

094 0240501 Cable cover, single, (for wall mounted cable feed, 10 units)<br />

1)<br />

094 0240601 Cable cover, double, (for wall mounted cable feed, 10 units)<br />

1)<br />

094 0240701 Fixing plate, single, (for non-Sauter frames, 10 units)<br />

1)<br />

094 0240801 Fixing plate, double, (for non-Sauter frames, 10 units)<br />

1)<br />

094 9241301 Cover, transparent (10 units)<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

2) Design may differ.<br />

70<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-RU341…346: ecoUnit341…346<br />

PDS 9<strong>4.</strong>040<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Room Control Unit for ecos<br />

Your benefit for increased energy efficiency<br />

Individual adjustment of presence and absence times as well as room setpoint correction, light and blind<br />

control for optimising the room‘s energy consumption.<br />

<strong>EY</strong>-SU106F001<br />

01<br />

Areas of application<br />

Operating unit for controlling and ensuring absolute room <strong>com</strong>fort. Temperature detection and control of differently<br />

equipped rooms via <strong>EY</strong>-<strong>modulo</strong> 5 ecos <strong>com</strong>municative intelligent unitary controllers.<br />

Properties<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 system family<br />

• Expandable with keypad <strong>EY</strong>-SU306<br />

• Room control unit in many functional,<br />

design and colour variants<br />

• Individual room climate control<br />

• Setting the operating mode for room<br />

occupancy and control of a three-stage fan<br />

• Lamp control and dimming<br />

• Blind control<br />

• Display with <strong>com</strong>prehensive<br />

status information on room conditions<br />

Technical description<br />

• Voltage supply from ecos3<br />

• Sub bus RS485, Protocol SLC<br />

Product<br />

Type Designation<br />

<strong>EY</strong>-RU341F001<br />

<strong>EY</strong>-RU344F001<br />

<strong>EY</strong>-RU346F001<br />

Control unit, NTC sensor, dXs setpoint adjuster, 2 buttons<br />

Control unit, NTC, dXs, fan, presence, 4 buttons<br />

Control unit, NTC, dXs, fan, presence, lighting or window blinds, 6 buttons<br />

Accessories<br />

Type Designation Page<br />

Operation<br />

<strong>EY</strong>-SU306 Keypad, without frame 72<br />

Mounting<br />

094 0240101 Frame, single, incl. f xing plate (for recessed junction box, 10 units)<br />

1)<br />

094 0240201 Frame, double, incl. f xing plate (for recessed junction box, 10 units)<br />

1)<br />

094 0240301 Plinth, single, (for wall mounting, 10 units)<br />

1)<br />

094 0240401 Plinth, double, (for wall mounting, 10 units)<br />

1)<br />

094 0240501 Cable cover, single, (for wall mounted cable feed, 10 units)<br />

1)<br />

094 0240601 Cable cover, double, (for wall mounted cable feed, 10 units)<br />

1)<br />

094 0240701 Fixing plate, single, (for non-Sauter frames, 10 units)<br />

1)<br />

094 0240801 Fixing plate, double, (for non-Sauter frames, 10 units)<br />

1)<br />

094 9241301 Plexiglas blind cover, single (10 units)<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

74<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-RC502: ecos502<br />

PDS 9<strong>4.</strong>110<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Room Automation Station<br />

Your benefit for increased energy efficiency<br />

Powerful function modules in ecos502 enable energy-optimised room control and the control of lights and<br />

blinds to ensure minimum energy consumption.<br />

Areas of application<br />

Room automation for temperature control, light and blind control, etc. Integration of non-Sauter trades<br />

via BACnet IP.<br />

Properties<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 system family<br />

• Room automation station for 2 rooms<br />

or 2 functional axes<br />

• Individual room conditioning adjustment<br />

through ecoUnit3 (<strong>EY</strong>-RU3 . . ) room control units<br />

• Optimisation of energy consumption through<br />

presence function, window contact control,<br />

requirements-based fan stage adjustment,<br />

light and blind control, and time-dependent<br />

setpoint adjustment<br />

• Time and calendar function<br />

• Integration in the facility management system<br />

via Ethernet/BACnet/IP data interface<br />

• Programming/parameterisation via PC with<br />

CASE Suite software (as per IEC 61131-3)<br />

Technical description<br />

• Voltage supply 230 V~<br />

• System bus Ethernet, protocol BACnet/IP<br />

Product<br />

Type<br />

<strong>EY</strong>-RC502F001<br />

Designation<br />

Room automation station<br />

Accessories<br />

Type Designation Page<br />

Mounting<br />

090024002 Terminal covers 295 mm (2 units)<br />

1)<br />

090024011 Wiring box 295 mm (2 units)<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

78<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-CM710: modu710<br />

PDS 97.016<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Communication Module moduCom with EIA-232<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 5 Technology modular, fast and universal.<br />

Areas of application<br />

Inclusion of non-Sauter systems and third-party products at automation level on the basis of f eld bus protocols<br />

with EIA-232 such as Modbus/RTU, M-Bus and others.<br />

Integration of third-party products with AS modu525 for integrated control and optimised regulation and the<br />

option of BACnet/IP <strong>com</strong>munication with the management level.<br />

Properties<br />

• Communication module with EIA 232 interface<br />

• Pluggable extension element for the<br />

automation station modu525<br />

• Connection to non-Sauter systems<br />

(SPS, refrigeration plant, counter…)<br />

• For point-to-point protocols<br />

• Connection for f eld bus protocols<br />

with optional level converter<br />

(RS 232 M-Bus, RS 232 RS 485)<br />

• Modular design (plinth/electronics)<br />

• Supply voltage provided by<br />

modu525 automation station<br />

• Direct labelling on front side<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

Technical description<br />

• Up to 2 COM modules AS modu525<br />

• Up to 256 non-Sauter system data points<br />

• 0,3 - 115,2 kBaud<br />

• DB-9 male (DTE)<br />

• Supported protocols:<br />

- Modbus/RTU (Master) - F010<br />

- M-Bus (RS232) - F020<br />

others on request<br />

Product<br />

Type<br />

<strong>EY</strong>-CM710F010<br />

<strong>EY</strong>-CM710F020<br />

Designation<br />

Communication module for Modbus/RTU (Master)<br />

Communication module for M-Bus (RS232)<br />

Accessories<br />

Type Designation Page<br />

Connecting cables<br />

0386301001 COM DB9(f)-DB9(f) 3 m (zero modem)<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

82<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 5<br />

Technical information<br />

Architecture<br />

Protocol processor 32 Bit, 33 MHz<br />

Memory<br />

2 MBit Flash, 1 Mbyte RAM<br />

Data points up to 256<br />

Updaterate<br />

up to 100 ms<br />

Installation<br />

Mounting<br />

on top-hat rail<br />

slot 1 on AS<br />

Dimensions B x H x T (mm) 42 x 170 x 115<br />

Weight (kg) 0,1<br />

Electrical supply<br />

Voltage supply<br />

from AS<br />

Dissipated power up to 150 mA<br />

(Current consumption)<br />

Dissipated power 2,3 W<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Environmental class IEC 60721 3K3<br />

CE conformity as per:<br />

EMC directive<br />

2004/108/EC EN 61000-6-1<br />

EN 61000-6-2<br />

EN 61000-6-4 1)<br />

Software Class A EN 60730-1 Appendix H<br />

Interfaces, <strong>com</strong>munication<br />

COM interface (DTE) DB-9 plug (male)<br />

UART : Baud rate 0,3..115,2 kBaud<br />

Data bits 5; 6; 7; 8<br />

Stop bits 1; 1,5; 2<br />

Parity<br />

None, even, odd<br />

Connection I/O bus 12-pole, integrated<br />

Protocol F010<br />

Modbus/RTU (Master)<br />

F020<br />

M-Bus (RS232)<br />

Additional information<br />

Fitting instructions<br />

P100002328<br />

Product Datasheet PDS 97.016<br />

Declaration on materials MD 97.016<br />

and the environment<br />

1) Device of electromagnetic disturbance Class A.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

83


Automation station<br />

Typ<br />

<strong>EY</strong> -AS420F001 <strong>EY</strong>-AS421F001<br />

Name modu420 modu421<br />

Page # 92 90<br />

Device Compact Automation Station Compact Automation Station<br />

Bus LON LON<br />

Inputs 6 10<br />

0…10 V, 4…20 mA, 0…10 V, 4…20 mA,<br />

digital, pulse, NTC, PTC, digital, pulse, NTC, PTC,<br />

Ni1000 or potentiometer Ni1000 or potentiometer<br />

counter<br />

counter<br />

Outputs 7 8<br />

universal 2 8<br />

0…10 V linear analogue 0…10 V linear<br />

digital 0/12 V (on/off)<br />

digital 0/12 V (on/off)<br />

or PWM Output<br />

or PWM Output<br />

4<br />

digital 5 –<br />

Triac 1,0 A<br />

supported<br />

LonMark Profile<br />

#0/#1/#3 <br />

#20020/#20100 <br />

#3300 – <br />

#8030 – –<br />

Control loop scanning time 100 ms 100 ms<br />

Interfaces 1 LON jack plug 1 LON jack plug<br />

mono 1/8“ mono 1/8“<br />

2 Scheduler objects <br />

Manual operation – –<br />

Buffer battery period – <br />

Supply voltage 24 V~/= 24 V~/=<br />

84 Right of amendment reserved © 2009 F r. Sauter AG


Overview <strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 4 – Freely programmable<br />

in line with the LonMark standard.<br />

<strong>EY</strong>-AS422F001 <strong>EY</strong> -AS422F002 <strong>EY</strong> -IO471F002 <strong>EY</strong> -AC430F001<br />

modu422 modu422 modu471 modu430<br />

88 88 96 94<br />

Compact Automation Station Compact Automation Station Compact I/O-Module Application Controller<br />

LON LON LON LON<br />

12 12 12 6<br />

0…10 V, 4…20 mA, 0…10 V, 4…20 mA, 0…10 V, 4…20 mA, 0…10 V, 4…20 mA,<br />

digital, pulse, NTC, PTC, digital, pulse, NTC, PTC, digital, pulse, NTC, PTC, digital, pulse, NTC, PTC<br />

Ni1000 or potentiometer Ni1000 or potentiometer Ni1000 or potentiometer or potentiometer<br />

counter counter – –<br />

12 12 12 7<br />

12 12 – 2<br />

analogue 0…10 V linear, analogue 0…10 V linear, 0…10 V linear<br />

4…20 mA 4…20 mA digital 0/12 V (on/off)<br />

digital 0/12 V (on/off) digital 0/12 V (on/off) or PWM Output<br />

or PWM Output<br />

or PWM Output<br />

– – 12 5<br />

Triac 1,0 A<br />

Triac 1,0 A<br />

<br />

– –<br />

– –<br />

– – – <br />

100 ms 100 ms 100 ms 100 ms<br />

1 LON jack plug 1 LON jack plug 1 LON jack plug 1 LON jack plug<br />

mono 1/8“ mono 1/8“ mono 1/8“ mono 1/8“<br />

– –<br />

– – –<br />

– –<br />

24 V~/= 24 V~/= 24 V~ 24 V~<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

85


LON room automation –<br />

room-by-room energy eff ciency.<br />

Room control units<br />

Typ<br />

<strong>EY</strong>-RU481F001 <strong>EY</strong> -RU481F002 <strong>EY</strong> -RU481F003 <strong>EY</strong> -RU482F001 <strong>EY</strong> -RU483F001<br />

Name ecoUnit481 ecoUnit481 ecoUnit481 ecoUnit482 ecoUnit483<br />

Page # 102 102 102 101 100<br />

Use Room temperature Room temperature Room temperature Fan Coil VAV<br />

Display/Set point adjuster – Scale ± Scale 15…27 °C LCD 1) LCD<br />

1)<br />

Input NTC 10 K Ty p 2 NTC 10 K Ty p 2 NTC 10 K Ty p 2 NTC 10 K NTC 10 K<br />

Measurement range -40...150 °C -40...150 °C -40...150 °C 0...70 °C 0...70 °C<br />

Supply voltage 24 V~/= (for LED) 24 V~/= (for LED) 24 V~/= (for LED) 12 V= 12 V=<br />

1) Plaintext display 2-line<br />

Room automation<br />

Typ<br />

<strong>EY</strong>-RC401F001 <strong>EY</strong> -RC402F001 <strong>EY</strong> -RC402F002 <strong>EY</strong> -RC403F001 <strong>EY</strong>-RC403F002<br />

Name ecos401 ecos402 ecos402 ecos403 ecos403<br />

Page # 110 108 108 108 108<br />

Bus LON LON LON LON LON<br />

Functions Fan Coil Fan Coil Fan Coil Fan Coil Fan Coil<br />

LonMark profile #8020 #8501 #8501 #8501 #8501<br />

Radio EnOcean ® – – – <br />

Inputs 6 6 6 6 6<br />

universal 6 6 6 6 6<br />

Outputs 7 8 8 10 10<br />

analogue 2 – – 2 2<br />

0…10 V linear – – 0…10 V linear 0…10 V linear<br />

digital 5 4 4 4 4<br />

Triac 1 A @ 24 V~ relay 230 V, 3 A relay 230 V, 3 A relay 230 V, 3 A relay 230 V, 3 A<br />

4 4 4 4<br />

Triac 1 A @ 230 V~ Triac 1 A @ 230 V~ Triac 1 A @ 230 V~ Triac 1A @ 230 V~<br />

Supply voltage 24 V~ 230 V~ 230 V~ 230 V~ 230 V~<br />

Dimensions (mm) 145 x 120 x 51 196 x 120 x 51 196 x 120 x 51 196 x 120 x 51 196 x 120 x 51<br />

86 Right of amendment reserved © 2009 F r. Sauter AG


Overview <strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-RC415F001 <strong>EY</strong> -RC415F002 <strong>EY</strong> -RC416F001 <strong>EY</strong> -RC416F002<br />

ecos415 ecos415 ecos416 ecos416<br />

106 106 104 104<br />

LON LON LON LON<br />

VAV VAV VAV VAV<br />

#8502 #8502 #8502 #8502<br />

– – <br />

2 2 4 4<br />

2 2 4 4<br />

3 3 6 6<br />

– – 2 2<br />

– – 0…10 V linear 0…10 V linear<br />

2 2 4 4<br />

Triac 0,75 A @ 24 V~ Triac 0,75 A @ 24 V~ Triac 0,75 A @ 24 V~ Triac 0,75 A @ 24 V~<br />

1 1<br />

0...10 V= 0...10 V=<br />

24 V~ 24 V~ 24 V~ 24 V~<br />

195 x 95 x 72 195 x 95 x 72 214 x 123 x 65 214 x 123 x 65<br />

487<br />

Right of amendment reserved © 2009 F r. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 4<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

24 V~/= ±15%, (50/60 Hz)<br />

Power consumption 5 VA (up to 18 VA)<br />

Connections<br />

Inputs universal 10<br />

0…10 V=<br />

4…20 mA<br />

potential free contact<br />

Ni1000<br />

Thermistor Type 2, 3 10 kΩ<br />

RTD 1 kΩ<br />

Potentiometer<br />

Pulse counter 500 ms min.<br />

on/off<br />

Outputs universal 8<br />

0…10 V=<br />

4…20 mA<br />

0...12 V= (on/off)<br />

PWM (adjustable cycle<br />

duration)<br />

Interfaces, <strong>com</strong>munication<br />

Protocol LonTalk ®<br />

Processor<br />

Neuron 3150, 8bits, 10 Mhz<br />

Memory<br />

Non-volatile 64 K<br />

Application<br />

Network<br />

TP/FT-10, 78 Kbps<br />

Clock<br />

Real time Clock<br />

Battery<br />

CR2032 Lithium<br />

Connection LON Audio Jack mono 1/8“<br />

Permissible ambient conditions<br />

Operating temperature 0…70 °C<br />

Storage and transport -20…70 °C<br />

temperature<br />

Humidity<br />

Installation<br />

0…85% rh<br />

Non-condensing<br />

W x H x D (mm) 145 × 120 × 51<br />

Weight (kg) 0,39<br />

Standards, guidelines and directives<br />

CE Emission<br />

EN 55022: 1998 Class B<br />

CE Immunity EN 61000-4-2: 1995,<br />

FCC<br />

UL Listed<br />

Material UL94-5V<br />

Additional information<br />

Fitting instructions<br />

Product Datasheet PDS 92.280<br />

Declaration on materials MD 92.280<br />

and the environment<br />

level 3 in air<br />

EN 61000-4-2: 1995,<br />

level 2 by contact<br />

EN 61000-4-3: 1996, level 2<br />

EN 61000-4-4: 1995, level 2<br />

EN 61000-4-6: 1996, level 2<br />

ENV 50204: 1995, level 2<br />

Device <strong>com</strong>plies with FCC<br />

rules part 15, subpart B,<br />

Class B<br />

UL916<br />

A<br />

P100002336<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

91


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-AS422: modu422<br />

PDS 92.275<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Automation Station<br />

Your benefit for increased energy efficiency<br />

Local plant data logging enables the analysis of energy consumption and ongoing optimisation.<br />

Integrated calendar functionality enables requirement-adapted plant operation with the lowest possible<br />

energy consumption.<br />

Areas of application<br />

Utilisable for various purposes such as fan coil, chill beam control, light control, heat pumps, ventilation<br />

systems or roof-top units.<br />

Properties<br />

• Compact, freely programmable LON automation station<br />

• Supports LonMark object types #0, #1, #3,<br />

#20020, #3300 and #20100<br />

• LonMark certif ed pursuant to Interoperability<br />

Directive Version 3.4<br />

• Separable lower housing for separate installation<br />

of terminals and electronic <strong>com</strong>ponents<br />

• Audio jacks for fast access to the LON network<br />

• LNS plug in for simple function conf guration<br />

• <strong>EY</strong>-AS422F002 with manual operating level for<br />

switching between manual and automatic operation<br />

Technical description<br />

• 24 V~/= Voltage supply<br />

• Universal inputs and outputs conf gurable with<br />

software<br />

• 12 universal inputs<br />

• 12 fused universal outputs<br />

• 2 scheduler objects<br />

• Real Time Clock<br />

• TP/FT 10, 78 Kbps<br />

• Neuron 3150 processor<br />

Product<br />

Type<br />

<strong>EY</strong>-AS422F001<br />

<strong>EY</strong>-AS422F002<br />

Designation<br />

Compact automation station<br />

Compact automation station with manual operation<br />

Accessories<br />

Type Designation Page<br />

Operating device<br />

<strong>EY</strong>-RU481F001 ecos 4 sensor 102<br />

<strong>EY</strong>-RU481F002 ecos 4 sensor, presence 102<br />

<strong>EY</strong>-RU481F003 ecos 4 sensor, presence, setpoint 102<br />

88<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-AS420: modu420<br />

PDS 92.285<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Automation Station<br />

Your benefit for increased energy efficiency<br />

Local plant data logging enables the analysis of energy consumption and ongoing optimisation.<br />

Integrated calendar functionality enables requirement-adapted plant operation with the lowest possible<br />

energy consumption.<br />

Areas of application<br />

Utilizable for various purposes such as fan coil, chill beam control, light control, heat pumps, ventilation systems<br />

or roof-top units.<br />

Properties<br />

• Compact, freely programmable<br />

LON automation station<br />

• Supports LonMark object types #0, #1, #3,<br />

#20020 and #20100<br />

• LonMark certif ed pursuant to Interoperability<br />

Directive Version 3.3<br />

• Separable lower housing for separate installation<br />

of terminals and electronic <strong>com</strong>ponents<br />

• Audio jacks for fast access to the LON network<br />

• LNS plug in for simple function conf guration<br />

Technical description<br />

• 24 V~/= Voltage supply<br />

• Universal inputs and outputs conf gurable with<br />

software<br />

• 6 universal inputs<br />

• 2 fused universal outputs<br />

• 5 Triac outputs<br />

• 2 scheduler objects<br />

• TP/FT 10, 78 Kbps<br />

• Neuron 3150 processor<br />

Product<br />

Type<br />

<strong>EY</strong>-AS420F001<br />

Designation<br />

Compact automation station<br />

Accessories<br />

Type Designation Page<br />

Operating device<br />

<strong>EY</strong>-RU481F001 ecos 4 sensor 102<br />

<strong>EY</strong>-RU481F002 ecos 4 sensor, presence 102<br />

<strong>EY</strong>-RU481F003 ecos 4 sensor, presence, setpoint 102<br />

92<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 4<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

24 V~/= ±15%, (50/60 Hz)<br />

Power consumption 6 VA (up to 15 VA)<br />

Connections<br />

Inputs universal 6<br />

0…10 V=<br />

4…20 mA<br />

potential free contact<br />

Ni1000<br />

Thermistor Type 2, 3 10 kΩ<br />

Potentiometer<br />

Outputs universal 2<br />

0…10 V=<br />

0...12 V= (on/off)<br />

PWM (adjustable cycle<br />

duration)<br />

Outputs digital 5<br />

Triac<br />

1,0 A @ 24 V~ external<br />

supply<br />

Interfaces, <strong>com</strong>munication<br />

Protocol LonTalk ®<br />

Processor<br />

Neuron 3150, 8bits, 10 Mhz<br />

Memory<br />

Non-volatile 64K Application<br />

and conf guration<br />

Network<br />

TP/FT-10, 78Kbps<br />

Connection LON Audio Jack mono 1/8“<br />

Permissible ambient conditions<br />

Operating temperature 0…70 °C<br />

Storage and transport -20…70 °C<br />

temperature<br />

Humidity<br />

0…85% rh<br />

Non-condensing<br />

Installation<br />

W x H x D (mm) 145 × 120 × 51<br />

Weight (kg) 0,35<br />

Standards, guidelines and directives<br />

CE Immunity EN 61000-4-2: 1995,<br />

level 2 by contact<br />

EN 61000-4-3: 1996, level 2<br />

EN 61000-4-4: 1995, level 2<br />

EN 61000-4-6: 1996, level 2<br />

ENV 50204: 1995, level 2<br />

FCC<br />

Device <strong>com</strong>plies with FCC<br />

rules part 15, subpart B,<br />

Class B<br />

UL Listed<br />

UL916<br />

Material UL94-5V<br />

A<br />

Additional information<br />

Fitting instructions<br />

P100002460<br />

Product Datasheet PDS 92.286<br />

Declaration on materials MD 92.286<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

95


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-IO471: modu471<br />

PDS 92.288<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Remote I/O-Module<br />

Your benefit for increased energy efficiency<br />

Accurate capture of plant data and issuance of control signals provides energy-eff cient control<br />

of installations.<br />

Areas of application<br />

Extends the LON network by the stated number of inputs and outputs. The module does not have any inherent<br />

capacity as regards control algorithms, trend memory or scheduler objects.<br />

Properties<br />

• Compact remote I/O module<br />

• Supports the LonMark objects #0, #1 and #3<br />

• LonMark certif ed pursuant to Interoperability<br />

Directive Version 3.4<br />

• Separable lower housing for separate installation<br />

of terminals and electronic <strong>com</strong>ponents<br />

• Audio jacks for fast access to the LON network<br />

• LNS plug-in for simple input and output<br />

conf guration<br />

Technical description<br />

• 24 V~ Voltage supply<br />

• Universal inputs and outputs conf gurable<br />

with software<br />

• 12 universal inputs<br />

• 12 digital outputs<br />

• TP/FT 10, 78 Kbps<br />

• Neuron 3150 processor<br />

Product<br />

Type<br />

<strong>EY</strong>-IO471F002<br />

Designation<br />

Remote I/O-Modul<br />

96<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 4<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

24 V~/= ±15%; 50/60 Hz<br />

Power consumption 8 VA<br />

Display<br />

Type Backlight<br />

Pixels 128 × 128<br />

Image size (mm) 55 × 55<br />

Interfaces, <strong>com</strong>munication<br />

Protocol LonTalk ®<br />

Transceiver FT -X1<br />

Network<br />

TP/FT-10, 78 Kbps<br />

Connection LON Audio Jack mono 1/8“<br />

Permissible ambient conditions<br />

Operating temperature 0…70 °C<br />

Transport and storage -20…70 °C<br />

temperature<br />

Humidity<br />

0…85% rh<br />

Non-condensing<br />

Installation<br />

W x H x D (mm) 116 × 116 × 38<br />

wall mounted<br />

Weight (kg) 0,40<br />

Standards, guidelines and directives<br />

CE Emission<br />

EN 55022: 1998 Class B<br />

CE Immunity EN 61000-4-2: 1995,<br />

level 3 in air<br />

EN 61000-4-2: 1995, level 2<br />

by contact<br />

EN 61000-4-3: 1996, level 2<br />

EN 61000-4-4: 1995, level 2<br />

EN 61000-4-6: 1996, level 2<br />

ENV 50204: 1995, level 2<br />

FCC<br />

Device <strong>com</strong>plies with FCC<br />

rules part 15, subpart B,<br />

Class B<br />

UL Listed<br />

UL916<br />

Material UL94-5V<br />

A<br />

Additional information<br />

Fitting instructions<br />

P100002333<br />

Product Datasheet PDS 93.025<br />

Declaration on materials MD 93.025<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

99


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-RU483: ecoUnit483<br />

PDS 9<strong>4.</strong>090<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

VAV Room Operating Unit<br />

Your benefit for increased energy efficiency<br />

Local presence button for targeted energy saving when the room is not occupied.<br />

Areas of application<br />

Room temperature detection for on-demand control of VAV applications in individual rooms.<br />

Can be used for VAV controllers <strong>EY</strong>-RC415 and <strong>EY</strong>-RC416.<br />

Properties<br />

• Room operating unit for wall surface mounting<br />

• Display unit shows room temperature,<br />

setpoint, fan stage, presence status, outside temp.<br />

• Keys for adjusting temperature setpoint,<br />

presence change-over and menu access<br />

• Usable as a manually operated device for<br />

starting up the volume f ow loop control<br />

• Audio jack plugs for fast access to the<br />

LON network<br />

Technical description<br />

• Temperature sensor in NTC technology<br />

• Two-line LCD text display<br />

• Plastic housing, pure white<br />

Product<br />

Type<br />

<strong>EY</strong>-RU483F001<br />

Designation<br />

VAV room operation unit with display<br />

Technical information<br />

Display<br />

Range<br />

2 rows, 8 characters<br />

Interfaces, <strong>com</strong>munication<br />

Communication<br />

2400 baud serial<br />

Interface 2-core<br />

Protocol<br />

EIA-232<br />

Cable<br />

Length<br />

up to 15 m<br />

Type<br />

22 AWG twisted pair strand<br />

Screening<br />

None<br />

LON Bus Audio Jack mono 1/8“<br />

Functionality<br />

Permissible ambient conditions<br />

Operating temperature 0…70 °C<br />

Transport and storage -20…70 °C<br />

temperature<br />

Humidity<br />

0…85% rh<br />

Non-condensing<br />

Installation<br />

W x H x D (mm) 124 × 85 × 28<br />

Weight (kg) 0,18<br />

Standards, guidelines and directives<br />

CE Immunity EN 61000-4-2: 1995<br />

EN 61000-4-3: 1995<br />

Sensor<br />

10K NTC Thermistor<br />

Range 0...70 °C<br />

Accuracy ±0,2 °C<br />

Resolution 0,1 °C<br />

FCC<br />

UL Listed<br />

Material UL94-V0<br />

EN 61000-4-4: 1995<br />

EN 61000-4-6: 1996<br />

Device <strong>com</strong>plies with FCC<br />

rules part 15, subpart B, Class B<br />

UL-873<br />

Additional information<br />

Fitting instructions<br />

P100002476<br />

Product Datasheet PDS 9<strong>4.</strong>090<br />

Declaration on materials MD 9<strong>4.</strong>090<br />

and the environment<br />

100<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 4<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

24 V~/= ±15%, (50/60 Hz)<br />

Power consumption 5 VA (up to 18 VA)<br />

Connections<br />

Inputs universal 12<br />

0…10 V=<br />

4…20 mA<br />

potential free contact<br />

Ni1000<br />

Thermistor Type 2, 3 10 kΩ<br />

RTD 1 kΩ<br />

Potentiometer<br />

Pulse counter 500 ms min.<br />

on/off<br />

Outputs universal 12<br />

0…10 V=<br />

4…20 mA<br />

0...12 V= (on/off)<br />

PWM (adjustable<br />

cycle duration)<br />

Interfaces, <strong>com</strong>munication<br />

Protocol LonTalk ®<br />

Processor<br />

Neuron 3150, 8bits, 10 Mhz<br />

Memory<br />

Non-volatile 64 K<br />

Application<br />

Network<br />

TP/FT-10, 78 Kbps<br />

Clock<br />

Real time<br />

Battery<br />

CR2032 Lithium<br />

Connection LON Audio Jack mono 1/8“<br />

Permissible ambient conditions<br />

Operating temperature 0…70 °C<br />

Storage and transport -20…70 °C<br />

temperature<br />

Humidity<br />

Installation<br />

0…85% rh<br />

Non-condensing<br />

W x H x D (mm) 196 × 120 × 51<br />

Weight (kg) 0,39<br />

Standards, guidelines and directives<br />

CE Emission<br />

EN 55022: 1998 Class B<br />

CE Immunity EN 61000-4-2: 1995,<br />

FCC<br />

UL Listed<br />

Material<br />

Additional information<br />

Fitting instructions<br />

Product Datasheet PDS 92.275<br />

Declaration on materials MD 92.275<br />

and the environment<br />

level 3 in air<br />

EN 61000-4-2: 1995,<br />

level 2 by contact<br />

EN 61000-4-3: 1996, level 2<br />

EN 61000-4-4: 1995, level 2<br />

EN 61000-4-6: 1996, level 2<br />

ENV 50204: 1995, level 2<br />

Device <strong>com</strong>plies with FCC<br />

rules part 15, subpart B,<br />

Class B<br />

UL916<br />

UL94-5VA<br />

P100002459<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

89


Products <strong>EY</strong>-<strong>modulo</strong> 4<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

24 V~/= ±15%, (50/60 Hz)<br />

Power consumption 6 VA (up to 15 VA)<br />

Connections<br />

Inputs universal 6<br />

0…10 V=<br />

4…20 mA<br />

potential free contact<br />

Ni1000<br />

Thermistor Type 2, 3 10 kΩ<br />

RTD 1 kΩ<br />

Potentiometer<br />

Pulse counter 350 ms min.<br />

on/off<br />

Outputs universal 2<br />

0…10 V=<br />

4…20 mA<br />

0...12 V= (on/off)<br />

PWM (adjustable cycle<br />

duration)<br />

Outputs digital 5<br />

Triac<br />

1,0 A @ 24 V~ external<br />

supply<br />

Interfaces, <strong>com</strong>munication<br />

Protocol LonTalk ®<br />

Processor<br />

Neuron 3150, 8bits, 10 Mhz<br />

Memory<br />

Non-volatile 64 K<br />

Application<br />

Non-volatile 128 K Trend<br />

Network<br />

TP/FT-10, 78 Kbps<br />

Connection LON Audio Jack mono 1/8“<br />

Permissible ambient conditions<br />

Operating temperature 0…70 °C<br />

Storage and transport -20…70 °C<br />

temperature<br />

Humidity<br />

0…85% rh<br />

Non-condensing<br />

Installation<br />

W x H x D (mm) 145 × 120 × 51<br />

Weight (kg) 0,35<br />

Standards, guidelines and directives<br />

CE Emission<br />

EN 55022: 1998 Class B<br />

CE Immunity EN 61000-4-2: 1995,<br />

level 3 in air<br />

EN 61000-4-2: 1995,<br />

level 2 by contact<br />

EN 61000-4-3: 1996, level 2<br />

EN 61000-4-4: 1995, level 2<br />

EN 61000-4-6: 1996, level 2<br />

ENV 50204: 1995, level 2<br />

FCC<br />

Device <strong>com</strong>plies with FCC<br />

rules part 15, subpart B,<br />

Class B<br />

UL Listed<br />

UL916<br />

Material UL94-5V<br />

A<br />

Additional information<br />

Fitting instructions<br />

P100002335<br />

Product Datasheet PDS 92.285<br />

Declaration on materials MD 92.285<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

93


Products <strong>EY</strong>-<strong>modulo</strong> 4<br />

Technical information<br />

Electrical supply<br />

Voltage supply 24 V~<br />

Power consumption 6 VA (up to 15 VA)<br />

Connections<br />

Inputs universal 12<br />

0…10 V=<br />

4…20 mA<br />

potential free contact<br />

Ni1000<br />

Thermistor Type 2, 3 10 kΩ<br />

Potentiometer<br />

Outputs digital 12<br />

Triac<br />

1,0 A @ 24 V= external<br />

supply<br />

PWM (adjustable cycle<br />

duration)<br />

Interfaces, <strong>com</strong>munication<br />

Protocol LonTalk ®<br />

Processor<br />

Neuron 3150, 8bits, 10 Mhz<br />

Memory<br />

Non-volatile 64 K Application<br />

and conf guration<br />

Network<br />

TP/FT-10, 78 Kbps<br />

Connection LON Audio Jack mono 1/8“<br />

Permissible ambient conditions<br />

Operating temperature 0…70 °C<br />

Storage and transport -20…70 °C<br />

temperature<br />

Humidity<br />

0…85% rh<br />

Non-condensing<br />

Installation<br />

W x H x D (mm) 195 × 120 × 51<br />

Weight (kg) 0,39<br />

Standards, guidelines and directives<br />

CE Emission<br />

EN 55022: 1998 Class B<br />

CE Immunity EN 61000-4-2: 1995,<br />

level 3 in air<br />

EN 61000-4-2: 1995,<br />

level 2 by contact<br />

EN 61000-4-3: 1996, level 2<br />

EN 61000-4-4: 1995, level 2<br />

EN 61000-4-6: 1996, level 2<br />

ENV 50204: 1995, level 2<br />

FCC<br />

Device <strong>com</strong>plies with FCC<br />

rules part 15, subpart B,<br />

Class B<br />

UL Listed<br />

UL916<br />

Material UL94-5V<br />

A<br />

Additional information<br />

Fitting instructions<br />

P100002473<br />

Product Datasheet PDS 92.288<br />

Declaration on materials MD 92.288<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

97


Products <strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-RU482: ecoUnit482<br />

PDS 9<strong>4.</strong>095<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Fan Coil Room Operating Unit<br />

Your benefit for increased energy efficiency<br />

Local presence button for targeted energy saving when the room is not occupied.<br />

Areas of application<br />

Room temperature detection for on-demand control of individual rooms. Usable in conjunction with fan coil<br />

controllers <strong>EY</strong>-RC402 and <strong>EY</strong>-RC403.<br />

Properties<br />

• Room operating unit for wall surface mounting<br />

• Display unit shows room temperature, setpoint,<br />

fan stage, presence status<br />

• Keys for adjusting fan stages and<br />

temperature setpoint<br />

• Audio jack plugs for fast access to the<br />

LON network<br />

Technical description<br />

• Temperature sensor in NTC technology<br />

• Two-line LCD text display<br />

• Plastic housing, pure white<br />

Product<br />

Type<br />

<strong>EY</strong>-RU482F001<br />

Designation<br />

Fan coil room operating with display<br />

Technical information<br />

Display<br />

Range<br />

2 rows, 8 characters<br />

Interfaces, <strong>com</strong>munication<br />

LON Bus Audio Jack mono 1/8“<br />

Communication<br />

2400 baud serial<br />

Interface 2-core<br />

Protocol<br />

EIA-232<br />

Cable<br />

Length<br />

up to 15 m<br />

Permissible ambient conditions<br />

Operating temperature 0...50 °C<br />

Transport and storage -30...50 °C<br />

temperature<br />

Humidity<br />

0...85% rh<br />

Non-condensing<br />

Installation<br />

W x H x D (mm) 124 × 85 × 28<br />

Weight (kg) 0,28<br />

Type<br />

Screening<br />

Functionality<br />

22 AWG twisted pair strand<br />

None<br />

Standards, guidelines and directives<br />

CE Immunity EN 61000-4-2: 1995<br />

EN 61000-4-3: 1995<br />

Sensor<br />

10K NTC Thermistor<br />

Range 0...70 °C<br />

Accuracy ±0,2 °C<br />

Resolution 0,1 °C<br />

FCC<br />

UL Listed<br />

Material UL94-V0<br />

EN 61000-4-4: 1995<br />

EN 61000-4-6: 1996<br />

Device <strong>com</strong>plies with FCC<br />

rules part 15, subpart B,<br />

Class B<br />

UL-873<br />

Additional information<br />

Fitting instructions<br />

P100002477<br />

Product Datasheet PDS 9<strong>4.</strong>095<br />

Declaration on materials MD 9<strong>4.</strong>095<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

101


Products <strong>EY</strong>-<strong>modulo</strong> 4<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

103


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-RC416: ecos416<br />

PDS 9<strong>4.</strong>115<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Room Automation Station, VAV Controller<br />

Your benefit for increased energy efficiency<br />

On-demand control of supply-air volume f ow under the utilisation of eff cient control strategies.<br />

CO 2<br />

dependent control for optimum room conditioning with minimum energy costs. Utilisation of<br />

battery-less EnOcean ® radio technology.<br />

Areas of application<br />

Variable VAV control in individual rooms Supports additional functions such as:<br />

• Fan control<br />

• 2-pipe and 4-pipe plants heating/cooling<br />

• Frost-protection function<br />

• Room lighting control<br />

Properties<br />

• Compact LON VAV controller<br />

• Supports the LonMark Functional Prof le #8502<br />

• LonMark certif ed pursuant to Interoperability<br />

Directive Version 3.3<br />

• LNS plug in for simple function conf guration<br />

Technical description<br />

• 24 V~ Voltage supply<br />

• Universal inputs and outputs conf gurable<br />

with software<br />

• 4 universal inputs<br />

• 2 universal outputs<br />

• 4 Triac outputs<br />

• TP/FT 10, 78 KBps<br />

• Neuron 3150 processor<br />

Product<br />

Type<br />

<strong>EY</strong>-RC416F001<br />

Designation<br />

Room automation station, VAV controller<br />

<strong>EY</strong>-RC416F002 Room automation station, VAV controller, EnOcean ®<br />

Accessories<br />

Type Designation Page<br />

Operating device<br />

<strong>EY</strong>-RU483F001 sensor-VAV, display 100<br />

<strong>EY</strong>-RU481F001 sensor 102<br />

<strong>EY</strong>-RU481F002 sensor, presence 102<br />

<strong>EY</strong>-RU481F003 sensor, presence, setpoint 102<br />

104<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 4<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

24 V~ ±15%, 50/60 Hz<br />

Power consumption appr. 5 VA (up to 10…50 VA<br />

if internal power supply for<br />

Triac is used)<br />

Connections<br />

Inputs universal 4<br />

0...10 V=<br />

<strong>4.</strong>..20 mA<br />

Potential free contact<br />

Thermistor Type 2,3 10 kΩ<br />

RTD 1 kΩ<br />

Pt100<br />

Potentiometer<br />

Outputs digital<br />

T riac 4<br />

0,75 A @ 24 V~<br />

Outputs universal 2<br />

0...10 V= linear<br />

0...12 V= digital<br />

PWM up to 20 mA. 600 Ω<br />

Interfaces, <strong>com</strong>munication<br />

Protocol LonTalk ®<br />

Processor<br />

Neuron 3150, 8bits, 10 Mhz<br />

Memory<br />

Non-volatile 64 K Application<br />

and conf guration<br />

Network<br />

TP/FT-10, 78 Kbps<br />

EnOcean ® F002<br />

6 available channels<br />

Radio frequency<br />

868,3 MHz<br />

Differential pressure sensor<br />

Pressure range<br />

0...250 Pa<br />

Accuracy<br />

±3% full scale<br />

Permissible ambient conditions<br />

Operating temperature 0…70 °C<br />

Transport and storage -20…70 °C<br />

temperature<br />

Humidity<br />

Installation<br />

Radio technology<br />

0…85% rh<br />

Non-condensing<br />

F002 EnOcean ®<br />

W x H x D (mm) 214 × 123 × 65<br />

Weight (kg) 1,05<br />

Standards, guidelines and directives<br />

CE Emission<br />

EN 55022: 1998 Class B<br />

CE Immunity EN 61000-4-2: 1995,<br />

FCC<br />

UL Listed<br />

Material UL94-5V<br />

Damper drive<br />

Runtime<br />

Torque<br />

Rotation angle<br />

Damper shaft<br />

Additional information<br />

Fitting instructions<br />

Product Datasheet PDS 9<strong>4.</strong>115<br />

Declaration on materials MD 9<strong>4.</strong>115<br />

and the environment<br />

level 3 in air<br />

EN 61000-4-2: 1995,<br />

level 2 by contact<br />

EN 61000-4-3: 1996, level 2<br />

EN 61000-4-4: 1995, level 2<br />

EN 61000-4-6: 1996, level 2<br />

ENV 50204: 1995, level 2<br />

Device <strong>com</strong>plies with FCC<br />

rules part 15, subpart B,<br />

Class B<br />

UL6EA7<br />

A<br />

120 s<br />

4 Nm<br />

95 ° adjustable<br />

8,5...18,2 mm<br />

P100002343<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

105


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-AS421: modu421<br />

PDS 92.280<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Automation Station<br />

Your benefit for increased energy efficiency<br />

Local plant data logging enables the analysis of energy consumption and ongoing optimisation.<br />

Integrated calendar functionality enables requirement-adapted plant operation with the lowest possible<br />

energy consumption.<br />

Areas of application<br />

Utilisable for various purposes such as fan coil, chill beam control, light control, heat pumps, ventilation<br />

systems or roof-top units.<br />

Properties<br />

• Compact, freely programmable<br />

LON automation station<br />

• Supports LonMark object types #0, #1, #3,<br />

#20020, #3300 and #20100<br />

• LonMark certif ed pursuant to Interoperability<br />

Directive Version 3.4<br />

• Separable lower housing for separate installation<br />

of terminals and electronic <strong>com</strong>ponents<br />

• Audio jacks for fast access to the LON network<br />

• LNS plug in for simple function conf guration<br />

Technical description<br />

• 24 V~/= Voltage supply<br />

• Universal inputs and outputs conf gurable<br />

with software<br />

• 10 universal inputs<br />

• 8 fused universal outputs<br />

• 2 scheduler objects<br />

• Real Time Clock<br />

• TP/FT 10, 78 KBps<br />

• Neuron 3150 Processor<br />

Product<br />

Type<br />

<strong>EY</strong>-AS421F001<br />

Designation<br />

Compact automation station<br />

Accessories<br />

Type Designation Page<br />

Operating device<br />

<strong>EY</strong>-RU481F001 ecos 4 sensor 102<br />

<strong>EY</strong>-RU481F002 ecos 4 sensor, presence 102<br />

<strong>EY</strong>-RU481F003 ecos 4 sensor, presence, setpoint 102<br />

90<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-AC430: modu430<br />

PDS 92.286<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Application Controller<br />

Your benefit for increased energy efficiency<br />

Innovative control algorithms support optimised starting, better load spread and CO 2<br />

-dependent control<br />

systems for maximum energy eff ciency.<br />

Areas of application<br />

The application-specif c control unit utilises various plug-ins to support roof-top units, heat pumps and<br />

ventilation systems.<br />

Properties<br />

• Compact application-specif c LON<br />

automation station<br />

• Supports the LonMark functional prof les #8030<br />

Roof Top Units, #8051 Heat Pump and #8080<br />

Unit Ventilation<br />

• LonMark certif ed pursuant to Interoperability<br />

Directive Version 3.3<br />

• Separable lower housing for separate installation<br />

of terminals and electronic <strong>com</strong>ponents<br />

• Audio jacks for fast access to the LON network<br />

• LNS plug in for simple function conf guration<br />

Technical description<br />

• 24 V~/= Voltage supply<br />

• Universal inputs and outputs conf gurable<br />

with software<br />

• 6 universal inputs<br />

• 5 Triac outputs<br />

• 4 scheduler objects<br />

• 128 k Flash memory for up to 12‘000 event<br />

entries<br />

• TP/FT 10, 78 KBps<br />

• Neuron 3150 processor<br />

Product<br />

Type<br />

<strong>EY</strong>-AC430F001<br />

Designation<br />

Application controller<br />

Accessories<br />

Type Designation Page<br />

Operating device<br />

<strong>EY</strong>-RU481F001 ecos 4 sensor 102<br />

<strong>EY</strong>-RU481F002 ecos 4 sensor, presence 102<br />

<strong>EY</strong>-RU481F003 ecos 4 sensor, presence, setpoint 102<br />

94<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-OP490: modu490<br />

PDS 93.025<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Operating Unit<br />

Your benefit for increased energy efficiency<br />

Calendar functions for optimised operation of LON installations with no additional management level<br />

Real-Time Clock enables daylight-dependent control of lighting in buildings for greater energy savings.<br />

Areas of application<br />

Operation and control of up to 250 data points in LON networks with no management level. Convenient on-site<br />

access to calendar functions. Management of up to 16 different calendars.<br />

Properties<br />

• Compact display with calendar functionality<br />

for wall surface mounting or recessed mounting<br />

• Supports LonMark objects #0, 16 scheduler<br />

object types #20020, real time clock #3300<br />

and display #20010<br />

• Data access can be password-protected<br />

• Audio jack plugs for fast access to the LON network<br />

• LNS plug in for simple function conf guration<br />

Technical description<br />

• Backlit LCD display with 128 x 128 pixels<br />

• 6 keys for navigation and data input<br />

• Battery-buffered real-time clock with a<br />

15-year lifetime<br />

• TP/FT 10, 78 KBps<br />

• Neuron 3150 Processor<br />

• Housing for surface mounting<br />

Product<br />

Type<br />

<strong>EY</strong>-OP490F001<br />

<strong>EY</strong>-OP490F002<br />

Designation<br />

Operating unit with display and calendar, surface mounting<br />

Operating unit with display and calendar, recessed mounting<br />

98<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-RU481: ecoUnit481<br />

PDS 9<strong>4.</strong>100<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Room Operating Unit<br />

Your benefit for increased energy efficiency<br />

Local presence button for targeted energy saving when the room is not occupied.<br />

Areas of application<br />

Room temperature detection for on-demand control of individual rooms. Usable for fan coils, chill beams,<br />

radiators or VAV applications.<br />

Properties<br />

• Room operating unit for wall surface mounting<br />

• Audio jack plugs for fast access to the<br />

LON network<br />

Technical description<br />

• Temperature sensor in NTC technology<br />

• Setpoint adjuster ±6 °C<br />

• Plastic housing, pure white<br />

Product<br />

Type<br />

<strong>EY</strong>-RU481F001<br />

<strong>EY</strong>-RU481F002<br />

<strong>EY</strong>-RU481F003<br />

Designation<br />

Room sensor<br />

Room sensor with LED, presence, warmer/colder<br />

Room sensor with LED, presence, temperature adjustment<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

(for status LED)<br />

F002, F003 24 V~/=<br />

Installation<br />

W x H x D (mm) 124 × 85 × 32,5<br />

Weight (kg) 0,18<br />

Standards, guidelines and directives<br />

Interfaces, <strong>com</strong>munication<br />

UL Listed<br />

UL-873<br />

Connection<br />

LON Audio Jack stereo/<br />

mono 1/8“<br />

Material UL94-V0<br />

Additional information<br />

Permissible ambient conditions<br />

Fitting instructions<br />

P100002478<br />

Operating temperature 0…70 °C<br />

Transport and storage -20…70 °C<br />

temperature<br />

Product Datasheet PDS 9<strong>4.</strong>100<br />

Declaration on materials MD 9<strong>4.</strong>100<br />

and the environment<br />

Humidity<br />

0…85% rh<br />

Non-condensing<br />

102<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-RC415: ecos415<br />

PDS 9<strong>4.</strong>120<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Room Automation Station VAV Light<br />

Your benefit for increased energy efficiency<br />

On-demand control of supply-air volume f ow under the utilisation of eff cient control strategies. CO 2<br />

dependent<br />

control for optimum room conditioning with minimum energy costs. Utilisation of battery-less EnOcean®<br />

radio technology.<br />

Areas of application<br />

Variable VAV control in individual rooms Supports additional functions such as:<br />

• Fan control<br />

• 2-pipe and 4-pipe plants heating/cooling<br />

• Frost-protection function<br />

• Room lighting control<br />

Properties<br />

• Compact LON VAV controller<br />

• Supports the LonMark Functional<br />

Prof le #8502<br />

• LonMark certif ed pursuant to Interoperability<br />

Directive Version 3.3<br />

• LNS plug in for simple function conf guration<br />

Technical description<br />

• 24 V~ Voltage supply<br />

• Universal inputs and outputs conf gurable<br />

with software<br />

• 2 universal inputs<br />

• 3 digital outputs<br />

• TP/FT 10, 78KBps<br />

• Neuron 3150 processor<br />

Product<br />

Type<br />

<strong>EY</strong>-RC415F001<br />

Designation<br />

Room automation station, VAV light<br />

<strong>EY</strong>-RC415F002 Room automation station, VAV light, EnOcean ®<br />

Accessories<br />

Type Designation Page<br />

Operating device<br />

<strong>EY</strong>-RU483F001 sensor-VAV, display 100<br />

<strong>EY</strong>-RU481F001 sensor 102<br />

<strong>EY</strong>-RU481F002 sensor, presence 102<br />

<strong>EY</strong>-RU481F003 sensor, presence, setpoint 102<br />

106<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 4<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

24 V~ ±15%, 50/60 Hz<br />

Power consumption appr. 5 VA (up to 10…50 VA<br />

if internal power supply for<br />

Triac is used)<br />

Connections<br />

Inputs universal 2<br />

0...10 V=<br />

<strong>4.</strong>..20 mA<br />

Potential-free contact<br />

Thermistor Type 2,3 10 kΩ<br />

RTD 1 kΩ<br />

Pt100<br />

Potentiometer<br />

Outputs digital 3<br />

Triac 2<br />

0,75 A @ 24 V~<br />

Digital 1<br />

0...10 V= for<br />

motion detector<br />

Interfaces, <strong>com</strong>munication<br />

Protocol LonTalk ®<br />

Processor<br />

Neuron 3150, 8bits, 10 Mhz<br />

Memory<br />

Non-volatile 64 K Application<br />

and conf guration<br />

Network<br />

TP/FT-10, 78 Kbps<br />

EnOcean ® F002<br />

6 available channels<br />

Radio frequency<br />

868,3 MHz<br />

Differential pressure sensor<br />

Pressure range<br />

0...250 Pa<br />

Accuracy<br />

±3% full scale<br />

Permissible ambient conditions<br />

Operating temperature 0…70 °C<br />

Transport and storage -20…70 °C<br />

temperature<br />

Humidity<br />

Installation<br />

0…85% rh<br />

Non-condensing<br />

W x H x D (mm) 195 × 95 × 72<br />

Weight (kg) 0,8<br />

Standards, guidelines and directives<br />

CE Emission<br />

EN55022: 1998 Class B<br />

CE Immunity EN 61000-4-2: 1995,<br />

FCC<br />

UL Listed<br />

Material UL94-5V<br />

Damper drive<br />

Torque<br />

Runtime for 90°<br />

rotation angle<br />

Rotation angle<br />

Damper shaft<br />

Additional information<br />

Fitting instructions<br />

Product Datasheet PDS 9<strong>4.</strong>120<br />

Declaration on materials MD 9<strong>4.</strong>120<br />

and the environment<br />

level 3 in air<br />

EN 61000-4-2: 1995,<br />

level 2 by contact<br />

EN 61000-4-3: 1996, level 2<br />

EN 61000-4-4: 1995, level 2<br />

EN 61000-4-6: 1996, level 2<br />

ENV 50204: 1995, level 2<br />

Device <strong>com</strong>plies with FCC<br />

rules part 15, subpart B,<br />

Class B<br />

UL6EA7<br />

A<br />

4 Nm<br />

120 s<br />

95 ° adjustable<br />

8,5...18,2 mm<br />

P100002339<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

107


Products <strong>EY</strong>-<strong>modulo</strong> 4<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

24 V~, ±15%, 50/60 Hz<br />

Power consumption 6 VA (up to 15 VA)<br />

Connections<br />

Inputs universal 6<br />

0...10 V=<br />

<strong>4.</strong>..20 mA<br />

Potential-free contact<br />

Thermistor type 2,3 10 kΩ<br />

RTD 1 kΩ<br />

Pt100<br />

Potentiometer<br />

Outputs<br />

digital 5<br />

Triac 1,0 A @ 24 V<br />

universal 2<br />

0...10 V<br />

0/12 V (on/off)<br />

PWM<br />

Interfaces, <strong>com</strong>munication<br />

Protocol LonTalk ®<br />

Processor<br />

Neuron 3150, 8bits, 10Mhz<br />

Memory<br />

Non-volatile 64K Application<br />

and conf guration<br />

Network<br />

TP/FT-10, 78 Kbps<br />

Permissible ambient conditions<br />

Operating temperature 0…70 °C<br />

Transport and storage -20…70 °C<br />

temperature<br />

Humidity<br />

0…85% rh<br />

Non-condensing<br />

Installation<br />

W x H x D (mm) 145 × 120 × 51<br />

Weight (kg) 0,35<br />

Standards, guidelines and directives<br />

CE Emission<br />

EN 55022: 1998 Class B<br />

CE Immunity EN 61000-4-2: 1995,<br />

level 3 in air<br />

EN 61000-4-3: 1996, level 2<br />

EN 61000-4-4: 1995, level 2<br />

EN 61000-4-6: 1996, level 2<br />

ENV 50204: 1995, level 2<br />

FCC<br />

Device <strong>com</strong>plies with FCC<br />

rules part 15, subpart B,<br />

Class B<br />

UL Listed<br />

UL616<br />

Material UL94-5V<br />

A<br />

Additional information<br />

Fitting instructions<br />

P100002340<br />

Product Datasheet PDS 9<strong>4.</strong>147<br />

Declaration on materials MD 9<strong>4.</strong>147<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

111


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-RC402, 403: ecos402, 403<br />

PDS 9<strong>4.</strong>135<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Room Automation Station, Fan Coil, 230 V<br />

Your benefit for increased energy efficiency<br />

On-demand control of fan coil and chill beam applications on the basis of eff cient control strategies.<br />

Utilisation of battery-less EnOcean ® radio technology.<br />

Areas of application<br />

Usable for fan coil or chill beam applications supports:<br />

• 3-stage fan<br />

• 1 elect. reheater<br />

• 2-pipe and 4-pipe plants heating / cooling<br />

• Frost-protection function<br />

• Room lighting control<br />

Properties<br />

• Compact LON fan coil controller<br />

• Supports the LonMark Functional Prof le #8501<br />

• LonMark certif ed pursuant to<br />

Interoperability Directive Version 3.3<br />

• Separable lower housing for separate<br />

installation of terminals and electronic <strong>com</strong>ponents<br />

• Audio jack plugs for fast access to the<br />

LON network<br />

• LNS plug in for simple function<br />

conf guration<br />

Technical description<br />

• 85...265 V~ Voltage supply<br />

• Universal inputs and outputs conf gurable with<br />

software<br />

• 6 universal inputs<br />

• Up to 2 universal outputs<br />

• 4 digital outputs<br />

• 4 relay contacts<br />

• TP/FT 10, 78 KBps<br />

• Neuron 3150 Processor<br />

Product<br />

Type<br />

<strong>EY</strong>-RC402F001<br />

Designation<br />

Room automation station, Fan coil, 230 V<br />

<strong>EY</strong>-RC402F002 Room automation station, Fan coil, 230 V, EnOcean ®<br />

<strong>EY</strong>-RC403F001 Room automation station, Fan coil, 230 V, 2 AO<br />

<strong>EY</strong>-RC403F002 Room automation station, Fan coil, 230 V, EnOcean ® , 2 AO<br />

Accessories<br />

Type Designation Page<br />

Operating device<br />

<strong>EY</strong>-RU482F001 sensor-FCU, display 101<br />

<strong>EY</strong>-RU481F001 sensor 102<br />

<strong>EY</strong>-RU481F002 sensor, presence 102<br />

<strong>EY</strong>-RU481F003 sensor, presence, setpoint 102<br />

108<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Automation station<br />

Type<br />

<strong>EY</strong>-AS200F001 <strong>EY</strong> -AS210F001 <strong>EY</strong> -AS225F001<br />

Name modu200 modu210 modu225<br />

Page # 120 118 116<br />

Device Compact Compact Compact<br />

Automation Station Automation Station Automation Station<br />

Bus novaNet novaNet novaNet<br />

novaLink – – <br />

Inputs 24 28 28…76<br />

analogue 7 (Ni/Pt1000) 8 (Ni/Pt1000) 8 (Ni/Pt1000)<br />

5 (U/Pot/(I)) 6 (U/I/R) 6 (U/I/R)<br />

non-floating <br />

digital 12 12 12<br />

extendable by<br />

48 with moduLink<br />

Pulse counter 2 2 2<br />

Outputs 10 14 1<strong>4.</strong>..26<br />

analogue 4 (0...10V) 6 (0...10V) 6 (0...10V)<br />

2 x 0...20mA 2 x 0...20mA<br />

digital 6 (0-I) 8 (0-I) 8<br />

extendable by<br />

8 (0-I-II) with moduLink<br />

over-voltage protection – – –<br />

Hardware addresses 36 42 102<br />

Software addresses 220 214 154<br />

maximum number 256 256 256<br />

Control loop scanning time 1000 ms 1000 ms 1000 ms<br />

Interface novaNet 1 a/b terminal 1 a/b terminal 1 a/b terminal<br />

modu240 1 RJ-45 1 RJ-45 1 RJ-45<br />

Program storage for<br />

system programs <br />

PROM<br />

2<br />

Program storage for<br />

user programs<br />

PROM <br />

Program storage for<br />

process data, variables<br />

SRAM <br />

Data buffer for power failure 3 years 3 years 3 years<br />

Supply voltage 24 V~/= 24 V~/= 24 V~/=<br />

112 Right of amendment reserved © 2009 F r. Sauter AG


Overview <strong>EY</strong>-<strong>modulo</strong> 2<br />

<strong>EY</strong>-RU241F001 <strong>EY</strong>-RU244F001 <strong>EY</strong> -RU246F001 <strong>EY</strong> -SU306F001<br />

ecoUnit241 ecoUnit244 ecoUnit246 ecoUnit306<br />

138 138 138 72, 140<br />

Temperature, Temperature, presence, Temperature, presence, Control system for lighting and<br />

setpoint correction setpoint correction, fan setpoint correction, fan, window blinds<br />

lighting/window blinds<br />

LCD LCD LCD –<br />

Cable Cable Cable Cable<br />

2 4 6 6<br />

– auto - 0 - 1 - 2 - 3 auto - 0 - 1 - 2 - 3 –<br />

adjustable adjustable adjustable –<br />

– 3 Modi 3 Modi –<br />

NTC NTC NTC –<br />

from ecos 2 from ecos 2 from ecos 2 from ecoUnit216/2<strong>4.</strong><br />

<strong>EY</strong>E206F002 <strong>EY</strong> -RC208F001 <strong>EY</strong>-RC209F001<br />

ecos206 ecos208 ecos209<br />

148 142 142<br />

DDC VAV Controller Room Automation Station Room Automation Station<br />

novaNet novaNet novaNet<br />

8 8 8<br />

1 (<strong>EY</strong>B2../<strong>EY</strong>-RU2..) 1 (<strong>EY</strong>B2../<strong>EY</strong>-RU2..) 1 (<strong>EY</strong>B2../<strong>EY</strong>-RU2..)<br />

2 (Ni1000), 2 (Ni/Pt1000), 2 (Ni/Pt1000),<br />

1 (0…10 V), 1 (0...10 V=), 1 (0...10 V=),<br />

3 (main output contact) 4 (main output contact) 4 (main output contact)<br />

1 (static pressure difference)<br />

6 14 18<br />

2 4 4<br />

3 (0-I-II) Triac, 2 (0-I-II) Triac, 2 (0-I-II) Triac,<br />

1 (0-I) Relay 5 (0-I) Relay 9 (0-I) Relay<br />

1 change-over relay 1 change-over relay<br />

Time and calendar functions, Time and calendar functions, Time and calendar functions,<br />

historic data historic data historic data<br />

24 V~ 230 V~ 230 V~<br />

178 x 103 x 42 244 x 120 x 73 244 x 120 x 73<br />

2115<br />

Right of amendment reserved © 2009 F r. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-AS225: modu225<br />

PDS 92.810<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Automation Station<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 –- Technology proven a thousand times over, with a new design.<br />

For accurate control functions, 24 hours a day!<br />

Areas of application<br />

Control, monitoring and optimisation of technical operating installations in sectors such as HV AC engineering.<br />

Properties<br />

• Compact automation station<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

• 28 inputs<br />

• 14 outputs<br />

• Can be extended to 102 I/O with<br />

moduLink field modules<br />

• Communication: Sauter novaNet<br />

• Programming/parameterisation via PC with<br />

CASE Suite Software (based on IEC 61131-3)<br />

• Control engineering libraries<br />

• Time and calendar function<br />

• Data recording (historical data base)<br />

Technical description<br />

• Voltage supply 24 V~/=<br />

• 12 digital inputs (alarm/status)<br />

• 8 analogue inputs (Ni/Pt1000, U, Pot)<br />

• 6 analogue inputs (U, Pot)<br />

• 2 pulse counters<br />

• 4 analogue outputs (0...10 V)<br />

• 2 analogue outputs (0...10 V/0...20 mA)<br />

• 8 digital outputs (Relays O-I)<br />

• Can be extended to 48 digital inputs with<br />

3 field modules moduLink174<br />

• Can be extended to 8 digital outputs with<br />

2/4 field modules moduLink164, 165<br />

• Can be extended to 4 analogue outputs with<br />

1 field module moduLink170<br />

Product<br />

Type<br />

<strong>EY</strong>-AS225F001<br />

Designation<br />

Compact automation station<br />

Accessories<br />

Type Designation Page<br />

Manual operating unit<br />

<strong>EY</strong>-OP240F001 modu240 134<br />

Connection cable<br />

0367842 002 Automation station - modu240 1,5 m<br />

1)<br />

0367842 003 Automation station - modu240 2,9 m<br />

1)<br />

0367842 004 Automation station - modu240 6,0 m<br />

1)<br />

Field module<br />

<strong>EY</strong>-FM164F001 moduLink164 digital output 4x 0-I (Changeover Relay) 130<br />

<strong>EY</strong>-FM165F001 moduLink165 digital output 2x 0-I-II (Changeover Relay) 128<br />

<strong>EY</strong>-FM170F001 moduLink170 analogue output 4x 0...10 V (2x 0...20 mA) 126<br />

<strong>EY</strong>-FM174F001 moduLink174 digital input 16x 124<br />

Data Memory<br />

0367883 002 PROM memory1Mb empty (USER data) pack à 5 pcs.<br />

1)<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

116<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 4<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

85...265 V~, 50/60 Hz<br />

Power consumption<br />

F001<br />

20 VA<br />

F002<br />

33 VA<br />

Connections<br />

Inputs universal (6x) 0...10 V=<br />

<strong>4.</strong>..20 mA<br />

Potential-free contact<br />

Thermistor Type 2,3 10 kΩ<br />

RTD 1 kΩ<br />

Pt100<br />

Potentiometer<br />

Outputs digital<br />

<strong>EY</strong>-RC402<br />

Relay contact 3<br />

up to 277 V~, 3 A<br />

Relay contact 1<br />

up to 277 V~, 3 A inductive,<br />

10 A resistive<br />

Triac 4<br />

1,0 A<br />

Outputs<br />

<strong>EY</strong>-RC403<br />

Relay contact 3<br />

up to 277 V~, 3 A<br />

Relay contact 1<br />

up to 277 V~, 3 A inductive,<br />

10 A resistive<br />

Triac 4<br />

1,0 A<br />

Universal 2<br />

0...10 V<br />

0/12 V (on/off)<br />

PWM<br />

Permissible ambient conditions<br />

Operating temperature 0…50 °C<br />

Transport and storage -20…70 °C<br />

temperature<br />

Humidity<br />

0…85% rh<br />

Non-condensing<br />

Installation<br />

W x H x D (mm) 195 × 120 × 51<br />

Weight (kg) 0,49<br />

Standards, guidelines and directives<br />

Protection Class<br />

II<br />

CE Electrical Safety EN 61010-1<br />

CE Emission<br />

EN 55022: 1998 Class B<br />

CE Immunity EN 61000-4-2: 1995,<br />

level 3 in air<br />

EN 61000-4-2: 1995,<br />

level 2 by contact<br />

EN 61000-4-3: 1996, level 2<br />

EN 61000-4-4: 1995, level 2<br />

EN 61000-4-6: 1996, level 2<br />

ENV 50204: 1995, level 2<br />

FCC<br />

Device <strong>com</strong>plies with FCC<br />

rules part 15, subpart B,<br />

Class B<br />

UL Listed<br />

UL61010-1<br />

Material UL94-5V<br />

A<br />

Additional information<br />

Fitting instructions<br />

<strong>EY</strong>-RC402, 403 P100002341<br />

Product Datasheet PDS 9<strong>4.</strong>135<br />

Declaration on materials MD 9<strong>4.</strong>135<br />

and the environment<br />

Interfaces, <strong>com</strong>munication<br />

Protocol LonTalk ®<br />

Processor<br />

Neuron 3150, 8bits, 10Mhz<br />

Memory<br />

Non-volatile 64K Application<br />

and conf guration<br />

Network<br />

TP/FT-10, 78 Kbps<br />

EnOcean ® F002<br />

5 available channels<br />

Radio frequency<br />

868,3 MHz<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

109


Overview <strong>EY</strong>-<strong>modulo</strong> 2<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 – thoroughly<br />

tried and tested technology, now with a new design!<br />

Universal controller<br />

Typ<br />

<strong>EY</strong>R203F001<br />

Name moduFlex<br />

Page # 122<br />

Device<br />

Universal Controller<br />

Bus novaNet<br />

Inputs 18<br />

digital<br />

analogue<br />

8 (thereof 2 useable as<br />

pulse counter)<br />

5 (Ni/Pt1000)<br />

5 (0...10 V)<br />

Outputs 8<br />

digital<br />

2 (O-I)<br />

2 (O-I-II)<br />

analogue 4 (0…10 V)<br />

Interfaces<br />

novaNet with auxiliary<br />

module only<br />

a/b terminal<br />

Operating Panel <strong>EY</strong>-OP240 RJ45-socket<br />

Power consumption<br />

10 VA<br />

Voltage supply 24 V~<br />

Field module<br />

Typ<br />

<strong>EY</strong>-FM164F001 <strong>EY</strong>-FM165F001 <strong>EY</strong> -FM170F001 <strong>EY</strong>-FM174F001<br />

Name moduLink164 moduLink165 moduLink170 moduLink174<br />

Page # 130 128 126 124<br />

Device Field Module Digital- Field Module Digital- Field Module Digital- Field Module Digital-<br />

Outputs 0-I Outputs 0-I-II Outputs Inputs<br />

For the stations <strong>EY</strong>-AS225F001 <strong>EY</strong>-AS225F001 <strong>EY</strong>-AS225F001 <strong>EY</strong>-AS225F001<br />

Bus novaLink novaLink novaLink novaLink<br />

Inputs<br />

digital – – – 16 (potential-free)<br />

Outputs 4 2 4 –<br />

analogue – – 4 (0...10 V) or –<br />

2 (0...10 V) and<br />

2 (0...20 mA)<br />

digital 4 (0-I) 2 (0-I-II) – –<br />

Current consumption 150 mA 150 mA 100 mA 120 mA<br />

Power supply from modu225 from modu225 from modu225 from modu225<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

113


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Power supply 24 V~/= (50/60 Hz) ±20%<br />

24 V DC (18...30 V)<br />

Power consumption up to 17 VA<br />

43 VA with f eld modules<br />

Dissipated power up to 8,7 W<br />

23 W with f eld modules<br />

Battery<br />

(buffer: RTC/SRAM) CR2032 plug-in<br />

Interfaces, <strong>com</strong>munication<br />

AS network/novaNet 1 x a/b-terminals<br />

Operating Panel<br />

<strong>EY</strong>-OP240F001<br />

1 x RJ-45-socket<br />

(Languages: German, French, English, Italian, Dutch,<br />

Spanish, Swedish, Norwegian, Danish, Portuguese,<br />

Finnish, Polish, Slovenian, Hungarian, Russian, Rumanian,<br />

Czech, Turkish, Slovakian)<br />

MFA 256<br />

Time <strong>com</strong>mands<br />

320 entries<br />

HDB-entries<br />

digital 2x 3584 (Block 1;3)<br />

analogue 2x 3584 (Block 2;4)<br />

Installation<br />

W x H x D (mm) 300 x 120 x 73<br />

Weight (kg) 0,8<br />

Standards, guidelines and directives<br />

Degree of protection IP 00 (EN 60529) 1)<br />

Protection class I (EN 60730-1)<br />

Environmental class<br />

CE conformity as per:<br />

Additional information<br />

Fitting instructions<br />

Product Datasheet PDS 92.810<br />

Declaration on materials MD 92.810<br />

and the environment<br />

IEC 60721 3K3<br />

Directive 73/23/EWG EN 60730<br />

EMC directive 89/336/EWG EN 61000-6-1<br />

Software Class A<br />

EN 61000-6-2 2)<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

EN 60730-1 Appendix H<br />

P100002323<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Transport and -25...70 °C<br />

storage temperature<br />

Humidity<br />

10...85% rh<br />

Non-condensing<br />

1) Degree of protection IP10 with terminal cover (accessory 0900240001).<br />

2) When the industrial standard EN61000-6-2 has to be fulf lled, the supply cables to the digital inputs (DI), the analogue<br />

inputs/outputs (AI/AO), the meter inputs (CI) and the voltage outputs (5 and 13 V) should not be longer than 30 m.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

117


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Power supply 24 V~ (50/60 Hz) ±20%<br />

24 V= (18...30 V)<br />

Power consumption up to 1<strong>4.</strong>5 VA<br />

Dissipated power up to 7.5 W<br />

Battery<br />

(buffer: RTC/SRAM) CR2032 plug-in<br />

Interfaces, <strong>com</strong>munication<br />

AS-Netzwerk/novaNet 1x a/b-terminals<br />

Operating Panel<br />

<strong>EY</strong>-OP240F001<br />

1x RJ-45-socket<br />

(Languages: German, French, English, Italian, Dutch,<br />

Spanish, Swedish, Norwegian, Danish, Portuguese,<br />

Finnish, Polish, Slovenian, Hungarian, Russian, Rumanian,<br />

Czech, Turkish, Slovakian)<br />

MFA 256<br />

Time <strong>com</strong>mands<br />

320 entries<br />

HDB-entries<br />

digital 2x 3584 (Block 1;3)<br />

analogue 2x 3584 (Block 2;4)<br />

Installation<br />

W x H x D (mm) 300 x 120 x 73<br />

Weight (kg) 0,75<br />

Standards, guidelines and directives<br />

Degree of protection IP 00 (EN 60529) 1)<br />

Protection class I (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

Directive 73/23/EWG EN 60730<br />

EMC directive 89/336/EWG EN 61000-6-1<br />

EN 61000-6-2 2)<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Software Class A<br />

EN 60730-1 Appendix H<br />

Additional information<br />

Fitting instructions<br />

P100002322<br />

Product Datasheet PDS 92.815<br />

Declaration on materials MD 92.815<br />

and the environment<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Transport and -25...70 °C<br />

storage temperature<br />

Humidity<br />

10...85% rh<br />

Non-condensing<br />

1) Degree of protection IP10 with terminal cover (accessory 0900240001).<br />

2) When the industrial standard EN61000-6-2 has to be fulf lled, the supply cables to the digital inputs (DI), the analogue<br />

inputs/outputs (AI/AO), the meter inputs (CI) and the voltage outputs (5 and 13 V) should not be longer than 30 m.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

119


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-AS200: modu200<br />

PDS 92.825<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Automation Station<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 – Technology proven a thousand times over, with a new design<br />

For accurate control functions, 24 hours a day!<br />

Areas of application<br />

Control, monitoring and optimisation of technical operating installations in sectors such as HV AC engineering.<br />

Properties<br />

• Compact automation station<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

• 26 inputs<br />

• 10 outputs<br />

• Communication: Sauter novaNet<br />

• Programming/parameterisation via PC with<br />

CASE Suite Software (based on IEC 61131-3)<br />

• Control engineering libraries<br />

• Time and calendar function<br />

• Data recording (historical data base)<br />

Technical description<br />

• Voltage supply 24 V~/=<br />

• 12 digital inputs (alarm/status)<br />

• 7 analogue inputs (Ni/Pt1000)<br />

• 5 analogue inputs (U, Pot)<br />

• 2 pulse counters<br />

• 4 analogue outputs (0...10 V)<br />

• 6 digital outputs (relays 0-I)<br />

Product<br />

Type<br />

<strong>EY</strong>-AS200F001<br />

Designation<br />

Compact automation station<br />

Accessories<br />

Type Designation Page<br />

Manual operating unit<br />

<strong>EY</strong>-OP240F001 modu240 134<br />

Connection cable<br />

0367842 002 Automation station - modu240 1,5 m<br />

1)<br />

0367842 003 Automation station - modu240 2,9 m<br />

1)<br />

0367842 004 Automation station - modu240 6,0 m<br />

1)<br />

Data Memory<br />

0367883 002 PROM memory1Mb empty (USER data) pack à 5 pcs.<br />

1)<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

120<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Power supply 24 V~ (50/60 Hz) ±20%<br />

24 V= (18...30 V)<br />

Power consumption up to 11.5 VA<br />

Dissipated power up to 6 W<br />

Battery<br />

(buffer: RTC/SRAM) CR2032 plug-in<br />

Interfaces, <strong>com</strong>munication<br />

AS-Netzwerk/novaNet 1x a/b-terminals<br />

Operating Panel<br />

<strong>EY</strong>-OP240F001<br />

1x RJ-45-socket<br />

(Languages: German, French, English, Italian, Dutch,<br />

Spanish, Swedish, Norwegian, Danish, Portuguese,<br />

Finnish, Polish, Slovenian, Hungarian, Russian, Rumanian,<br />

Czech, Turkish, Slovakian)<br />

MFA 256<br />

Time <strong>com</strong>mands<br />

320 entries<br />

HDB-entries<br />

digital 2x 3584 (Block 1;3)<br />

analogue 2x 3584 (Block 2;4)<br />

Installation<br />

W x H x D (mm) 244 x 120 x 73<br />

Weight (kg) 0,65<br />

Standards, guidelines and directives<br />

Degree of protection IP 00 (EN 60529) 1)<br />

Protection class I (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

Directive 73/23/EWG EN 60730<br />

EMC directive 89/336/EWG EN 61000-6-1<br />

EN 61000-6-2 2)<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Software Class A<br />

EN 60730-1 Appendix H<br />

Additional information<br />

Fitting instructions<br />

P100002321<br />

Product Datasheet PDS 92.825<br />

Declaration on materials MD 92.825<br />

and the environment<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Humidity<br />

10...85% rh<br />

Non-condensing<br />

1) Degree of protection IP10 with terminal cover (accessory 0900240001).<br />

2) When the industrial standard EN61000-6-2 has to be fulf lled, the supply cables to the digital inputs (DI), the analogue<br />

inputs/outputs (AI/AO), the meter inputs (CI) and the voltage outputs (5 and 13 V) should not be longer than 30 m.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

121


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-RC401: ecos401<br />

PDS 9<strong>4.</strong>147<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Room Automation Station, Fan Coil, 24 V<br />

Your benefit for increased energy efficiency<br />

Usage-dependent controller for fan coil applications on the basis of eff cient control strategies.<br />

Areas of application<br />

Usable for fan coil and chill beam applications supports:<br />

• 3stage fanr<br />

• Heating/cooling<br />

• Frost-protection function<br />

Properties<br />

• Compact LON fan coil controller<br />

• Supports the LonMark Functional Prof le #8020<br />

• LonMark certif ed pursuant to<br />

Interoperability Directive Version 3.3<br />

• Separable lower housing for separate<br />

installation of terminals and electronic <strong>com</strong>ponents<br />

• Audio jack plugs for fast access to the<br />

LON network<br />

• LNS plug in for simple function conf guration<br />

Technical description<br />

• 24 V~ Voltage supply<br />

• Universal inputs and outputs<br />

conf gurable with software<br />

• 6 universal inputs<br />

• 2 universal outputs<br />

• 5 digital outputs<br />

• TP/FT 10, 78 KBps<br />

• Neuron 3150 processor<br />

Product<br />

Type<br />

<strong>EY</strong>-RC401F001<br />

Designation<br />

Room automation station, Fan coil, 24 V<br />

Accessories<br />

Type Designation Page<br />

Operating device<br />

<strong>EY</strong>-RU481F001 sensor 102<br />

<strong>EY</strong>-RU481F002 sensor, presence 102<br />

<strong>EY</strong>-RU481F003 sensor, presence, setpoint 102<br />

110<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Freely programmable, individual<br />

room climate with the <strong>SAUTER</strong> ecos.<br />

Room control units<br />

Typ<br />

<strong>EY</strong> -RU210F001 <strong>EY</strong>-RU211F001 <strong>EY</strong>-RU214F001 <strong>EY</strong>-RU216F001<br />

Name ecoUnit210 ecoUnit211 ecoUnit214 ecoUnit216<br />

Page # 136 136 136 136<br />

Use Temperature sensor Temperature, Temperature, presence, Temperature, presence,<br />

setpoint correction setpoint correction, fan setpoint correction, fan,<br />

lighting or window blinds<br />

Display – Scale ± LED LED<br />

Data transmission Cable Cable Cable Cable<br />

Key functions – Rotary knob Rotary knob + 2 buttons Rotary knob + 4 buttons<br />

Fan stages – – auto - 0 - 1 - 2 - 3 auto - 0 - 1 - 2 - 3<br />

Setpoint correction – adjustable adjustable adjustable<br />

Room occupancy – – 3 Modi 3 Modi<br />

Sensor NTC NTC NTC NTC<br />

Supply voltage from ecos 2 from ecos 2 from ecos 2 from ecos 2<br />

Individual room control<br />

Typ<br />

<strong>EY</strong>E200F001 <strong>EY</strong>E200F002 <strong>EY</strong>E202F001 <strong>EY</strong>E205F002<br />

Name ecos200 ecos200 ecos202 ecos205<br />

Page # 144 144 146 148<br />

Device DDC ind. Room Controller DDC ind. Room Controller DDC ind. Room Controller DDC VAV Controller<br />

Data transmission novaNet novaNet novaNet novaNet<br />

Inputs 4 4 7 6<br />

1 (<strong>EY</strong>B2../<strong>EY</strong>-RU2..) 1 (<strong>EY</strong>B2../<strong>EY</strong>-RU2..) 1 (<strong>EY</strong>B2../<strong>EY</strong>-RU2..) 1 (<strong>EY</strong>B2../<strong>EY</strong>-RU2..)<br />

1 (Ni1000), 1 (Ni1000), 2 (Ni1000), 1 (Ni1000),<br />

2 (main output contact) 2 (main output contact) 1 (0…10 V), 1 (0…10 V),<br />

3 (main output contact) 2 (main output contact)<br />

1 (static pressure difference)<br />

Outputs 7 8 7 3<br />

analogue 2 2 2 1<br />

digital 2 (0-I-II) Triac, 2 (0-I-II) Triac, 2 (0-I-II) Triac, 2 (0-I-II) Triac<br />

3 (0-I) Relay 4 (0-I) Relay 3 (0-I) Relay<br />

Functions Time and calendar functions, Time and calendar functions, Time and calendar functions, Time and calendar functions,<br />

historic data historic data historic data historic data<br />

Supply voltage 230 V~ 230 V~ 24 V~ 24 V~<br />

Dimensions (mm) 178 x 103 x 53 178 x 103 x 53 178 x 103 x 42 178 x 103 x 42<br />

114 Right of amendment reserved © 2009 F r. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-AS210: modu210<br />

PDS 92.815<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Automation Station<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 – Technology proven a thousand times over, with a new design<br />

For accurate control functions, 24 hours a day!<br />

Areas of application<br />

Control, monitoring and optimisation of technical operating installations in sectors such as HV AC engineering.<br />

Properties<br />

• Compact automation station<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

• 28 inputs<br />

• 14 outputs<br />

• Communication Sauter novaNet<br />

• Programming/parameterisation via PC with<br />

CASE Suite Software (based on IEC 61131-3)<br />

• Control engineering libraries<br />

• Time and calendar function<br />

• Data recording (historical data base)<br />

Technical description<br />

• Voltage supply 24 V~/=<br />

• 12 digital inputs (alarm/status)<br />

• 8 analogue inputs (Ni/Pt1000, U, Pot)<br />

• 6 analogue inputs (U, Pot)<br />

• 2 pulse counters<br />

• 4 analogue outputs (0...10 V)<br />

2 analogue outputs (0...10 V/0...20 mA)<br />

• 8 digital outputs (relays 0-I)<br />

Product<br />

Type<br />

<strong>EY</strong>-AS210F001<br />

Designation<br />

Compact automation station<br />

Accessories<br />

Type Designation Page<br />

Manual operating unit<br />

<strong>EY</strong>-OP240F001 modu240 134<br />

Connection cable<br />

0367842 002 Automation station - modu240 1,5 m<br />

1)<br />

0367842 003 Automation station - modu240 2,9 m<br />

1)<br />

0367842 004 Automation station - modu240 6,0 m<br />

1)<br />

Data Memory<br />

0367883 002 PROM memory1Mb empty (USER data) pack à 5 pcs.<br />

1)<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

118<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>R203: moduFlex 203<br />

PDS 92.507<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Universal Controller<br />

Your benefit for increased energy efficiency<br />

For accurate control functions, 24 hours a day!<br />

Areas of application<br />

Open- and closed-loop control (DDC & PLC) of installations, e.g. in HV AC applications.<br />

Properties<br />

• Data structure for several control loops<br />

• Can be networked and provided with<br />

<strong>com</strong>munication capability by adding the auxiliar y<br />

module for novaNet (accessor y no. 374413)<br />

• Direct <strong>com</strong>munication with <strong>EY</strong>-OP250 touch-panel<br />

with the Pt to Pt auxiliar y module<br />

(accessory no. 374448) is possible.<br />

• Programmable/parameterisation via PC with<br />

CASE Suite software (based on IEC 61131-3)<br />

Technical description<br />

• Voltage supply 24 V~<br />

• 18 inputs (digital/analogue)<br />

• 8 outputs (digital/analogue)<br />

Product<br />

Type<br />

<strong>EY</strong>R203F001<br />

Designation<br />

moduFlex universal controller<br />

Accessories<br />

Type Designation Page<br />

Operating units<br />

<strong>EY</strong>-OP240 Local Control Panel modu240 134<br />

<strong>EY</strong>-OP250 Touch-Panel modu250 132<br />

Micro-programme<br />

0501149 002 For <strong>EY</strong>R203 with modu240. Languages: Ger man, French, English, Polish,<br />

1)<br />

Slovenian, Hungarian, Rumanian, Russian, Czech, Turkish, Slovakian<br />

Connection cable<br />

0367842 002 moduFlex – modu240 1,5 m<br />

1)<br />

0367842 003 moduFlex – modu240 2,9 m<br />

1)<br />

0367842 004 moduFlex – modu240 6,0 m<br />

1)<br />

0367862 001 moduFlex – modu250 1,5 m<br />

1)<br />

0367862 002 moduFlex – modu250 2,9 m<br />

1)<br />

0367862 003 moduFlex – modu250 6,0 m<br />

1)<br />

Data Memory<br />

0367883 001 6× empty PROM‘s 512 KBit (User-PROM)<br />

1)<br />

Auxiliary modules<br />

0374413 001 novaNet <strong>com</strong>munication (MV 505770)<br />

1)<br />

0374448 001 Point to point for direct connection of modu250 up to 6m<br />

1)<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

122<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

Power consumption<br />

24 V~, ± 20%, 50/60 Hz<br />

10 VA<br />

Installation<br />

W x H x D (mm) 235 x 147,5 x 64,5<br />

Weight (kg) 0,8<br />

Connections<br />

Digital inputs<br />

8 (2 of which can<br />

be used as pulse meters)<br />

Digital outputs 2× 0-I<br />

2× 0-I-II<br />

Analogue inputs<br />

5× Ni/Pt1000<br />

5× 0...10 V<br />

Analogue outputs 4× 0...10 V<br />

Interfaces, <strong>com</strong>munication<br />

AS-Network/novaNet 1× a/b-terminals<br />

Operating Panel<br />

<strong>EY</strong>-OP240F001<br />

1× RJ-45-socket<br />

Languages: German, French, English, Italian, Dutch,<br />

Spanish, Swedish, Norwegian, Danish, Portuguese,<br />

Finnish (for other languages, see ‘Accessories’)<br />

MFA 128<br />

Time <strong>com</strong>mands<br />

320 entries<br />

HDB-entries<br />

digital 1792 (Block 1)<br />

analogue 1792 (Block 2)<br />

Standards, guidelines and directives<br />

Degree of protection IP 00 (EN 60529) 1)<br />

Protection class I (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

Directive 73/23/EWG EN 60730<br />

EMC directive 89/336/EWG EN 61000-6-1<br />

EN 61000-6-2 2)<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Agency USA/Canada UL Listed: UL 916<br />

CSA certified: CSA C22.2<br />

Additional information<br />

Fitting instructions 0505769<br />

Product Datasheet PDS 92.507<br />

Declaration on materials MD 92.507<br />

and the environment<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Transport and -25...70 °C<br />

storage temperature<br />

Humidity<br />

10...85% rh<br />

Non-condensing<br />

1) Degree of protection IP10 with terminal cover (accessory 0900240001).<br />

2) When the industrial standard EN61000-6-2 has to be fulf lled, the supply cables to the digital inputs (DI), the analogue<br />

inputs/outputs (AI/AO), the meter inputs (CI) and the voltage outputs (5 and 13 V) should not be longer than 30 m.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

123


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-FM174: moduLink174<br />

PDS 92.830<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Field Module, digital inputs<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 – Technology proven a thousand times over, with a new design.<br />

Areas of application<br />

To record digital inputs (alarm/status) in technical operating installations, e.g. in HVAC engineering.<br />

Properties<br />

• Remote unit for modu225<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

• 16 digital inputs<br />

• Insert for direct labelling/inscription<br />

• Can be located up to 100 m from the<br />

automation station<br />

• Signalling with bi-colour LED (red/green)<br />

Technical description<br />

• Communication/voltage supply via novaLink bus<br />

(2-wire) from AS<br />

• 16 digital inputs<br />

Product<br />

Type<br />

<strong>EY</strong>-FM174F001<br />

Designation<br />

Field module, potential free digital inputs<br />

Accessories<br />

Type Designation Page<br />

Inserts, Labels<br />

0920000 174 Front insert, printable, yellow. 25 sheets with 6 front inser ts each, perforated<br />

1)<br />

Covers<br />

0367841 001 Terminal cover<br />

1)<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

124<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Current consumption<br />

Dissipated power<br />

up to 120 mA<br />

up to 0,1 W<br />

Installation<br />

W x H x D (mm) 115 x 90 x 50<br />

Weight (kg) 0,24<br />

Inputs<br />

Category<br />

Potential-free contacts<br />

connected to earth<br />

Opto-coupler<br />

Transistors<br />

Permitted<br />

input resistance<br />

up to 24 V~/=<br />

Permissible input resistance up to 1 kΩ (including line)<br />

Recording time<br />

30 ms<br />

Polling cycle<br />

150 ms<br />

Interfaces, <strong>com</strong>munication<br />

AS - moduLink connection up to 100 m (5 nF / 7,5 Ω)<br />

twisted, shielded<br />

to earth on both ends<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

EMC directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2 1)<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Additional information<br />

Fitting instructions<br />

P100002321<br />

Product Datasheet PDS 92.830<br />

Declaration on materials MD 92.830<br />

and the environment<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Transport and -25...70 °C<br />

storage temperature<br />

Humidity<br />

10...85% rh<br />

Non-condensing<br />

1) When the industrial standard EN61000-6-2 has to be fulf lled, the supply cables to the inputs should not be longer<br />

than 30 m.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

125


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-FM170: moduLink170<br />

PDS 92.835<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Field Module analogue signal 0...10 V (0...20 mA)<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 – Technology proven a thousand times over, with a new design.<br />

Areas of application<br />

To record digital inputs (alarm/status) in technical operating installations, e.g. in HVAC engineering.<br />

Properties<br />

• Remote unit for modu225<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

• 4 analogue outputs<br />

• Insert for direct labelling/inscription<br />

• Can be located up to 100 m from the<br />

automation station<br />

• Preselection of defined tension status for<br />

prio- and watchdog-function<br />

Technical description<br />

• Communication/voltage supply via novaLink bus<br />

(2-wire) from AS<br />

• 2 analogue outputs 0...10 V<br />

• 2 analogue outputs 0...10 V/0...20 mA<br />

• 1 output for monitoring the novaLink bus<br />

Product<br />

Type<br />

<strong>EY</strong>-FM170F001<br />

Designation<br />

Field module, analogue signal 0...10 V/(2x 0...20 mA)<br />

with manual operation<br />

Accessories<br />

Type Designation Page<br />

Inserts, Labels<br />

0920000 170 Front insert, printable, yellow. 25 sheets with 6 front inser ts each, perforated<br />

1)<br />

Covers<br />

0367841 001 Terminal cover<br />

1)<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

126<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Current consumption up to 100 mA<br />

Dissipated power up to 0,1 W<br />

Emergency power supply 24 V~/=<br />

Outputs<br />

Type<br />

Analogue signal<br />

4x 0...10 V (2x 0...20mA)<br />

Interfaces, <strong>com</strong>munication<br />

AS - moduLink connection up to 100 m (5 nF / 7,5 Ω)<br />

twisted, shielded<br />

to earth on both ends<br />

Installation<br />

W x H x D (mm) 115 x 90 x 50<br />

Weight (kg) 0,24<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

EMC directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2 1)<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Transport and -25...70 °C<br />

storage temperature<br />

Humidity<br />

10...85% rh<br />

Non-condensing<br />

Additional information<br />

Fitting instructions<br />

P100002346<br />

Product Datasheet PDS 92.835<br />

Declaration on materials MD 92.835<br />

and the environment<br />

1) When the industrial standard EN61000-6-2 has to be fulf lled, the supply cables to the outputs should not be longer<br />

than 30 m.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

127


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-FM165: moduLink165<br />

PDS 92.840<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Field Module, digital outputs 0-I-II<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 – Technology proven a thousand times over, with a new design.<br />

Areas of application<br />

Control of actuators such as contactors, valve actuators or signalling for technical operating installations, e.g.<br />

in HVAC engineering.<br />

Properties<br />

• Remote unit for modu225<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

• 2 digital outputs/2-stage<br />

• Insert for direct labelling/inscription<br />

• Can be located up to 100 m from the<br />

automation station<br />

• Defined relay statuses can be preselected for<br />

priority or watchdog function<br />

• Can be used as local precaution/emergency control<br />

with manual control of outputs<br />

Technical description<br />

• Communication/voltage supply via novaLink bus<br />

(2-wire) from AS<br />

• Emergency power supply: 24 V~/=<br />

• 2 digital outputs, relays 0-I-II (changeover)<br />

• 1 output for monitoring the novaLink bus<br />

Product<br />

Type<br />

<strong>EY</strong>-FM165F001<br />

Designation<br />

Field module, <strong>com</strong>mand 0-I-II with LED and manual operation<br />

Accessories<br />

Type Designation Page<br />

Inserts, Labels<br />

0920000 165 Front insert, printable: yellow. 25 sheets with 6 front inser ts each, perforated<br />

1)<br />

Covers<br />

0367841 001 Terminal cover<br />

1)<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

128<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Current consumption up to 150 mA<br />

Dissipated power up to 1 W<br />

Emergency power supply 24 V~/=<br />

Outputs<br />

Category<br />

Relays, change-over contacts<br />

Load<br />

250 V~/2A ohmic load<br />

Switching frequency 1 Mio<br />

Interfaces, <strong>com</strong>munication<br />

AS - moduLink connection up to 100 m (5 nF / 7,5 Ω)<br />

twisted, shielded<br />

to earth on both ends<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Transport and -25...70 °C<br />

storage temperature<br />

Humidity<br />

10...85% rh<br />

Non-condensing<br />

Installation<br />

W x H x D (mm) 115 x 90 x 50<br />

Weight (kg) 0,24<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class I (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

EMC directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2 1)<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Additional information<br />

Fitting instructions<br />

P100002346<br />

Product Datasheet PDS 92.840<br />

Declaration on materials MD 92.840<br />

and the environment<br />

1) When the industrial standard EN61000-6-2 has to be fulf lled, the supply cables to the outputs should not be longer<br />

than 30 m.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

129


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Current consumption up to 150 mA<br />

Dissipated power up to 1 W<br />

Emergency power supply 24 V~/=<br />

Outputs<br />

Category<br />

Relays, change-over contacts<br />

Load<br />

250 V~/2A ohmic load<br />

Switching frequency 1 Mio<br />

Interfaces, <strong>com</strong>munication<br />

AS - moduLink connection up to 100 m (5 nF / 7,5 Ω)<br />

twisted, shielded<br />

to earth on both ends<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Transport and -25...70 °C<br />

storage temperature<br />

Humidity<br />

10...85% rh<br />

Non-condensing<br />

Installation<br />

W x H x D (mm) 115 x 90 x 50<br />

Weight (kg) 0,24<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class I (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

EMC-directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2 1)<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Additional information<br />

Fitting instructions<br />

P100002346<br />

Product Datasheet PDS 92.845<br />

Declaration on materials MD 92.845<br />

and the environment<br />

1) When the industrial standard EN61000-6-2 has to be fulf lled, the supply cables to the outputs should not be longer<br />

than 30 m.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

131


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-OP250: modu250<br />

PDS 93.070<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Touch Panel<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 – Technology proven a thousand times over - with a new design.<br />

Areas of application<br />

Graphic display, navigation and operation of the automation station and its systems.<br />

Properties<br />

• Graphic, touch-sensitive operating and display unit for<br />

network-wide use of <strong>EY</strong>-<strong>modulo</strong> 2 automation stations<br />

• Menu-driven operating interface for the visualisation<br />

of automation stations and systems<br />

• Alarm lists, data point lists, time switching programs<br />

and calendar, as well as trend data<br />

• Modification of setpoints and control value defaults,<br />

as well as digital control <strong>com</strong>mands<br />

• Editing of time switching programs and calendars<br />

• Freely programmable graphic system displays<br />

with dynamic data points<br />

• Access rights with individually applied users<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 family<br />

Technical description<br />

• Voltage supply 230 V~<br />

• Graphic display 320 x 240 pixels (QVGA)<br />

• Active area 140 x 105 mm<br />

• Models Colour with 256 colours (F001),<br />

Monochrome (F002)<br />

• Languages that can be parameterised using<br />

CASE Suite<br />

• RJ-45, DB-9 interfaces for parameterisation,<br />

updates<br />

• RJ-11 interface for novaNet system bus<br />

Product<br />

Type<br />

<strong>EY</strong>-OP250F001<br />

<strong>EY</strong>-OP250F002<br />

Designation<br />

Colour touch panel<br />

Monochrome touch panel<br />

Accessories<br />

Type Designation Page<br />

Software<br />

GZF520F001 CASE TPC parameterisation software for Windows for free layout<br />

1)<br />

of operating interface, incl. operating manual<br />

Connection cable<br />

0367862 001 Automation station - modu250 1,5 m<br />

1)<br />

0367862 002 Automation station - modu250 2,9 m<br />

1)<br />

0367862 003 Automation station - modu250 6,0 m<br />

1)<br />

General<br />

0374494 001 Operating pin set for modu250<br />

1)<br />

0374509 001 Plug, 3-pole, packed<br />

1)<br />

0374515 001 Set for degree of protection IP 65<br />

1)<br />

0374568 001 Seal, single (for set 0374515 001)<br />

1)<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

132<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

Nenn- Power consumption<br />

Features<br />

Display<br />

colour or monochrome<br />

Resolution<br />

Display<br />

backlighting<br />

Active surface W x H<br />

Memory<br />

48...62 Hz<br />

85...250 V~<br />

up to 7 W<br />

5,7 Inch<br />

4-wire resistive touch<br />

320 x 240 (QVGA)<br />

256 colours<br />

time-controlled switch off<br />

140 x 105 mm<br />

8 MB Flash, 8 MB RAM<br />

Interfaces, <strong>com</strong>munication<br />

1x RJ-11 socket<br />

novaNet<br />

1x RJ-45 socket<br />

Ethernet 10BaseT<br />

(incl. application download)<br />

1x DB9 plug<br />

RS232 (system update)<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Storage and -25...70 °C<br />

transport temperature<br />

Humidity<br />

10...85% rh<br />

Non-condensing<br />

Installation<br />

W x H x D (mm) 240 x 156 x 46<br />

Weight (kg) 1,0<br />

Standards, guidelines and directives<br />

Degree of protection IP 20 (EN 60529)<br />

With accessory 0374515 001 IP 65 at front<br />

Protection class I (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

EMC 89/336/EWG EN 61000-6-1<br />

EN 61000-6-2<br />

EN 61000-6-4<br />

EN 55022 Class A<br />

Additional information<br />

Fitting instructions 0505814<br />

Product Datasheet PDS 93.070<br />

Declaration on materials and MD 93.070<br />

the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

133


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

Power consumption<br />

Dissipated power<br />

from AS<br />

100 mA<br />

0,1 W<br />

Installation<br />

W x H x D (mm) 80 x 144 x 36<br />

Weight (kg) 0,3<br />

Standards, guidelines and directives<br />

Interfaces, <strong>com</strong>munication<br />

1x RJ-45 socket<br />

Degree of protection IP 40/20 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Distance<br />

up to 20 m, screened<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

Languages<br />

Micro-programme AS Modulo2:<br />

German, French, English, Italian, Dutch, Spanish,<br />

Swedish, Norwegian, Danish, Portuguese, Finnish, Polish,<br />

Slovenian, Hungarian, Russian, Czech, Turkish, Slovakian<br />

EMC directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2<br />

EN 61000-6-4<br />

EN 55022 Klasse A<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Transport and -25...65 °C<br />

storage temperature<br />

Additional information<br />

Fitting instructions 0505399<br />

Product Datasheet PDS 93.075<br />

Declaration on materials and MD 93.075<br />

Humidity<br />

10...85% rh<br />

Non-condensing<br />

the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

135


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-RU210…216: ecoUnit210…216<br />

PDS 9<strong>4.</strong>175<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Room Control Unit for <strong>EY</strong>-<strong>modulo</strong> 2 ecos<br />

Your benefit for increased energy efficiency<br />

Individual adjustment of presence and absence times as well as room setpoint correction, light and blind<br />

control for optimising the room‘s energy consumption.<br />

Areas of application<br />

Operating unit for controlling and ensuring absolute room <strong>com</strong>for t. Temperature detection and control of<br />

differently equipped rooms through <strong>com</strong>municative <strong>EY</strong>-<strong>modulo</strong> 2 ecos intelligent unitar y controllers.<br />

Properties<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 system family<br />

• Room control unit in many functional,<br />

design and colour variants<br />

• Individual room climate control<br />

• Operating mode adjustment for room occupancy<br />

and control of a three-stage fan<br />

Technical description<br />

• Voltage supply from ecos 2<br />

• Connection 3-wire<br />

Product<br />

Type<br />

<strong>EY</strong>-RU210F001<br />

<strong>EY</strong>-RU211F001<br />

<strong>EY</strong>-RU214F001<br />

Designation<br />

Control unit ecos2, NTC-sensor<br />

Control unit ecos2, NTC, setpoint adjuster (dXs)<br />

Control unit ecos2, NTC, dXs, 2 buttons<br />

<strong>EY</strong>-RU216F001 Control unit ecos2, NTC, dXs, 4 buttons 2)<br />

Accessories<br />

Type<br />

Designation<br />

Mounting<br />

094 0240101 Frame, single, incl. fixing plate (for recessed junction box, 10 pcs.)<br />

1)<br />

094 0240201 Frame, double, incl. fixing plate (for recessed junction box, 10 pcs.)<br />

1)<br />

094 0240301 Plinth, single, (for wall mounting, 10 pcs.)<br />

1)<br />

094 0240401 Plinth, double, (for wall mounting, 10 pcs.)<br />

1)<br />

094 0240501 Cable cover, single, (for wall mounted cable feed, 10 pcs.)<br />

1)<br />

094 0240601 Cable cover, double, (for wall mounted cable feed, 10 pcs.)<br />

1)<br />

094 0240701 Fixing plate, single, (for non-Sauter frames, 10 pcs.)<br />

1)<br />

094 0240801 Fixing plate, double, (for non-Sauter frames, 10 pcs.)<br />

1)<br />

094 9241301 Cover transparent, single (10 pcs.)<br />

1)<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

2) The ecoUnit306 switching unit (<strong>EY</strong>-SU306) can be added to the ecoUnit216 room operating unit (<strong>EY</strong>-RU216).<br />

136<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Voltage supply from ecos 2<br />

Installation<br />

Weight (kg) 0,1<br />

Sensor<br />

Measurement range 0...40 °C<br />

Resolution<br />

0,1 K<br />

Functionality<br />

Setpoint correction adjustable<br />

Room occupancy LED 3 modes, Display-LED<br />

Fan stage LED<br />

5 modes, Display-LED<br />

Connection<br />

Cable<br />

3-wire<br />

Length<br />

up to 100 m<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

EMC directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2 1)<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Additional information<br />

Fitting instructions<br />

P100002471<br />

Product Datasheet PDS 9<strong>4.</strong>175<br />

Declaration on materials and MD 9<strong>4.</strong>175<br />

the environment<br />

1) When the industrial standard EN61000-6-2 has to be fulf lled, the supply cables should not be longer than 30 m.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

137


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Voltage supply from ecos 2<br />

Installation<br />

Weight (kg) 0,1<br />

Sensor<br />

Measurement range 0...40 °C<br />

Resolution<br />

0,1 K<br />

Functionality<br />

Setpoint correction Adjustable<br />

Room occupancy 3 modes<br />

Fan stages<br />

5 functions<br />

Position LED<br />

green<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

EMC directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Connection<br />

Cable<br />

3-core<br />

Length (to <strong>EY</strong>-RU)<br />

up to 100 m<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Additional information<br />

Fitting instructions<br />

P100001966<br />

Product Datasheet PDS 9<strong>4.</strong>040<br />

Declaration on materials and MD 9<strong>4.</strong>040<br />

the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

139


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-SU306: ecoUnit306<br />

PDS 9<strong>4.</strong>035<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Switching Unit for Room Control Unit<br />

Your benefit for increased energy efficiency<br />

Control lights and blinds to optimise the room‘s energy consumption.<br />

Areas of application<br />

Switching unit connected with ecoUnit2 and ecoUnit3 for controlling lights, blinds, etc. via <strong>EY</strong>-<strong>modulo</strong> 2ecos/<br />

<strong>EY</strong>-<strong>modulo</strong> 5 ecos <strong>com</strong>municative intelligent unitary controllers.<br />

Properties<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 and 5 system family<br />

• Keypad for extending the ecoUnit3/ecoUnit2<br />

(<strong>EY</strong>-RU3 . . /<strong>EY</strong>-RU2 . . )<br />

• Switching unit in many functional,<br />

design and colour variants<br />

• Lamp control and dimming<br />

• Blind control<br />

Technical description<br />

• Voltage supply from ecoUnit3 or ecoUnit2<br />

• Connection 2-core<br />

• Keypad with 6 key functions<br />

Product<br />

Type<br />

<strong>EY</strong>-SU306F001<br />

Designation<br />

Keypad for 6 key functions<br />

Accessories<br />

Type Designation Page<br />

Mounting<br />

094 0240101 Frame, single, incl. f xing plate (for recessed junction box, 10 pcs.)<br />

1)<br />

094 0240201 Frame, double, incl. f xing plate (for recessed junction box, 10 pcs.)<br />

1)<br />

094 0240301 Plinth, single, (for wall mounting, 10 pcs.)<br />

1)<br />

094 0240401 Plinth, double, (for wall mounting, 10 pcs.)<br />

1)<br />

094 0240501 Cable cover, single, (for wall mounted cable feed, 10 pcs.)<br />

1)<br />

094 0240601 Cable cover, double, (for wall mounted cable feed, 10 pcs.)<br />

1)<br />

094 0240701 Fixing plate, single, (for non-Sauter frames, 10 pcs.)<br />

1)<br />

094 0240801 Fixing plate, double, (for non-Sauter frames, 10 pcs.)<br />

1)<br />

094 9241301 Plexiglas blind cover, single (10 pcs.)<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

140<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Functionality<br />

Position LED<br />

green<br />

Installation<br />

Weight (kg) 0,1<br />

Connection<br />

Cable<br />

2-core<br />

Length (to <strong>EY</strong>-RU)<br />

up to 30 m<br />

Permissible ambient conditions<br />

Operating temperature 5...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Standards, guidelines and directives<br />

Degree of protection IP 30 (EN 60529)<br />

Protection class III (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

EMC directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Additional information<br />

Fitting instructions<br />

P100001963<br />

Product Datasheet PDS 9<strong>4.</strong>035<br />

Declaration on materials MD 9<strong>4.</strong>035<br />

and the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

141


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Voltage supply 230 V~ ±10%<br />

Power consumption<br />

up to 29 VA/11 W<br />

Battery<br />

(buffer: RTC/SRAM)<br />

CR2032 plug-in<br />

(Lithium)<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Standards, guidelines and directives<br />

Degree of protection IP 20 (EN 60529)<br />

(with terminal cover/<br />

wiring box)<br />

Protection class I (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

EMC directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2 1)<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Installation<br />

Weight (kg) 0,8<br />

Additional information<br />

Fitting instructions<br />

<strong>EY</strong> -RC208<br />

P100002324<br />

<strong>EY</strong> -RC209<br />

P100002326<br />

Product Datasheet PDS 9<strong>4.</strong>185<br />

Declaration on materials and MD 9<strong>4.</strong>185<br />

the environment<br />

Inputs<br />

Operating units <strong>EY</strong>B2 . . /<strong>EY</strong>-RU2 . .<br />

Temperature sensor<br />

Ni1000<br />

U/Pot/(I) 0…10 V=<br />

Main output contact<br />

on/off<br />

<strong>EY</strong>-RC208F001<br />

1<br />

2<br />

1<br />

4<br />

<strong>EY</strong>-RC209F001<br />

1<br />

2<br />

1<br />

4<br />

Outputs<br />

Triac switching outputs 0-I-II (24 V~, 1 A)<br />

Relay switching outputs Change-over contacts<br />

(250 V~,10 A)<br />

(Start up current 80 A) NO (250 V~,1 A)<br />

Relay switching outputs NO (250 V~,1 A)<br />

Change over<br />

(250 V~,1 A)<br />

Analogue<br />

0...10 V (load ≥ 1 kΩ)<br />

<strong>EY</strong>-RC208F001<br />

2<br />

1<br />

2<br />

3<br />

–<br />

4<br />

<strong>EY</strong>-RC209F001<br />

2<br />

1<br />

2<br />

6<br />

1<br />

4<br />

1) When the industrial standard EN61000-6-2 has to be fulf lled, the supply cables to the digital inputs (DI), the analogue<br />

inputs/outputs (AI/AO) and the meter inputs (CI) should not be longer than 30 m.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

143


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>E200: ecos200<br />

PDS 9<strong>4.</strong>200<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

DDC Individual Room Controller<br />

Your benefit for increased energy efficiency<br />

Efficient function modules in ecos enable energy-optimised room control and therefore guarantee minimal<br />

energy consumption.<br />

Areas of application<br />

Individual single room control, fan coil units, ceiling cooling control, etc.<br />

Properties<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 system family<br />

• Individual adaptation of room climate using room control<br />

Technical description<br />

• Voltage supply 230 V~<br />

• Systembus novaNet, 2-wire<br />

devices in the series <strong>EY</strong>-RU2 . . and <strong>EY</strong>B2 . .<br />

• Optimisation of energy consumption thanks to presence<br />

function, window contact monitoring, ventilator position<br />

switching according to requirements and time-dependent<br />

setpoint specification<br />

• Time and calendar function<br />

• Recording of historical data<br />

• Integration into building management system via<br />

novaNet data interface<br />

• Programming/parameterisation via PC with CASE Suite<br />

software (based on IEC 61131-3)<br />

Product<br />

Type<br />

<strong>EY</strong>E200F001<br />

<strong>EY</strong>E200F002<br />

Designation<br />

DDC individual room controller 3 Relays<br />

DDC individual room controller 4 Relays<br />

144<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

230 V~ ±10%, 50/60Hz<br />

Power consumption<br />

14 VA; incl. 6 VA external<br />

Dissipated power<br />

14 W<br />

Permissible ambient conditions<br />

Operating temperature. 0...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Installation<br />

Weight (kg) 0,7<br />

Standards, guidelines and directives<br />

Degree of protection IP 10 (EN 60529)<br />

Protection class I (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

EMC directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2 1)<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

Software Class A<br />

EN 60730-1 Appendix H<br />

Additional information<br />

Fitting instructions 0505907<br />

Product Datasheet PDS 9<strong>4.</strong>200<br />

Declaration on materials and MD 9<strong>4.</strong>200<br />

the environment<br />

Inputs<br />

<strong>EY</strong>E200F001<br />

<strong>EY</strong>E200F002<br />

for operating unit<br />

<strong>EY</strong>B2.., <strong>EY</strong>-RU2..<br />

1<br />

1<br />

for temperature sensor<br />

Ni1000<br />

1<br />

1<br />

for main output contact<br />

On/Off<br />

2<br />

2<br />

Outputs<br />

Triac switching outputs 0-I-II (24 V~, 1 A)<br />

Relay switching outputs NO (250 V~, 2 A)<br />

Relay switching outputs NO (250 V~, 10 A)<br />

Analogue<br />

0...10 V (load ≥ 1 kΩ)<br />

<strong>EY</strong>E200F001<br />

2<br />

3<br />

0<br />

2<br />

<strong>EY</strong>E200F002<br />

2<br />

3<br />

1<br />

2<br />

1) When the industrial standard EN61000-6-2 has to be fulf lled, the supply cables to the digital inputs (DI), the analogue<br />

inputs/outputs (AI/AO) and the meter inputs (CI) should not be longer than 30 m.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

145


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-FM164: moduLink164<br />

PDS 92.845<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Field Module, digital outputs 0-I<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 – Technology proven a thousand times over, with a new design.<br />

Areas of application<br />

Control of actuators such as contactors, valve actuators or signalling for technical operating installations, e.g.<br />

in HVAC engineering.<br />

Properties<br />

• Remote unit for modu225<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

• 4 digital outputs<br />

• Insert for direct labelling/inscription<br />

• Can be located up to 100 m from the<br />

automation station<br />

• Defined relay statuses can be preselected for<br />

priority or watchdog function<br />

• Can be used as local precaution/emergency<br />

control with manual control of outputs<br />

Technical description<br />

• Communication/voltage supply via novaLink bus<br />

(2-wire) from AS<br />

• Emergency power supply: 24 V~/=<br />

• 4 digital outputs, relays 0-I (changeover)<br />

• 1 output for monitoring the novaLink bus<br />

Product<br />

Type<br />

<strong>EY</strong>-FM164F001<br />

Designation<br />

Field module, digital output 0-I with LED displays and<br />

manual operation<br />

Accessories<br />

Type Designation Page<br />

Inserts, Labels<br />

0920000 164 Front insert, printable: yellow. 25 sheets with 6 front inser ts each, perforated<br />

1)<br />

Covers<br />

0367841 001 Terminal cover<br />

1)<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

130<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-OP240: modu240<br />

PDS 93.075<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Control Panel<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 – Technology proven a thousand times over – with a new design.<br />

Areas of application<br />

Direct display, navigation and operation of the automation station and its systems.<br />

Properties<br />

• Local operating and display unit for direct manual<br />

operation of <strong>EY</strong>-<strong>modulo</strong> 2 automation stations on site<br />

• Menu-driven operating interface for visualisation<br />

of the data points of an automation station<br />

• Display of measurements, alarms, status messages<br />

• Operation of default target values and digital<br />

positioning <strong>com</strong>mands<br />

• Operated via 6 mambrane keys<br />

• Editing time programs<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 family<br />

Technical description<br />

• Voltage supply direct from AS<br />

• LCD resolution 128 x 64 pixels<br />

• Display for 8 lines of 21 characters each<br />

• Multilingual character set direct from AS<br />

• RJ-45 interface for point-to-point connection<br />

with AS<br />

• Can be f tted to front door of MCC<br />

Product<br />

Type<br />

<strong>EY</strong>-OP240F001<br />

Designation<br />

Local control panel<br />

Accessories<br />

Type Designation Page<br />

Connection cable<br />

0367842 001 Automation station - modu240 0,35 m<br />

1)<br />

0367842 002 Automation station - modu240 1,5 m<br />

1)<br />

0367842 003 Automation station - modu240 2,9 m<br />

1)<br />

0367842 004 Automation station - modu240 6,0 m<br />

1)<br />

Mounting<br />

0367829 001 Panel bracket<br />

1)<br />

0367878 001 Wall or top-hat bracket<br />

1)<br />

0367880 001 Table stand<br />

1)<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

134<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-RU241…246: ecoUnit241…246<br />

PDS 9<strong>4.</strong>170<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Room Control Unit for ecos<br />

Your benefit for increased energy efficiency<br />

Individual adjustment of presence and absence times as well as room setpoint correction, light and blind<br />

control for optimising the room‘s energy consumption.<br />

Areas of application<br />

Operating unit for controlling and ensuring absolute room <strong>com</strong>fort. Temperature detection and control of differently<br />

equipped rooms via <strong>EY</strong>-<strong>modulo</strong> 2 ecos <strong>com</strong>municative intelligent unitary controllers.<br />

Properties<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 system family<br />

• Expandable with keypad <strong>EY</strong>-SU306<br />

• Room control unit in many functional,<br />

design and colour variants<br />

• Individual room climate control<br />

• Setting the operating mode for room<br />

occupancy and control of a three-stage fan<br />

• Lamp control and dimming<br />

• Blind control<br />

• Display with <strong>com</strong>prehensive<br />

status information on room conditions<br />

Technical description<br />

• Voltage supply from ecos2<br />

• 3-wire connection<br />

Product<br />

Type Designation<br />

<strong>EY</strong>-RU241F001<br />

<strong>EY</strong>-RU244F001<br />

<strong>EY</strong>-RU246F001<br />

Control unit, NTC sensor, dXs setpoint adjuster, 2 buttons<br />

Control unit, NTC, dXs, fan, presence, 4 buttons<br />

Control unit, NTC, dXs, fan, presence, 6 buttons<br />

Accessories<br />

Type Designation Page<br />

Operation<br />

<strong>EY</strong>-SU306 Keypad, without frame 72<br />

Mounting<br />

094 0240101 Frame, single, incl. f xing plate (for recessed junction box, 10 pcs.)<br />

1)<br />

094 0240201 Frame, double, incl. f xing plate (for recessed junction box, 10 pcs.)<br />

1)<br />

094 0240301 Plinth, single, (for wall mounting, 10 pcs.)<br />

1)<br />

094 0240401 Plinth, double, (for wall mounting, 10 pcs.)<br />

1)<br />

094 0240501 Cable cover, single, (for wall mounted cable feed, 10 pcs.)<br />

1)<br />

094 0240601 Cable cover, double, (for wall mounted cable feed, 10 pcs.)<br />

1)<br />

094 0240701 Fixing plate, single, (for non-Sauter frames, 10 pcs.)<br />

1)<br />

094 0240801 Fixing plate, double, (for non-Sauter frames, 10 pcs.)<br />

1)<br />

094 9241301 Plexiglas blind cover, single (10 pcs.)<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

138<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-RC208, 209: ecos208, 209<br />

PDS 9<strong>4.</strong>185<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Room Automation Station<br />

Your benefit for increased energy efficiency<br />

Efficient function modules in ecos enable energy-optimised room control, control of lights and blinds,<br />

and therefore guarantee minimal energy consumption.<br />

Areas of application<br />

Room automation for controlling temperature, lighting and blinds.<br />

Properties<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 system family<br />

• Individual adaptation of room climate using room<br />

control devices in the series <strong>EY</strong>-RU2 . . and <strong>EY</strong>B2 . .<br />

• Optimisation of energy consumption thanks to presence<br />

function, window contact monitoring, ventilator position<br />

switching according to requirements, light and blind<br />

<strong>controls</strong>, as well as time-dependent setpoint specification<br />

• Time and calendar function<br />

• Recording of historical data<br />

• Integration into building management system via<br />

novaNet data interface<br />

• Programming/parameterisation via PC with CASE Suite<br />

software (based on IEC 61131-3)<br />

Technical description<br />

• Voltage supply 230 V~<br />

• Systembus novaNet, 2-core<br />

Product<br />

Type<br />

<strong>EY</strong>-RC208F001<br />

<strong>EY</strong>-RC209F001<br />

Designation<br />

Room automation station 6 Relays<br />

Room automation station 10 Relays<br />

Accessories<br />

Type Designation Page<br />

Mounting<br />

0900240001 Terminal cover 240 mm (2 pcs.)<br />

1)<br />

0900240010 Wiring box 240 mm (2 pcs.)<br />

1)<br />

Data Memory<br />

0367883 002 5x empty PROMs 1 MBit (User PROM)<br />

1)<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

142<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>E202: ecos202<br />

PDS 9<strong>4.</strong>201<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

DDC Individual Room Controller<br />

Your benefit for increased energy efficiency<br />

Efficient function modules in ecos enable energy-optimised room control and therefore guarantee minimal<br />

energy consumption.<br />

Areas of application<br />

Individual single room control, fan coil units, ceiling cooling control, etc.<br />

Properties<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 system family<br />

• Individual adaptation of room climate using room<br />

control devices in the series <strong>EY</strong>-RU2 . . and <strong>EY</strong>B2 . .<br />

• Optimisation of energy consumption thanks to presence<br />

function, window contact monitoring, ventilator position<br />

switching according to requirements and time-dependent<br />

setpoint specification<br />

• Time and calendar function<br />

• Recording of historical data<br />

• Integration into building management system via<br />

novaNet data interface<br />

• Programming/parameterisation via PC with CASE Suite<br />

software (based on IEC 61131-3)<br />

Technical description<br />

• Voltage supply 24 V~<br />

• Systembus novaNet, 2-wire<br />

Product<br />

Type<br />

<strong>EY</strong>E202F001<br />

Designation<br />

DDC individual room controller<br />

146<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

Power consumption<br />

Connections<br />

24 V~ ± 20%, 50/60 Hz<br />

10 VA<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Inputs<br />

for operating unit 1× <strong>EY</strong>B2.., <strong>EY</strong>-RU2..<br />

for temperature sensor 2× Ni1000<br />

for <strong>com</strong>mand variable 1× 0...10 V (Ri = 10 k Ω)<br />

for main output contact 3× On/Off<br />

Outputs<br />

Triac switching outputs 2× 0-I-II (24 V~, 1 A)<br />

Relay switching outputs 3× NO (250 V~, 2 A)<br />

Analogue<br />

2× 0...10 V (load ≥ 1 kΩ)<br />

Installation<br />

Weight (kg) 0,37<br />

Standards, guidelines and directives<br />

Degree of protection IP 10 (EN 60529)<br />

Protection class II (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

EMC directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2 1)<br />

EN 61000-6-4<br />

EN 55022 Class A<br />

Software Class A<br />

EN 60730-1 Appendix H<br />

Additional information<br />

Fitting instructions 0505444<br />

Product Datasheet PDS 9<strong>4.</strong>201<br />

Declaration on materials and MD 9<strong>4.</strong>201<br />

the environment<br />

1) When the industrial standard EN61000-6-2 has to be fulf lled, the supply cables should not be longer than 30 m.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

147


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>E205, 206: ecos205, 206<br />

PDS 9<strong>4.</strong>205<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

DDC VAV Controller<br />

Your benefit for increased energy efficiency<br />

On-demand control of supply-air volume flow under the utilisation of ef ficient control strategies<br />

CO 2<br />

dependent control for optimum room conditioning with minimum energy costs.<br />

Areas of application<br />

Variable VAV control in individual rooms<br />

Supports additional functions such as:<br />

• fan control<br />

• electric reheater<br />

• 2-pipe and 4-pipe plants heating/cooling<br />

• frost-protection function<br />

• room lighting control<br />

Properties<br />

• Compact DDC VAV Controller<br />

• Location-independent static differential pressure pickup<br />

• Batter-buffered RAM for parameters, clock and<br />

calendar functions<br />

Technical description<br />

• Voltage supply 24 V~<br />

• 8 inputs<br />

• 6 outputs<br />

Product<br />

Type<br />

<strong>EY</strong>E205F002<br />

<strong>EY</strong>E206F002<br />

Designation<br />

DDC VAV controller<br />

DDC VAV controller 1 relay<br />

148<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

Power consumption<br />

Installation<br />

Weight (kg) 0,4<br />

24 V~ ± 20%, 50/60 Hz<br />

10 VA<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Humidity<br />

up to 85% rh<br />

Non-condensing<br />

Operating pressure pstat 1) ±3 kPa<br />

Standards, guidelines and directives<br />

Degree of protection IP 10 (EN 60529)<br />

Protection class II (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

EMC directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2 2)<br />

EN 61000-6-4 3)<br />

EN 55022 Class A<br />

Software Class A<br />

EN 60730-1 Appendix H<br />

Additional information<br />

Fitting instructions 0505467<br />

Product Datasheet PDS 9<strong>4.</strong>205<br />

Declaration on materials and MD 9<strong>4.</strong>205<br />

the environment<br />

Inputs<br />

For operating unit<br />

<strong>EY</strong>B250...256<br />

For temperature sensor Ni1000<br />

For <strong>com</strong>mand variable 0...10 V (Ri = 10 k Ω)<br />

For main output contact On/Off<br />

Static pressure difference 4)<br />

Pressure range<br />

0...300 Pa<br />

Linearity<br />

Type 2% FS<br />

Reproducibility<br />

Type 0,2% FS<br />

Membranes<br />

Silicone rubber LSR<br />

Positional requirements ±0,51% FS<br />

Zero point stability < 0,2% FS<br />

<strong>EY</strong>E205<br />

1<br />

1<br />

1<br />

2<br />

1<br />

<strong>EY</strong>E206<br />

1<br />

2<br />

1<br />

3<br />

1<br />

Outputs<br />

Triac switching outputs 0-I-II (24 V~, 1 A)<br />

Relay switching outputs NO (250 V~, 2 A)<br />

Analogue<br />

0...10 V (load ≥ 1 kΩ)<br />

<strong>EY</strong>E205<br />

2<br />

–<br />

1<br />

<strong>EY</strong>E206<br />

3<br />

1<br />

2<br />

1) The zero point should be recalibrated if the permissible operating pressure is exceeded.<br />

2) When the industrial standard EN61000-6-2 has to be fulf lled, the supply cables to the digital inputs (DI), the analogue<br />

inputs/outputs (AI/AO) and the meter inputs (CI) should not be longer than 30 m.<br />

3) Device <strong>com</strong>plies with interference class A.<br />

4) Due to technical plant considerations the minimum pressure difference for Vmin should not exceed 2 Pa.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

149


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-AM300: moduNet300<br />

PDS 96.010<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

novaNet-BACnet Application Master<br />

Your benefit for increased energy efficiency<br />

Open <strong>com</strong>munication for interoperable operation of the <strong>com</strong>plete optimised system.<br />

Areas of application<br />

Integration and migration of <strong>EY</strong>3600 and <strong>EY</strong>-<strong>modulo</strong> 2 systems in BACnet/IP systems and also in the<br />

<strong>EY</strong>-<strong>modulo</strong> 5 family at the automation level.<br />

Extension of BACnet functionality such as persistent trend log, exter nal scheduling, BBMD and FD.<br />

Properties<br />

• BACnet application master for novaNet<br />

• For integration of novaNet stations (<strong>EY</strong>3600,<br />

<strong>EY</strong> <strong>modulo</strong> 2) in BACnet/IP systems (<strong>EY</strong> -<strong>modulo</strong> 5)<br />

• Automatic generation of BACnet I/O objects from<br />

defined stations based on novaNet<br />

• Special functions such as Loop and Intrinsic<br />

Reporting for I/O objects<br />

• Dynamic objects such as Schedule, Calendar for<br />

optimised, time controlled systems<br />

• Dynamic trend log for the analysis of the system<br />

• Dynamic Event Enrolment objects for individual<br />

alarm handling<br />

• BACnet/IP network integration with BBMD or/and<br />

FD functionality<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

• Communication BACnet/IP (EN ISO 16484 5)<br />

• Communication with 2-wire novaNet system bus<br />

as novaNet-PC<br />

Technical description<br />

• Voltage supply: 24 V~/= (F001),<br />

230 V~ (F002)<br />

• RJ-45 plug for Ethernet 10/100Base-T<br />

(10/100 MBit/s)<br />

• 2 RS-232 interfaces for parameterisation,<br />

updates<br />

• 5 LEDs for Status, Link, Activity, Speed,<br />

novaNet-Send<br />

• Up to a total of 1000 BACnet objects<br />

• Up to 16 Notification Class objects<br />

• Up to 100 Event Enrolments<br />

• Up to 100 Schedules and 40 Calendars<br />

• Up to 50 Trend log<br />

Product<br />

Type<br />

<strong>EY</strong>-AM300F001<br />

Designation<br />

novaNet-BACnet Application Master 24 V~/=<br />

<strong>EY</strong>-AM300F002 novaNet-BACnet Application Master 230 V~<br />

Accessories<br />

Type Designation Page<br />

Manual<br />

7001007 00x moduNet300 (<strong>EY</strong>K) BACnet manual (language: x=1 (De),<br />

1)<br />

x=2 (Fr), x=3 (En))<br />

Connection cable<br />

0367842 002 Ethernet RJ45-RJ45 1,5 m<br />

1)<br />

0367842 003 Ethernet RJ45-RJ45 2,9 m<br />

1)<br />

0367842 004 Ethernet RJ45-RJ45 6 m<br />

1)<br />

0386301 001 COM DB9(f)-DB9(f) 3 m<br />

1)<br />

Connection cable<br />

0367862 001 Automation station - novaNet292 1,5 m<br />

1)<br />

0367862 002 Automation station - novaNet292 2,9 m<br />

1)<br />

0367862 003 Automation station - novaNet292 6 m<br />

1)<br />

150<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

Right of amendment reserved © 2009 Fr. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

F001<br />

24 V~ ± 20%, 50/60 Hz<br />

24 V= (18...30 V=)<br />

F002<br />

230 V~, 50/60 Hz<br />

Power consumption 10 VA<br />

Dissipated power up to 8 W<br />

Properties<br />

Number of BACnet-objects up to 1000 (total)<br />

Number of time programs up to 100 (schedules)<br />

Number of calendars up to 40 (calendars)<br />

Number of histor.<br />

Data objects<br />

up to 50 (trend Log)<br />

Log data sets (total) up to 10‘000 (Log buf fer)<br />

Number of users def. up to 100<br />

(Event enrolment objects)<br />

Interfaces, <strong>com</strong>munication<br />

COM interface (2x) DB-9 plug (male, DTE)<br />

COM 1 (RS-232) parameterisation<br />

COM 2 (RS-232) modem connection<br />

novaNet interface RJ-11 socket (6/6)<br />

2x a/b-terminals<br />

BACnet interface<br />

RJ-45 Ethernet socket<br />

10/100 Base-Tx Autosensing<br />

Communication protocol BACnet/IP<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Transport and storage temperature -25...70 °C<br />

Humidity<br />

10...85% rh<br />

Non-condensing<br />

Installation<br />

W x H x D (mm) 244 x 120 x 73<br />

Weight (kg)<br />

F001 1,1<br />

F002 0,5<br />

Standards, guidelines and directives<br />

Degree of protection IP 20 (EN 60529)<br />

Protection class I (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

CE conformity as per:<br />

Directive 2006/95/EWG EN 60730<br />

EMC directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2<br />

EN 61000-6-3<br />

EN 61000-6-4<br />

EN 55024<br />

Additional information<br />

Fitting instructions<br />

P100002334<br />

Product Datasheet PDS 96.010<br />

Declaration on materials and MD 96.010<br />

the environment<br />

Product documentation HB 7001007<br />

PICS 7010011<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

151


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Voltage supply<br />

Current consumption<br />

Dissipated power<br />

Communication<br />

Bus system<br />

novaNet<br />

Number of segments<br />

Total capacitance<br />

Total resistance<br />

Delay time<br />

Power supply for<br />

E/O converter<br />

Indicators<br />

LED<br />

Power<br />

novaNet<br />

24 V~/= ±20% or<br />

230 V~ ±10%<br />

up to 400 mA<br />

up to 5 W<br />

2-wire<br />

twisted and screened<br />

4 for novaNet copper cable<br />

of witch 3 for fibre-optic<br />

200 nF pro segment<br />

300 Ω pro segment<br />

ca. 20 µs for copper cable<br />

ca. 25 µs for fibre-optic<br />

+13 V up to 0,1 A<br />

1x green<br />

4x yellow Send/Receive<br />

Permissible ambient conditions<br />

Operating temperature 0…45 °C<br />

Transport and storage -25...70 °C<br />

temperature<br />

Humidity<br />

10...85% rh<br />

Non-condensing<br />

Installation<br />

W x H x D (mm) 244 × 120 × 72<br />

Weight (kg) 1,5<br />

Standards, guidelines and directives<br />

Degree of protection IP 20 (EN 60529) 1)<br />

Protection class I (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

Conformity as per:<br />

EMC directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2 2)<br />

EN 61000-6-4<br />

Additional information<br />

Fitting instructions<br />

P100002329<br />

Product Datasheet PDS 96.020<br />

Declaration on materials and MD 96.020<br />

the environment<br />

1) Degree of protection IP10 with terminal cover (accessory no. 0900240001).<br />

2) If industrial standard (EN 61000-6-2) has to be fulf lled, the cables for the 13 V voltage output should be no longer<br />

than 30 m.<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

155


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-BU292: moduNet292<br />

PDS 96.015<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

novaNet-Ethernet Interface<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 integrated in known IP technology.<br />

Areas of application<br />

Parameterisation of <strong>EY</strong>-<strong>modulo</strong> 2 and <strong>EY</strong>3600 stations via Inter net protocol based on Ethernet. Access for<br />

management-level software such as all the <strong>SAUTER</strong> novaPro display devices and novaNet OPC ser vers.<br />

Properties<br />

• Bus access device for the novaNet system bus<br />

with Ethernet interface<br />

• For the integration of novaNet stations (<strong>EY</strong>3600,<br />

<strong>EY</strong> <strong>modulo</strong> 2) in IP networks that are based on<br />

Ethernet (LAN/WAN)<br />

• For <strong>SAUTER</strong> CASE applications<br />

• For downloading programs to the stations<br />

• For <strong>SAUTER</strong> novaPro displays<br />

• For remote monitoring via the Inter net<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> system family<br />

• Communication TCP/IP<br />

• Communication with 2-wire novaNet system bus<br />

Technical description<br />

• Voltage supply: 230 V~, 115 V~<br />

• DIN rail mounting (F001), table<br />

model (F002)<br />

• a/b plug (F001), RJ-11 (F002) for novaNet<br />

• RJ-45 plug for Ethernet 10Base-T<br />

(10 MBit/s)<br />

• Fixed IP addressing<br />

• RS-232 interface for parameterisation,<br />

updates<br />

• 5 LEDs for Error, novaNet-Send, Power,<br />

Activity, Link<br />

Product<br />

Type<br />

<strong>EY</strong>-BU292F001<br />

<strong>EY</strong>-BU292F002<br />

Designation<br />

novaNet-Ethernet Interface (Control panel model)<br />

novaNet-Ethernet Interface (Table model)<br />

Accessories<br />

Type Designation Page<br />

Software<br />

YYD 292 F010 moduNet292 driver software, current version on CD 2) 1)<br />

Connection cable<br />

0367862 001 Automation station - moduNet292 1,5 m<br />

1)<br />

0367862 002 Automation station - moduNet292 2,9 m<br />

1)<br />

0367862 003 Automation station - moduNet292 6 m<br />

1)<br />

Connection cable<br />

0367842 002 Ethernet 1,5 m<br />

1)<br />

0367842 003 Ethernet 2,9 m<br />

1)<br />

0367842 004 Ethernet 6 m<br />

1)<br />

0386301 001 Serial cable for firmware update and software reset (DB 9)<br />

1)<br />

0386507 001 Ethernet crossover cable 3 m<br />

1)<br />

General<br />

0374509 001 3-pole plug part (supplied with F001)<br />

1)<br />

0374677 001 Mounting kit for 2 DIN-rail mounting<br />

1)<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

2) The CD must be ordered separately or it can be obtained from the Intranet.<br />

152<br />

Right of amendment reserved © 2009 Fr. Sauter AG


156<br />

Software


Management software<br />

Technical information<br />

Hardware<br />

Processor<br />

PC memory<br />

Hard drive<br />

Graphic<br />

card memory<br />

Monitor resolution<br />

Graphics<br />

CD drive<br />

Interfaces<br />

Pentium III 1,8 GHz<br />

(re<strong>com</strong>mended: 3 GHz or higher)<br />

256 MB RAM (512 MB re<strong>com</strong>.)<br />

For Vista: minimum 1 GB<br />

At least 1,8 GB (depending<br />

on plant size; 9 GB re<strong>com</strong>mended)<br />

At least 32 MB<br />

At least 800 x 600 Pixel (SVGA)<br />

VGA, SVGA and any other<br />

graphic card that supports<br />

the desktop of the operating<br />

system. Colour depth should<br />

be at least 256 colours.<br />

For installation<br />

1 mouse port<br />

2 serial interfaces (RS-232)<br />

1 parallel interface LPT for<br />

printer<br />

1 network connection<br />

1 USB port for dongle<br />

Software<br />

Operating system Client: Microsoft Windows 2000,<br />

Windows XP, Windows Vista<br />

with akt. Servicepack, Server:<br />

Windows 2003 with current<br />

service pack<br />

Web server<br />

Browser<br />

Microsoft Internet<br />

Explorer<br />

Internet Information Server<br />

(Microsoft IIS) Vers. 5.0. . IIS V7<br />

required for VISTA<br />

Any browser incorporating the<br />

SUN JAVA plug-in in<br />

version 1.5.0.60 or higher.<br />

minimum Version 6.0 with<br />

current service pack<br />

List of products<br />

NovaPro Web basic package<br />

• USB-Dongle<br />

• 1 Web-Client<br />

• Data point visualisation<br />

• Storage of historical data<br />

• Trend<br />

• Event-Viewer<br />

• Pop-Up, Sound<br />

• List-Viewer<br />

• User management<br />

• Data backup<br />

• Direct printing<br />

• Filter functions<br />

• Timer programs<br />

• Calendar<br />

• Formula package<br />

• Cyclical protocols<br />

• BACnet-Client<br />

• novaNet connection<br />

• OPC-Client<br />

• Maintenance messaging<br />

YZP510F020 Basic package<br />

incl. 500 data points<br />

Extension<br />

YZP511F010<br />

YZP511F020<br />

YZP512F010<br />

YZP513F010<br />

YZP513F020<br />

YZP513F030<br />

YZP513F040<br />

YZP513F050<br />

YZP514F010<br />

YZP514F020<br />

YZP514F030<br />

YZP514F040<br />

YZP514F050<br />

YZP514F060<br />

YZP514F070<br />

1 additional Web Client<br />

Data point extension of<br />

100 addresses<br />

I/O-Assistent<br />

(start-up and analysis tool)<br />

Provision of data<br />

pursuant to HBGA 3.0<br />

Audit Trail pursuant to FDA<br />

Event Dispatcher<br />

(SMS, voicemail, fax, e-mail)<br />

Monthly protocol pursuant to<br />

HBGA 3.0<br />

Data memory export to CSV file<br />

novaNet autodial operation<br />

Process link-up <strong>EY</strong>2400<br />

OPC server<br />

SQL server<br />

Modbus RTU / Modbus IP<br />

BACnet server<br />

Process link-up to Amadeus<br />

accounting system<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

159


Y ZP410…431: novaPro Open Suite<br />

PDS 99.410<br />

Highly integrated management level for visualisation<br />

control of technical plant.<br />

Your benefit for increased energy efficiency<br />

The management level provides you with an overview of energy and media consumption and enables<br />

you to introduce targeted optimisation measures. The effectiveness of introduced measures is immediately<br />

verifiable thanks to historical data logging.<br />

novaPro Open Software<br />

Areas of application<br />

Visualisation, control and optimisation of technical plant, for instance in building technology.<br />

Properties<br />

• Management level for visualising and controlling <strong>com</strong>plex plant in process and building<br />

technology (HVAC)<br />

• Integration of various non-Sauter systems via ODBC, DDE, SQL or OPC (more than 100 different<br />

drivers available)<br />

• BACnet Client functionality with graphic visualisation and user interface<br />

• Powerful alarm management with variable alarm forwarding via SMS, e-mail, fax, voicemail<br />

• Current web technology enables decentralised, multi-user-capable management<br />

• Centralised time switching and trend data logging for optimum energy management<br />

• Adaptable to suit plant requirements through modular scalability<br />

• Fulfils highest security demands through smartcard authentication or biometric (finger print)<br />

supported authentication<br />

• Audit Trail pursuant to FDA 21CFR Part 11. Historic logging of all system-relevant intervention<br />

• Graphic visualisation on PDA or Smartphone via GPRS, WLAN or Bluetooth<br />

Product<br />

Type Designation<br />

YZP410...431<br />

novaPro Open Suite<br />

Accessories<br />

Type Designation Page<br />

Router<br />

<strong>EY</strong>Z291 novaNet 291 novaNet-Router<br />

1)<br />

DL-Converter<br />

<strong>EY</strong>Z485 V.24/<strong>EY</strong>2400 DL-Converter<br />

1)<br />

1) Please refer to product datasheet (PDS) for further information.<br />

2) With Visualisation; Scheduler; Driver for <strong>EY</strong>3600 novaNet; 5 WEB-Clients; Report generator;<br />

PLC functionality; OPC-Server and OPC-Client.<br />

3) Send alarms as an SMS, an e-mail or a fax. Planner for organising duty technicians.<br />

160<br />

Right of amendment reserved © 2009 F r. Sauter AG


Products <strong>EY</strong>-<strong>modulo</strong> 2<br />

Technical information<br />

Electrical supply<br />

Voltage supply 230 V~ +10%, -15%,<br />

115 V~ +10%, -15%,<br />

50/60 Hz<br />

Power consumption 6 VA, < 7 W<br />

Interfaces, <strong>com</strong>munication<br />

novaNet<br />

F001<br />

1× a/b-terminals<br />

F002<br />

1× RJ-11-socket<br />

Ethernet<br />

1× RJ-45-socket<br />

10Base-T<br />

10 MBit/s<br />

Serial interface<br />

1× DB-9 (male)<br />

RS-232 to DTE (57k6, 8n1)<br />

Standard settings<br />

TCP/IP address 192.168.10.20<br />

Subnet mask 255.255.255.0<br />

TCP Port (App 1)<br />

51806 (nova292-Server)<br />

TCP Port (App 2)<br />

51807 (nova291-Emulation)<br />

Permissible ambient conditions<br />

Operating temperature 0...45 °C<br />

Storage and transport -25...70 °C<br />

temperature<br />

Humidity<br />

10...85% rh<br />

Non-condensing<br />

Installation<br />

W x H x D (mm)<br />

F001 193 × 131 × 41<br />

F002 228 × 131 × 41<br />

Weight (kg)<br />

F001 0,65<br />

F002 0,70<br />

Standards, guidelines and directives<br />

Degree of protection IP 00 (EN 60529)<br />

Protection class I (EN 60730-1)<br />

Environmental class<br />

IEC 60721 3K3<br />

CE conformity as per:<br />

Directive 2006/95/EWG EN 60650-1<br />

EMC-directive 2004/108/EG EN 61000-6-1<br />

EN 61000-6-2<br />

EN 61000-6-4<br />

Software Class A<br />

EN 60730-1 Appendix H<br />

Additional information<br />

Fitting instructions<br />

P100002338<br />

Product Datasheet PDS 96.015<br />

Declaration on materials and MD 96.015<br />

the environment<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

153


Type index<br />

Type Description Page<br />

<strong>EY</strong>-OP250F002 Touch-panel modu250; b/w; 5.7“; for novaNet 132<br />

<strong>EY</strong>-OP490F001 Local control unit modu490; with display and calendar 98<br />

<strong>EY</strong>-OP840F001 Local control unit modu840; for <strong>EY</strong>-<strong>modulo</strong> 5 automation station 66<br />

<strong>EY</strong>R203F001 Regulator moduFlex; 28 I/O 122<br />

<strong>EY</strong>-RC208F001 Room automation station; 6 relays 142<br />

<strong>EY</strong>-RC209F001 Room automation station; 10 relays 142<br />

<strong>EY</strong>-RC401F001 Room automation station; fan-coil; 24 V 110<br />

<strong>EY</strong>-RC402F001 Room automation station; fan-coil; 230 V 108<br />

<strong>EY</strong>-RC402F002 Room automation station; fan-coil; 230 V; EnOcean® 108<br />

<strong>EY</strong>-RC403F001 Room automation station; fan-coil; 230 V; 2 AO 108<br />

<strong>EY</strong>-RC403F002 Room automation station; fan-coil; 230 V; EnOcean®; 2 AO 108<br />

<strong>EY</strong>-RC415F001 Room automation station; VAV light 106<br />

<strong>EY</strong>-RC415F002 Room automation station; VAV light; EnOcean® 106<br />

<strong>EY</strong>-RC416F001 Room automation station; VAV controller 104<br />

<strong>EY</strong>-RC416F002 Room automation station; VAV controller; EnOcean® 104<br />

<strong>EY</strong>-RC502F001 Room automation station; 2 way; 18 relay 78<br />

<strong>EY</strong>-RU110F001 Radio control unit; NTC; no frame 68<br />

<strong>EY</strong>-RU141F001 Radio control unit; LCD; NTC; dXs; no frame 68<br />

<strong>EY</strong>-RU144F001 Radio control unit; LCD; NTC; dXs; 2 buttons; no frame 68<br />

<strong>EY</strong>-RU146F001 Radio control unit; LCD; NTC; dXs; 4 buttons; no frame 68<br />

<strong>EY</strong>-RU210F001 ecos 2 control unit; NTC; no frame 136<br />

<strong>EY</strong>-RU211F001 ecos 2 control unit; NTC; dXs; no frame 136<br />

<strong>EY</strong>-RU214F001 ecos 2 control unit; NTC; dXs; 2 buttons; no frame 136<br />

<strong>EY</strong>-RU216F001 Control unit ecos 2; NTC; dXs; 4 buttons; no frame 136<br />

<strong>EY</strong>-RU241F001 Control Unit; NTC Sensor; dXs; 2 buttons; no frame 138<br />

<strong>EY</strong>-RU244F001 Control Unit; NTC; dXs; fan, presence, 4 buttons; no frame 138<br />

<strong>EY</strong>-RU246F001 Control Unit; NTC; dXs; fan, presence, 6 buttons; no frame 138<br />

<strong>EY</strong>-RU310F001 ecos 5 control unit; NTC; no frame 76<br />

<strong>EY</strong>-RU311F001 ecos 5 control unit; NTC; dXs; no frame 76<br />

<strong>EY</strong>-RU314F001 ecos 5 control unit; NTC; dXs; 2 buttons; no frame 76<br />

<strong>EY</strong>-RU316F001 ecos 5 control unit; NTC; dXs; 4 buttons; no frame 76<br />

<strong>EY</strong>-RU341F001 ecos 5 control unit; LCD; NTC; dXs; no frame 74<br />

<strong>EY</strong>-RU344F001 ecos 5 control unit; LCD; NTC; dXs; 2 buttons; no frame 74<br />

<strong>EY</strong>-RU346F001 ecos 5 control unit; LCD; NTC; dXs; 4 buttons; no frame 74<br />

<strong>EY</strong>-RU481F001 ecos 4 control unit; Sensors 102<br />

<strong>EY</strong>-RU481F002 ecos 4 control unit; Sensor; motion 102<br />

<strong>EY</strong>-RU481F003 ecos 4 control unit; Sensor; motion; dXs 102<br />

<strong>EY</strong>-RU482F001 ecos 4 control unit; LCD; NTC; FCU 101<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

163


<strong>SAUTER</strong> type index overview.<br />

Type Description Page<br />

<strong>EY</strong>-RU483F001 ecos 4 control unit; LCD; NTC; VAV 100<br />

<strong>EY</strong>-SU106F001 Button unit for radio control unit; 6 buttons; no frame 70<br />

<strong>EY</strong>-SU306F001 Button unit for control unit; 6 buttons; no frame 72, 140<br />

YZP410F001 novaPro Open; basic package 500 addresses 160<br />

YZP410F101 novaPro Open; basic package 2000 addresses 160<br />

YZP410F201 novaPro Open; basic package 5000 addresses 160<br />

YZP410F301 novaPro Open; basic package 65000 addresses 160<br />

YZP416F101 novaPro Open; Driver <strong>EY</strong>2400 160<br />

YZP416F201 novaPro Open; Driver <strong>EY</strong>3600 für Wizcon (in YZP410) 160<br />

YZP416F302 novaPro Open; Driver GN Johnson System 91; N2 Protection 160<br />

YZP416F303 novaPro Open; Driver Landis & Gyr PRV1 controller 160<br />

YZP416F304 novaPro Open; Driver Landis & Gyr PRV2 controller 160<br />

YZP416F307 novaPro Open; OPC Server Lonworks through LNS data 160<br />

YZP416F308 novaPro Open; OPC Server Lonworks native LNS/LCA 160<br />

YZP416F311 novaPro Open; Driver native BACnet (vpiwnbcn.dll) 160<br />

YZP416F312 novaPro Open; Siemens SIMATIC S5/S7; TCP/IP (vpiwnstp) 160<br />

YZP417F101 novaPro Open; Access for 10 WEB Clients 160<br />

YZP417F201 novaPro Open; Access for 20 WEB Clients 160<br />

YZP417F301 novaPro Open; Access for 100 WEB Clients 160<br />

YZP418F001 novaPro Open; AAM Advanced Alarm Module 160<br />

YZP418F101 novaPro Open; TTS Text To Speech 160<br />

YZP419F101 novaPro Open; Upgrade 500 to 2000 addresses 160<br />

YZP419F201 novaPro Open; Upgrade 2000 to 5000 addresses 160<br />

YZP419F301 novaPro Open; Upgrade 5000 to 65000 addresses 160<br />

YZP420F003 novaPro Open; Version update; previous version to latest 160<br />

YZP420F004 novaPro Open; older Version update to actual version 160<br />

YZP420F999 novaPro Open; Suite current CD 160<br />

YZP421F001 novaPro Open; nova scheduler Enterprise edition 160<br />

YZP421F002 novaPro Open; novaPLC Upgrade from 500 to 65000 Addresses 160<br />

YZP422F001 novaPro Open; exchange of a dongle parallel plug by USB 160<br />

YZP423F001 novaPro Open; XL Report; Reporting Tool 160<br />

YZP425F001 novaPro Open; eToken PKI client licence 160<br />

YZP425F002 novaPro Open; eToken USB 32K 160<br />

YZP425F003 novaPro Open; eToken USB 64K 160<br />

YZP426F001 novaPro Open; Biometry PID enrolment licence 160<br />

YZP426F002 novaPro Open; Biometry PID verification licence 160<br />

YZP427F001 novaPro Open; FPS single flat silicon USB 160<br />

YZP427F002 novaPro Open; FPS single flat optical USB desktop 160<br />

164<br />

Right of amendment reserved © 2009 F r. Sauter AG


Software<br />

Open management level,<br />

tailored to your individual needs.<br />

novaPro Open Software<br />

novaPro Web<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

157


Management software<br />

Technical information<br />

Hardware<br />

Processor<br />

PC memory<br />

Hard drive<br />

Graphic card<br />

memory<br />

Monitor resolution<br />

Graphics<br />

DVD drive<br />

Interfaces<br />

Pentium III 800 MHz<br />

(re<strong>com</strong>mended: 2 GHz or higher)<br />

256 MB RAM (512 MB re<strong>com</strong>.)<br />

For Vista: minimum 1 GByte<br />

at least 1,8 GB (depending on<br />

plant size; 9 GB re<strong>com</strong>mended)<br />

32 MB<br />

at least 800 x 600 Pixel (SVGA)<br />

VGA, SVGA and any other<br />

graphic card that supports<br />

the desktop of the operating<br />

system. Colour depth<br />

should be at least 256 colours.<br />

for installation<br />

1 mouse port<br />

2 serial interfaces (RS-232)<br />

1 network connection<br />

1 USB port for dongle<br />

Software<br />

Operating system<br />

Web server<br />

Browser<br />

Windows XP Pro SP2, Windows<br />

2003 Server SP1, Windows Vista<br />

Business or Ultimate<br />

Internet Information Server<br />

(Microsoft IIS) IIS V7 required<br />

for VISTA<br />

Any browser incorporating the<br />

SUN JAVA plug-in in<br />

version 1.5.0.60 or higher.<br />

Microsoft Internet Minimum Version 6.0 with<br />

Explorer or 7.0<br />

List of products<br />

NovaPro Open basic package 2)<br />

YZP410F001 Basic package incl. 500 addresses<br />

YZP410F101 Basic package incl. 5‘000<br />

addresses<br />

YZP410F201 Basic package incl. 5‘000<br />

addresses<br />

YZP410F301 Basic package incl. 65‘000<br />

addresses<br />

Options<br />

YZP416F101 Drive <strong>EY</strong>2400<br />

YZP416F201 Driver <strong>EY</strong>3600 for Wizcon<br />

(contained in YZP410F . . . )<br />

YZP416F302 Driver for Johnson Controls<br />

System 91, N2 Protocol<br />

YZP416F303 Driver for Landis & Gyr<br />

PRV 1 Controller<br />

YZP416F304 Driver for Landis & Gyr<br />

PRV 2 Controller<br />

YZP416F307 OPC Server Lonworks<br />

through LNS database<br />

YZP416F308 OPC Server Lonworks<br />

native LNS / LCA<br />

YZP416F311 Driver for native BACnet<br />

(vpiwnbcn.dll)<br />

YZP416F312 Driver for Siemens SIMATIC<br />

S5 / S7, TCP/IP (vpiwnstp)<br />

YZP417F101 Access for 10 WEB Clients<br />

YZP417F201 Access for 20 WEB Clients<br />

YZP417F301 Access for 100 WEB Clients<br />

YZP418F001 AAM Advanced Alarm Module 3)<br />

YZP418F101 TTS Text to Speech<br />

(Voicemail add-on for the<br />

Advanced Alarm Module)<br />

YZP419F101 Upgrade from 500 to 2‘000 addresses<br />

YZP419F201 Upgrade from 2‘000 to 5‘000<br />

addresses<br />

YZP419F301 Upgrade from 5‘000 to 65‘000<br />

addresses<br />

YZP420F003 V ersion update from previous<br />

version to current version<br />

YZP420F004 V ersion update from older<br />

version to current version<br />

YZP420F999 novaPro Open Suite - current CD<br />

YZP421F001 novaScheduler Enterprise Edition<br />

YZP421F002 novaPLC Upgrade from 500 to<br />

65‘000 addresses<br />

YZP422F001 Repl. parallel dongle for USB<br />

YZP423F001 XL Report<br />

YZP425F001 eToken PKI Client Licence<br />

YZP425F002 eToken USB 32K<br />

YZP425F003 eToken USB 64K<br />

YZP426F001 Biometry PID Enrolment Licence<br />

YZP426F002 Biometry PID Verification Licence<br />

YZP427F001 FPS Single Flat Silicon USB<br />

YZP427F002 FPS Single Flat Optical USB<br />

Desktop<br />

YZP427F003 FPS Single Flat Optical USB Kiosk<br />

YZP427F004 FPS Single Flat Optical Ether net<br />

YZP427F005 FPS Single Flat Optical FBI USB<br />

YZP427F006 FPS Single Flat/Rolled Optical<br />

FBI USB<br />

YZP428F001 WizLogger<br />

YZP429F001 WizAudit<br />

YZP430F001 LDAPE Enrolment Lizenz<br />

YZP430F002 LDAPV Verification Lizenz<br />

YZP431F001 Licence PDA per web client (JVM)<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

161


Type index<br />

Type Description Page<br />

YZP427F003 novaPro Open; FPS single flat optical USB kiosk 160<br />

YZP427F004 novaPro Open; FPS single flat optical Ether net 160<br />

YZP427F005 novaPro Open; FPS single flat optical FBI USB 160<br />

YZP427F006 novaPro Open; FPS single flat/rolled optical FBI USB 160<br />

YZP428F001 novaPro Open; WizLogger 160<br />

YZP429F001 novaPro Open; WizAudit 160<br />

YZP430F001 novaPro Open; LDAPE enrolment licence 160<br />

YZP430F002 novaPro Open; LDAPV verification licence 160<br />

YZP431F001 novaPro Open; Licence PDA per web client (JVM) 160<br />

YZP510F010 novaPro Web; Basic package light inclusive 100 data points 158<br />

YZP510F020 novaPro Web; Basic package with USB dongle; inclusive 500 data points 158<br />

YZP510F030 novaPro Web; Basic; runtime; no editors; inclusive 1000 data points 158<br />

YZP511F010 novaPro Web; 1 additional web client 158<br />

YZP511F020 novaPro Web; Data point expansion; by 100 addresses 158<br />

YZP512F010 novaPro Web; I/O assistant; Start-up and analysis tool 158<br />

YZP513F010 novaPro Web; Data provision; according to HBGA 3.0 158<br />

YZP513F020 novaPro Web; FDA audit trail 158<br />

YZP513F030 novaPro Web; Event dispatcher; (SMS; voice; fax; e-mail) 158<br />

YZP513F040 novaPro Web; Monthly reports ; according to HBGA 3.0 158<br />

YZP513F050 novaPro Web; Export of date into CSV-file 158<br />

YZP514F010 novaPro Web; novaNet circuit switching 158<br />

YZP514F020 novaPro Web; <strong>EY</strong>2400 process link 158<br />

YZP514F030 novaPro Web; OPC server 158<br />

YZP514F040 novaPro Web; SQL Server 158<br />

YZP514F050 novaPro Web; Modbus RTU / Modbus IP 158<br />

YZP514F060 novaPro Web; BACnet server 158<br />

YZP514F070 novaPro Web; Process link; Amadeus booking system 158<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

165


<strong>EY</strong>-<strong>modulo</strong> 5<br />

<strong>EY</strong>-BU180: moduNet180<br />

PDS 96.020<br />

<strong>EY</strong>-<strong>modulo</strong> 4<br />

<strong>EY</strong>-<strong>modulo</strong> 2<br />

Repeater System Bus novaNet<br />

Your benefit for increased energy efficiency<br />

<strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 – Technology proven a thousand times over, with a new design.<br />

Areas of application<br />

Segment extension for extensive novaNet networks for <strong>EY</strong> -<strong>modulo</strong> 2 family and <strong>EY</strong>3600 systems.<br />

Properties<br />

• Device for the physical extension of the<br />

novaNet system bus<br />

• Transparent repeater with 4 channels with equal rights<br />

• Three of four channels with connector for RS232<br />

(f bre-optic cable)<br />

• Part of the <strong>SAUTER</strong> <strong>EY</strong>-<strong>modulo</strong> 2 family<br />

• Communication with 2-wire novaNet system bus<br />

Technical description<br />

• Voltage supply: 24 V~/=, 230 V~<br />

• Current consumption: 400 mA<br />

• 4 channels with various connection possibilities<br />

for copper cable, 3 connections for<br />

f bre-optic cable<br />

• Delay time: ~20 µs for copper, ~25 µs for<br />

fibre-optic cable<br />

• 4 send/receive LEDs for novaNet signals<br />

Product<br />

Type Designation<br />

<strong>EY</strong>-BU180F001 novaNet Repeater 24 V~/=, 230V~<br />

Accessories<br />

Type Description Page<br />

General<br />

0900420001 Terminal cover (240 mm) pack à 2 pcs.<br />

1)<br />

1) Please refer to product datasheet (PDS) for fur ther information.<br />

154<br />

Right of amendment reserved © 2009 Fr. Sauter AG


<strong>SAUTER</strong> Accessories overview.<br />

Accessories<br />

Description<br />

0367829001 Fixing bracket for panel modu240<br />

0367841001 Terminal cover<br />

0367842001 Connecting cable 0.35 cm; modu240 in front<br />

0367842002 Connecting cable Ethernet; 1.5 m; modu240 - AS<br />

0367842003 Connecting cable Ethernet; 2.9 m; modu240 - AS<br />

0367842004 Connecting cable Ethernet; 6.0 m; modu240 - AS<br />

0367862001 Connecting cable; novaNet 1.5 m<br />

0367862002 Connecting cable; novaNet 2.9 m<br />

0367862003 Connecting cable; novaNet 6.0 m<br />

0367878001 Wall or hut-rail holder modu240<br />

0367880001 Desktop stand modu240<br />

0367883002 Empty EPROM 1Mbit (User-EPROM) 5 pieces<br />

0374452002 Labels; self-adhesive 800 pieces for modu164<br />

0374452003 Labels; self-adhesive 400 pieces for modu165<br />

0374452004 Labels; self-adhesive 1000 pieces for modu170<br />

0374452005 Labels; self-adhesive 640 pieces for modu174<br />

0374494001 Operating pen with holder; for modu250<br />

0374509001 Plug 3-Pin for modu250<br />

0374515001 Set IP65 for modu250<br />

0374677001 Installation Kit for 2-DIN Rail (for moduNET292, <strong>EY</strong>-BU292F001)<br />

0374680001 Seal IP 65 for modu250<br />

0386301001 Connecting cable 3.0 m; 291-PC; novaNet<br />

0386507001 Cable Crossover Ethernet; 3 m; C AT-5<br />

0501174002 Micro program modu225 for modu240<br />

0900240001 Terminal covers; 240 mm; 2 pieces<br />

0900240002 Terminal covers; 295 mm; 2pieces<br />

0900240010 Wiring box 240 mm<br />

0900240011 Wiring box 295 mm<br />

0920000020 Front inserts for moduLink164…174; 25 sheets at 6 pieces<br />

0920000101 Front inserts for modu630…670; 10 sheets at 6 pieces<br />

0930240511 Panel fitting kit; with RJ-11 cable (6 m) quadruple<br />

0940240101 Single frame; white; For flush-mounted socket; 10 pieces<br />

0940240201 Double frame; white; For flush-mounted socket; 10 pieces<br />

0940240301 Single orifice plate; white; for wall mounting; 10 pieces<br />

0940240401 Double orifice plate; white; for wall mounting; 10 pieces<br />

0940240501 Single cable cover; for surface mounting cable duct; 10 pieces<br />

0940240601 Double cable cover; for surf-mounting cable duct; 10 pieces<br />

0940240701 Mounting plate; single; for external frame; 10 pieces<br />

166<br />

Right of amendment reserved © 2009 F r. Sauter AG


YZP510…514: novaPro Web<br />

PDS 99.420<br />

BACnet/IP management level for visualisation and<br />

control of technical plant.<br />

Your benefit for increased energy efficiency<br />

The management level provides you with an overview of energy and media consumption and enables<br />

you to introduce targeted optimisation measures. The effectiveness of introduced measures is immediately<br />

verifiable thanks to historical data logging.<br />

novaPro Web<br />

Areas of application<br />

Visualisation, control and optimisation of technical plant, for instance in building technology.<br />

Properties<br />

• Management level for visualising and controlling <strong>com</strong>plex MSR building technology plant (HVAC)<br />

• Native BACnet client with object-oriented data structures<br />

• Visualisation and operation via dynamic plant images or lists<br />

• Plant images presented in tree structure for speedy navigation<br />

• Powerful alarm management with variable alarm forwarding via SMS, e-mail, fax, voicemail<br />

• Automatic trend curve definition in plant images and/or plant lists<br />

• Dynamic plant list updating<br />

• Alarm monitoring with entries in an event journal and operation protocol with alarm logging to<br />

alarm printer or file<br />

• Hierarchical access protection<br />

• Logging and filing of historical data with visualisation in trend curves<br />

• Audit Trail with historical logging of all system-relevant interventions<br />

• Centralised time switching and trend data logging for optimum energy management<br />

• Product information on the monitored aggregates (spare parts details, data sheets, etc.) available<br />

online from the system<br />

Product<br />

Type Designation<br />

YZP510...514 novaPro Web<br />

Accessories<br />

Type Designation Page<br />

Router<br />

<strong>EY</strong>Z291F001 novaNet 291 novaNet-Router<br />

1)<br />

DL-Converter<br />

<strong>EY</strong>Z485F001 V.24/<strong>EY</strong>2400 DL-Converter<br />

1)<br />

Interface<br />

<strong>EY</strong>-BU292F001 novaNet Ethernet interface for switch cabinet installation 152<br />

<strong>EY</strong>-BU292F002 novaNet Ethernet interface as a table-top model 152<br />

1) Please refer to product datasheet (PDS) for further information.<br />

158<br />

Right of amendment reserved © 2009 F r. Sauter AG


<strong>SAUTER</strong> type index overview.<br />

Type Description Page<br />

<strong>EY</strong>-AC430F001 Controller RTU; HP; UV modu430; 5 UI; 5 triac 2 AO; plug-in 94<br />

<strong>EY</strong>-AM300F001 Application Master moduNet300; novaNet-BACnet; 24 V~/= 150<br />

<strong>EY</strong>-AM300F002 Application Master moduNet300; novaNet-BACnet; 230 V~ 150<br />

<strong>EY</strong>-AS200F001 Automation station; <strong>com</strong>pact; modu200; 34 I/O 120<br />

<strong>EY</strong>-AS210F001 Automation station; <strong>com</strong>pact; modu210; 42 I/O 118<br />

<strong>EY</strong>-AS225F001 Automation station modu225; 42 I/O; with up to 5 moduLink extensible up to 102 I/O October ´08 116<br />

<strong>EY</strong>-AS420F001 Automation station; <strong>com</strong>pact; modu420; 6 UI; 2 UO; 5 Triac 92<br />

<strong>EY</strong>-AS421F001 Automation station; <strong>com</strong>pact; modu421; 10 UI; 8 UO 90<br />

<strong>EY</strong>-AS422F001 Automation station; <strong>com</strong>pact; modu422; 12 UI; 12 UO 88<br />

<strong>EY</strong>-AS422F002 Automation station; <strong>com</strong>pact; modu422; 12 UI; 12 UO; HOA switch 88<br />

<strong>EY</strong>-AS525F001 Automation station; modu525; 26-154 I/O; BACnet/IP; Web 54<br />

<strong>EY</strong>-BU180F001 novaNet repeater moduNet180; 4-port; 24 V~/= 154<br />

<strong>EY</strong>-BU180F002 novaNet repeater moduNet180; 4port; 230 V~ 154<br />

<strong>EY</strong>-BU292F001 novaNet-Ethernet moduNet292; DIN rail installation 152<br />

<strong>EY</strong>-BU292F002 novaNet-Ethernet interface moduNet292; Desktop model 152<br />

<strong>EY</strong>-CM710F010 Communication module moduCom; RS232; Modbus/RTU master 82<br />

<strong>EY</strong>-CM710F020 Communication module moduCom; RS232; M-bus 82<br />

<strong>EY</strong>-CM720F010 Communication module moduCom; RS485; Modbus/RTU master 80<br />

<strong>EY</strong>E200F001 Room automation station; 3 relays 144<br />

<strong>EY</strong>E200F002 Room automation station; 4 relays 144<br />

<strong>EY</strong>E202F001 Room automation station; 3 relays 146<br />

<strong>EY</strong>E205F002 Room automation station; VAV; no relay 148<br />

<strong>EY</strong>E206F002 Room automation station; VAV; 1 relay 148<br />

<strong>EY</strong>-FM164F001 Remote field module for modu225; 4 DO (A-0-I) 130<br />

<strong>EY</strong>-FM165F001 Remote field module for modu225; 2 DO (A-0-I-II) 128<br />

<strong>EY</strong>-FM170F001 Remote field module for modu225; 4 AO 126<br />

<strong>EY</strong>-FM174F001 Remote field module for modu225; 16 DI 124<br />

<strong>EY</strong>-IO471F002 Automation station modu471; Remote I/O; 12 UI; 12 DO triac 96<br />

<strong>EY</strong>-IO530F001 I/O: Input module modu530; 8 UI/8 DI (universal/digital) 56<br />

<strong>EY</strong>-IO550F001 I/O: Output module modu550; 6 DO (relays) 58<br />

<strong>EY</strong>-IO551F001 I/O: Output module modu551; 16 DO (open collector) 60<br />

<strong>EY</strong>-IO570F001 I/O: Input/output module modu570; 8 UI/4 AO (universal/analogue) 62<br />

<strong>EY</strong>-LO630F001 LO: LED signalling modu630; 16 DI 64<br />

<strong>EY</strong>-LO650F001 LO: Control unit with LED modu650; 6 DO (A-0-I) 64<br />

<strong>EY</strong>-LO650F002 LO: Control unit with LED modu650; 3 DO (A-0-I-II) 64<br />

<strong>EY</strong>-LO670F001 LO: Control unit with LED modu670; 8 DI/4 AO 64<br />

<strong>EY</strong>-OP240F001 Local operating unit modu240; for automation station 134<br />

<strong>EY</strong>-OP250F001 Touch-panel modu250; colour; 5.7“; for novaNet 132<br />

162<br />

Right of amendment reserved © 2009 F r. Sauter AG


Type index<br />

Accessories<br />

Description<br />

0940240801 Mounting plate; double; for exter nal frame; 10 pieces<br />

0949241301 Plexiglas blanking piece; single (10 pieces)<br />

0970360510 3-pin pin plug (supplied)<br />

0970360511 3-pin T-plug for uninterruptible bus disconnection<br />

0970360520 DB-9 terminal block<br />

Right of amendment reserved © 2009 Fr. Sauter AG<br />

167


Summary of technical characters and symbols.<br />

Detectors<br />

Room temperature<br />

T<br />

Relative room humidity<br />

H%<br />

Temperature<br />

T<br />

Relative humidity (stem)<br />

H%<br />

Outside temperature<br />

T<br />

Absolute humidity (stem)<br />

Hx<br />

Duct pressure<br />

P<br />

Monitors<br />

Temperature<br />

Humidity (relative)<br />

T H%<br />

Frost protection<br />

T<br />

Pressure<br />

P<br />

Valves<br />

Butterfly valve (continuous)<br />

Butterfly valve<br />

Three-way valve (continuous)<br />

Three-way valve<br />

Valve (continuous)<br />

Valve<br />

Pumps<br />

Pump<br />

Pump with frequency converter<br />

FU<br />

Heating<br />

Boiler<br />

Converter (heat exchanger)<br />

1<br />

168<br />

Right of amendment reserved © 2009 F r. Sauter AG


Know-how<br />

Consumer (radiator)<br />

Expansion<br />

Ventilation<br />

Filter (with supervision)<br />

PD<br />

Silencer<br />

VAV unit (constant)<br />

VAV unit (variable)<br />

Air damper (continuous)<br />

Air damper<br />

Air heater<br />

Air cooler<br />

Fan (one-step)<br />

1<br />

Fan with frequency converter<br />

N<br />

Cooling<br />

Refrigerating machine<br />

Heat pump<br />

R<br />

P<br />

Recooling condenser<br />

Ice storage<br />

Miscellaneous<br />

Counter<br />

000<br />

Service Switch<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

169


Our customers stay totally informed about the whys<br />

and wherefores – <strong>SAUTER</strong> training keeps you at the<br />

leading edge of building management.<br />

<strong>SAUTER</strong> training – from building automation basics to the latest<br />

innovative advances.<br />

Planners, installation managers, <strong>SAUTER</strong> staf f, building operators – <strong>com</strong>pact specialist<br />

seminars spread know-how around the <strong>com</strong>munity involved with our automation systems,<br />

reaching well beyond the material usually covered in specific courses. Our training<br />

programme covers ever y aspect of project management, operating, and energy audits<br />

for optimal deployment of power resources.<br />

<strong>SAUTER</strong> Academy – specialist know-how for our customers.<br />

We linked up with Winterthur Technical College (Schweizerische Technische Fachschule<br />

Winterthur, STFW) and the Technician & IT Training College in Zug (Zuger Techniker- und<br />

Informatikschule, zti) to develop a series of specialised seminars that bring participants up<br />

to speed with the latest developments, and impart practical knowledge that they can put<br />

to use right away. Thoroughly qualified lecturers are on hand to teach the fundamentals of<br />

installation and control technology. Not only do you get to grips with <strong>SAUTER</strong> equipment<br />

and systems, after wards you will also be executing building automation projects with<br />

even greater professionalism.<br />

<strong>SAUTER</strong> custom seminars – teaching just what you need to know.<br />

Our in-house experts deliver practical training tailored to individual needs, and focused<br />

on your own installation. Yo u can then handle day-to-day operations with confidence,<br />

plus you have the know-how necessary for getting the most out of your <strong>SAUTER</strong> system.<br />

In developing a training scheme especially for you and your staf f, we naturally listen<br />

to what you want. Ask us! We are always open to individual requests.<br />

170<br />

Right of amendment reserved © 2009 F r. Sauter AG


SWISS<br />

C E R TIFI C A TI O N<br />

SCESm 002, 023<br />

X. Edelmann, Präsident SQS T. Zahner, Geschäftsführer SQS<br />

Swiss Made<br />

IQNet Partners*:<br />

AENOR Spain AFAQ AFNOR France AIB-Vinçotte International Belgium ANCE Mexico APCER Portugal CISQ Italy CQC China<br />

CQM China CQS Czech Republic Cro Cert Croatia DQS Germany DS Denmark ELOT Greece FCAV Brazil<br />

FONDONORMA Venezuela HKQAA Hong Kong China ICONTEC Colombia IMNC Mexico Inspecta Certification Finland<br />

IRAM Argentina JQA Japan KFQ Korea MSZT Hungary Nemko AS Norway NSAI Ireland PCBC Poland QMI Canada<br />

Quality Austria Austria RR Russia SAI Global Australia SII Israel SIQ Slovenia SIRIM QAS International Malaysia<br />

SQS Switzerland SRAC Romania TEST St Petersburg Russia YUQS Serbia<br />

IQNet is represented in the USA by: AFAQ AFNOR, AIB-Vinçotte International, CISQ, DQS, NSAI Inc., QMI and SAI Global<br />

* The list of IQNet partners is valid at the time of issue of this certificate. Updated information is available under www.iqnet-certification.<strong>com</strong><br />

Training & certificates<br />

When the customers are satisf ed,<br />

you know that the technology is excellent.<br />

<strong>SAUTER</strong> is ISO-cer tified and conforms to international standards .<br />

You can take it for granted that <strong>SAUTER</strong> meets internationally recognised standards<br />

of quality, environmental protection and occupational safety. Our management<br />

system, cer tified throughout the group, for ms the basis for <strong>com</strong>plete SQS cer tification<br />

(Swiss Association for Quality and Management Systems) for all <strong>SAUTER</strong> <strong>com</strong>panies.<br />

<strong>SAUTER</strong> is certified in these areas:<br />

• Quality, environment and occupational safety:<br />

ISO 9001, ISO 14001, OHSAS 18001<br />

• Group-wide quality management: ISO 9001:2000<br />

• Environmental management: ISO 14001:2004<br />

• Occupational safety management: OHSAS 18001:1999<br />

• BACnet<br />

• eu.bac<br />

• LON<br />

Zertifikat<br />

Die SQS bescheinigt hiermit, dass nachstehend genanntes Unternehmen über ein Managementsystem<br />

verfügt, welches den Anforderungen der aufgeführten normativen Grundlagen entspricht.<br />

Fr. Sauter AG<br />

CH-4016 Basel<br />

Zertifizierter Bereich<br />

Ganzes Unternehmen<br />

Tätigkeitsgebiet<br />

Building Control<br />

Normative Grundlagen<br />

ISO 9001:2000 Qualitätsmanagement-System<br />

ISO 14001:2004 Umweltmanagement-System<br />

OHSAS Arbeitssicherheits- und<br />

18001:2007 Gesundheitsschutz-Managementsystem<br />

CERTIFICATE<br />

IQNet and SQS<br />

hereby certify that the organization<br />

Fr. Sauter AG<br />

CH-4016 Basle<br />

Certified area<br />

Whole Company<br />

Field of activity<br />

Building Control<br />

has implemented and maintains a<br />

Management System<br />

which fulfills the requirements of the following standards<br />

ISO 9001:2000 / ISO 14001:2004 / OHSAS 18001:2007<br />

Scope No: 19<br />

Issued on: 2008-08-10<br />

Validity date: 2011-08-09<br />

Registration Number: CH-10805<br />

LICENCE<br />

LICENCE<br />

Number: 020708<br />

Fr. Sauter AG<br />

received the licence to use the eu.bac mark for the product<br />

<strong>EY</strong>E202F001<br />

for the application(s)<br />

Fan Coil Unit System<br />

based on the certification rules of eu.bac<br />

and the Certificate 03001<br />

This licence will expire on 29 October 2012<br />

020708<br />

Schweizerische Vereinigung für<br />

Dieses SQS-Zertifikat hat Gültigkeit<br />

Qualitäts- und Management-Systeme SQS bis und mit 9. August 2011<br />

Bernstrasse 103, CH-3052 Zollikofen Scope-Nummer 19<br />

Ausgabedatum: 10. August 2008<br />

Registrierungsnummer 10805<br />

René Wasmer<br />

President of IQNet<br />

Theodor Zahner<br />

Managing Director SQS<br />

29 October 2007<br />

Managing Director Winfried Brandt<br />

Frankfurt am Main<br />

eu.bac<br />

european building automation and <strong>controls</strong> Association - eu.bac<br />

Lyoner Straße 18 - 60528 Frankfurt am Main - Germany<br />

Right of amendment reserved © 2009 F r. Sauter AG<br />

171


Notes<br />

172


Notes<br />

173


Notes<br />

174


Systems<br />

Components<br />

Services<br />

Facility Management<br />

70011000003 V12<br />

<strong>SAUTER</strong> HeadOffice<br />

Fr. Sauter AG Im Surinam 55 CH-4016 Basle<br />

• •<br />

Tel. +41 (0) 61 69 55-555 Fax +41 (0) 61 69 55-510<br />

•<br />

info@<strong>sauter</strong>-<strong>controls</strong>.<strong>com</strong> www.<strong>sauter</strong>-<strong>controls</strong>.<strong>com</strong><br />

•<br />

Subject to modifications © 2009 Fr. Sauter AG

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!