Intelligent Solutions for Building Services ISSUE 19<br />
<strong>SAV</strong>’S <strong>NEW</strong> INTEGRAL BYPASS OFFERS<br />
IN-BUILT AUTOMATIC PUMP PROTECTION<br />
S<br />
<strong>When</strong> <strong>it</strong> <strong>comes</strong> <strong>to</strong> <strong>pipes</strong><br />
<strong>size</strong> <strong>does</strong> <strong>matter</strong><br />
Energy consultant Chris Parsloe highlights a key feature<br />
of the service provided by <strong>SAV</strong> Modules<br />
S<br />
izing of the multilayer <strong>pipes</strong>,<br />
manifolds and valves that make<br />
up the FloCon modules is an essential<br />
feature of the <strong>SAV</strong> service. W<strong>it</strong>hout this<br />
facil<strong>it</strong>y the design engineer would be<br />
faced w<strong>it</strong>h the daunting task of<br />
<strong>SAV</strong>’S <strong>NEW</strong> MAN IN<br />
WALES AND THE WEST<br />
S<br />
AV Modules<br />
has appointed<br />
David Edge as area<br />
sales manager<br />
covering Wales<br />
and the southwest<br />
of England.<br />
He will be based at<br />
Penarth near Cardiff, w<strong>it</strong>hin easy<br />
reach of specifiers and projects in<br />
South Wales, Bris<strong>to</strong>l and the south<br />
western peninsular.<br />
The appointment underlines <strong>SAV</strong>'s<br />
conviction that the UK market for<br />
energy saving, variable volume<br />
technology is opening up - and fast!<br />
His career has included appointments<br />
w<strong>it</strong>h a building services consultancy<br />
in Bridgend and a mechanical and<br />
electrical contrac<strong>to</strong>r based in Cardiff.<br />
selecting each<br />
component,<br />
calculating <strong>it</strong>s<br />
pressure loss and<br />
summating the<br />
losses <strong>to</strong> give an<br />
overall resistance.<br />
The only data the<br />
client needs <strong>to</strong> provide are the flow<br />
rates and pressure losses through the<br />
terminal un<strong>it</strong>s, plus some indication<br />
of the maximum lengths of<br />
multilayer pipe between manifolds<br />
and terminals. This data is required in<br />
order <strong>to</strong> <strong>size</strong> the 2-port control valves<br />
and the governing differential<br />
pressure control valves.<br />
Sizing of these two key components is<br />
the trickiest part of the exercise. In<br />
order <strong>to</strong> achieve good author<strong>it</strong>y, the 2-<br />
port valve must be <strong>size</strong>d such that the<br />
pressure loss across <strong>it</strong> is a significant<br />
proportion of the <strong>to</strong>tal pressure loss<br />
controlled constant by the DPCV. Due<br />
<strong>to</strong> the uniform pattern of the modular<br />
arrangement, this calculation can<br />
usually be au<strong>to</strong>mated.<br />
There’s no subst<strong>it</strong>ute for an<br />
experienced engineer’s input <strong>to</strong> the<br />
sizing process!<br />
AV Modules has announced an<br />
enhancement the company’s<br />
FloCon Commissioning Module design.<br />
In future all FloCon un<strong>it</strong>s will be<br />
supplied ready f<strong>it</strong>ted w<strong>it</strong>h a bypass that<br />
ensures that system flow never falls<br />
below 10%. This offers a simple, but<br />
highly effective, solution <strong>to</strong> the<br />
“Achille’s Heel” of the variable volume<br />
approach <strong>to</strong> energy saving by providing<br />
au<strong>to</strong>matic protection for expensive<br />
variable speed pumping systems, which<br />
cannot be allowed <strong>to</strong> pump against a<br />
closed system.<br />
The new <strong>SAV</strong> feature will also improve<br />
system response time by ensuring that<br />
there is some heating or chilled water in<br />
the local pipework at all times.<br />
The bypass addresses another<br />
frequent concern <strong>to</strong> consultants by<br />
ensuring good “local” circulation of<br />
chemicals added <strong>to</strong> the system water<br />
<strong>to</strong> combat pseudomonads. These slime<br />
forming organisms can be a problem in<br />
closed circu<strong>it</strong> lower temperature<br />
systems, especially those w<strong>it</strong>h nil or<br />
low levels of oxygen.<br />
Bypasses will be an integral feature of<br />
All <strong>SAV</strong> FloCon Modules – <strong>size</strong>d and<br />
selected <strong>to</strong> match individual<br />
application requirements. Pump<br />
selection is unlikely <strong>to</strong> be affected in<br />
the major<strong>it</strong>y of cases.<br />
The technique makes a perfect match<br />
for the Differential Pressure Control<br />
Valves (DPCV’s) used by <strong>SAV</strong> Modules.<br />
To ensure that the system is completely<br />
“future-proof” all <strong>SAV</strong> Commissioning<br />
Modules now also incorporate a spacer<br />
section <strong>to</strong> make room for the integration<br />
of an energy meter should this ever be<br />
required.<br />
Continued on page 2<br />
SA-COC-001904
Continued from page 1<br />
Pioneered<br />
<strong>SAV</strong> pioneered the modular concept for<br />
distribution of hot and chilled water in<br />
heating and air cond<strong>it</strong>ioning systems.<br />
The <strong>SAV</strong> FloCon Commissioning<br />
Modules is now a standard solution for<br />
use w<strong>it</strong>h 2 and 4-pipe fan coil systems<br />
and chilled beams.<br />
Now a simple, but highly effective<br />
improvement perm<strong>it</strong>s even more<br />
efficient performance. <strong>SAV</strong> FloCon<br />
Commissioning Modules can now be<br />
supplied w<strong>it</strong>h an integral 10% bypass<br />
already f<strong>it</strong>ted.<br />
The option <strong>to</strong> incorporate small, in-built<br />
Differential Pressure Control Valves<br />
(DPCV's) has always been a major<br />
feature of <strong>SAV</strong> FloCon Module design.<br />
FloCon Commissioning Modules used<br />
w<strong>it</strong>h flexible multi-layer pipework make<br />
<strong>it</strong> possible <strong>to</strong> sub-divide the system in<strong>to</strong><br />
smaller, self-contained sub systems<br />
each served by a single distribution<br />
Module w<strong>it</strong>h <strong>it</strong>s own integral DPCV. The<br />
distance from DPCV <strong>to</strong> control valve is<br />
reduced <strong>to</strong> the minimum and accurate<br />
modulating control of the pumping<br />
system is maximised.<br />
The right 2-port valves can be selected.<br />
Modules also reduce the need for<br />
add<strong>it</strong>ional sub-branch rigid pipework,<br />
which might otherwise be required.<br />
The Commissioning Module technique<br />
enables one compact DPCV <strong>to</strong> be<br />
shared by up <strong>to</strong> six terminal un<strong>it</strong>s w<strong>it</strong>h a<br />
maximum loading of 11.6kW heating<br />
and 6.3kW cooling per terminal – a<br />
highly cost efficient ratio.<br />
Moreover, because the DPCV’s are<br />
located close <strong>to</strong> the terminals, the<br />
pressures they control are relatively low –<br />
typically 0.2 – 0.5 bar. Crucial good valve<br />
author<strong>it</strong>y can be achieved every time.<br />
Minimum flow<br />
However, <strong>to</strong> protect the pump(s) a<br />
minimum flow equivalent <strong>to</strong> 10% of the<br />
system maximum must be maintained<br />
at all times.<br />
This can be achieved by utilising a<br />
reverse acting DPCV, which operates on<br />
the main flow lines on each floor. This<br />
senses rising pressure and will throttle<br />
flow down <strong>to</strong> 10-15% as the system<br />
closes down. Such DPCV's are expensive,<br />
however, and offer poor local control.<br />
An alternative is <strong>to</strong> configure the system<br />
w<strong>it</strong>h one fan coil un<strong>it</strong> in the mini system<br />
served by the <strong>SAV</strong> FloCon Module f<strong>it</strong>ted<br />
w<strong>it</strong>h a 3-port valve so that the system<br />
can never <strong>to</strong>tally shut down.<br />
Now there’s a third alternative. <strong>SAV</strong><br />
Modules is offering FloCon un<strong>it</strong>s w<strong>it</strong>h<br />
an in-built 10% permanent bypass. This<br />
solution is simple, but ensures that the<br />
system is protected at all times - w<strong>it</strong>hout<br />
special design consideration.<br />
Pre-insulated Pipe Protection For <strong>SAV</strong><br />
Connections In The Heart Of The C<strong>it</strong>y<br />
S<br />
AV FloCon Modules continue <strong>to</strong><br />
play their part at the heart of UK<br />
commerce.<br />
Located just northeast of St Pauls, 20<br />
Gresham Street is a new build<br />
development by Hermes Offices<br />
offering 240,00 ft 2 of prime office space<br />
in the oldest part of London.<br />
<strong>SAV</strong> Modules has supplied 200 FloCon<br />
Commissioning Modules <strong>to</strong> Skanska<br />
Rashleigh Weatherfoil for integration<br />
in<strong>to</strong> the air cond<strong>it</strong>ioning system serving<br />
the eight-s<strong>to</strong>rey building.<br />
The un<strong>it</strong>s were specified by Hilson<br />
Moran - London Office.<br />
The project team already had experience<br />
of the speed which <strong>SAV</strong>'s Modular<br />
solutions could bring <strong>to</strong> the installation<br />
and commissioning of v<strong>it</strong>al services.<br />
They'd previously used <strong>SAV</strong> FloCon<br />
Modules at Adelaide House at the north<br />
end of London Bridge. COPY AA<br />
This time <strong>it</strong> was decided <strong>to</strong> aim for<br />
further savings in time and installation<br />
cost by pre-insulating the <strong>SAV</strong> Alupex<br />
pipework w<strong>it</strong>h Armaflex Tuffcoat. This<br />
flexible n<strong>it</strong>rile rubber insulation<br />
material features an outer polymeric<br />
coating. It protects pipework against<br />
mechanical impact and is resistant <strong>to</strong><br />
attack by birds and rodents. A built-in<br />
vapour barrier prevents condensation<br />
and that outer coating means that no<br />
painting is required.<br />
H e r e ’ s H o w T h e F l o C o n C o m m i s s i o n i n g M o d u l e W o r k s . . .<br />
Concept<br />
In trad<strong>it</strong>ional systems, using copper pipe, the valves<br />
must be close <strong>to</strong> the fan coils <strong>to</strong> allow full flushing of<br />
the pipe work. Once you employ flexible, multi-layer, plastic coated metal<br />
pipe where no flushing is needed, all valves can be centralized. This allows<br />
off-s<strong>it</strong>e assembly, swift commissioning and effortless maintenance.<br />
Features<br />
Flow<br />
Manifold<br />
Flushing by-pass<br />
and air vent<br />
Return<br />
Manifold<br />
TRADITIONAL DESIGN - FLUSHING BYPASS LOCAL TO FAN COIL<br />
Simple multi-layer pipe installation<br />
FLUSHING<br />
PATH<br />
BSRIA FLUSHING<br />
& CLEANING<br />
GUIDE AG1/2001<br />
Large bodied<br />
strainer<br />
DPCV<br />
FULL OFF-SITE ASSEMBLY AND TESTING UNDER<br />
STRICT QUALITY CONTROL<br />
COMPACT BOX IS VAPOUR SEALED<br />
TO PREVENT CONDENSATION<br />
4 Fan Coils = 8 branch tees (24 joints) - Copper pipe in 3 meter lengths<br />
FloCon MODULE DESIGN - MANIFOLD IS COMMON FLUSHING BYPASS<br />
Flexible<br />
Multi-layer Pipe<br />
2-6 Fan Coils<br />
per module<br />
Recommend 15m<br />
<strong>to</strong> furthest terminal<br />
Flexible<br />
Multi-layer Pipe<br />
Available in a range of <strong>size</strong>s all the<br />
way up <strong>to</strong> 1 4 in, <strong>SAV</strong>’s special strainer<br />
will provide full flow until a minimum<br />
50% of <strong>it</strong>s large 100 cm 3 capac<strong>it</strong>y is<br />
full. It’s easy <strong>to</strong> service <strong>to</strong>o.<br />
THE BIG 3<br />
Large Bodied Strainer - Centralized Flushing, Back Flushing, Venting & Balancing, Insulated and Vapour Sealed Box<br />
FLUSHING THROUGH MAIN BRANCH<br />
TERMINAL BRANCH AIR PURGE BACK FLUSHING THROUGH TERMINAL BRANCH<br />
Max module inlet<br />
<strong>size</strong> - 32mm<br />
Valve<br />
Module<br />
Max pipe feed <strong>to</strong> terminal<br />
un<strong>it</strong>s - 20mm<br />
FLUSHING<br />
PATH<br />
4 Fan Coils need only 2 branch tees (just 6 joints in all)<br />
“Manifold & multilayer pipe more cost efficient <strong>to</strong> install” (See BSRIA costing sheets)<br />
Joint-less continuous pipe runs from<br />
FloCon module <strong>to</strong> fan coil<br />
As BSRIA Guide AG1/2001:-<br />
- Remove CM strainer baskets<br />
- flush/chemical clean steel <strong>pipes</strong><br />
- final fill w<strong>it</strong>h treated water<br />
- replace CM strainer baskets<br />
- vent all CMs.
Draper’s Gardens Sets Modular Record<br />
D<br />
raper's Gardens in London EC2 has<br />
made <strong>it</strong>s way in<strong>to</strong> <strong>SAV</strong>'s record<br />
books.<br />
The 14-s<strong>to</strong>rey office and retail<br />
development now under construction<br />
here for the Royal Bank of Scotland<br />
represents the largest order yet placed<br />
for <strong>SAV</strong> FloCon Commissioning<br />
Modules.<br />
And - for the record - the project is also<br />
one of the first <strong>to</strong> employ Modules<br />
featuring the new integral bypass (see<br />
page 2).<br />
Nearly 300 Modules will be supplied,<br />
<strong>to</strong>gether w<strong>it</strong>h Alupex multi-layer flexible<br />
pipe work, <strong>to</strong> distribute heating and<br />
cooling services <strong>to</strong> over 1000 fan coil<br />
un<strong>it</strong>s in the 37,500m 2 development.<br />
FloCon Commissioning Modules used<br />
w<strong>it</strong>h flexible multi-layer pipework make<br />
<strong>it</strong> possible <strong>to</strong> sub-divide the system in<strong>to</strong><br />
ime is money. Services for new<br />
build projects are carefully preplanned<br />
for fast installation and speedy<br />
commissioning, so that occupants can<br />
be moved in<strong>to</strong> the building as soon as<br />
possible.<br />
If the building is in a prime location the<br />
need for a fast track solution is usually<br />
even more urgent.<br />
But what if the building is not only in<br />
one of London's most prestigious s<strong>it</strong>es,<br />
but is also already occupied - w<strong>it</strong>h<br />
tenant having <strong>to</strong> move out while the<br />
environmental control system is<br />
upgraded?<br />
That's exactly the scenario that led <strong>to</strong><br />
specification of <strong>SAV</strong> FloCon Modules<br />
for 1-7 Savoy Court. This Grade ll listed<br />
building dates from 1903 and stands<br />
immediately adjacent <strong>to</strong> the Savoy<br />
Hotel.<br />
Savoy Court, off the Strand, is, by the<br />
way, the only street in the whole of<br />
Br<strong>it</strong>ain where all traffic drives on the<br />
right!<br />
The 57,000ft 2 office space over eight<br />
floors has been <strong>to</strong>tally refurbished for<br />
the existing tenant, who relocated <strong>to</strong><br />
temporary accommodation while the<br />
work was carried out. Bluu Solutions<br />
designed the new office environment<br />
and managed <strong>it</strong>s construction.<br />
The air cond<strong>it</strong>ioning system installed<br />
by Kentex comprises <strong>SAV</strong> FloCon<br />
Modules distributing hot water and<br />
chilled water <strong>to</strong> a 4-pipe fan coil<br />
system. For maximum speed new fan<br />
coils were installed in the locations of<br />
the old un<strong>it</strong>s they replaced. Pipework<br />
and distribution systems, however,<br />
have been completely revised <strong>to</strong> meet<br />
modern requirements for easy<br />
maintenance and more efficient<br />
control.<br />
The <strong>SAV</strong> un<strong>it</strong>s are located in the ceiling<br />
voids w<strong>it</strong>h runs of Alupex multi-layer<br />
pipework taking the most convenient<br />
paths <strong>to</strong> the fan coils mounted in the<br />
ceilings, or behind wood paneling on<br />
the walls.<br />
For further information contact:<br />
<strong>SAV</strong> MODULES, SCANDIA HOUSE, 131 ARMFIELD CLOSE,<br />
WEST MOLESEY, SURREY KT8 2JR<br />
TEL: +44 (0)20 8941 4153 FAX: +44 (0)20 8783 1132<br />
WEB: www.savmodules.com E-MAIL: info@savmodules.com<br />
smaller, self-contained sub systems<br />
each served by a single distribution<br />
Module w<strong>it</strong>h <strong>it</strong>s own integral Differential<br />
Pressure Control Valve (DPCV). The<br />
distance from DPCV <strong>to</strong> control valve is<br />
reduced <strong>to</strong> the minimum and accurate<br />
modulating control of the pumping<br />
system is maximised.<br />
The right 2-port valves can be selected.<br />
Modules also reduce the need for<br />
add<strong>it</strong>ional sub-branch rigid pipework.<br />
Pressfar Connections<br />
Mechanical and electrical contrac<strong>to</strong>rs<br />
N.G.Bailey opted for Pressfar pressf<strong>it</strong><br />
connections <strong>to</strong> the <strong>SAV</strong> Modules at<br />
Draper's Gardens. This option is now<br />
available <strong>to</strong> <strong>SAV</strong> cus<strong>to</strong>mers seeking <strong>to</strong><br />
combine high integr<strong>it</strong>y connections<br />
w<strong>it</strong>h ease of use under s<strong>it</strong>e cond<strong>it</strong>ions.<br />
Designed for use w<strong>it</strong>h all types of multilayer<br />
<strong>pipes</strong> Pressfar f<strong>it</strong>tings are<br />
THE RIGHT CHOICE FOR <strong>SAV</strong>OY COURT<br />
T<br />
available in a range of <strong>size</strong>s from 1 /2 inch<br />
all the way up <strong>to</strong> 1 1 /2 inch. F<strong>it</strong>tings are<br />
provided w<strong>it</strong>h a double seal ring w<strong>it</strong>h a<br />
rectangular section that perm<strong>it</strong>s the use<br />
of three different types of jaws.<br />
The steel bush, which be<strong>comes</strong><br />
deformed during pressing, is reversible<br />
- making <strong>it</strong> possible <strong>to</strong> check the proper<br />
pipe insertion on the f<strong>it</strong>ting.<br />
A further safeguard is provided by the<br />
plastic ring, which is used <strong>to</strong> correctly<br />
set the bush and hold <strong>it</strong> still during<br />
pressing. The ring is also colour-coded<br />
<strong>to</strong> ensure easy <strong>size</strong> identification.<br />
Arch<strong>it</strong>ects and building services design<br />
consultants for the Draper’s Gardens<br />
project are Foggo Associates of London.<br />
CREATING THE RIGHT<br />
ENVIRONMENT AT<br />
CHISWICK PARK<br />
C<br />
hiswick Park is one of the UK's<br />
largest commercial developments.<br />
The 30-acre landscaped business park<br />
<strong>to</strong> the west of London offers every<br />
facil<strong>it</strong>y for work and play from aircond<strong>it</strong>ioned<br />
offices <strong>to</strong> retail un<strong>it</strong>s and<br />
restaurants.<br />
Building 9 is the first on the s<strong>it</strong>e <strong>to</strong> feature<br />
a pre-installed fan coil system - boosting<br />
<strong>it</strong>s appeal <strong>to</strong> potential tenants. Sixty <strong>SAV</strong><br />
FloCon Commissioning Modules located<br />
in the floor voids serve the system - each<br />
supplying heating and cooling media <strong>to</strong><br />
a group of 4-pipe fan coils at the<br />
perimeter of each of the five floors.<br />
<strong>SAV</strong>’s Commissioning Module<br />
technique enables one compact DPCV<br />
<strong>to</strong> be shared by up <strong>to</strong> six terminal un<strong>it</strong>s<br />
w<strong>it</strong>h a maximum loading of 11.6kW<br />
heating and 6.3kW cooling per<br />
terminal – a highly cost efficient ratio.<br />
If the pressure available from the<br />
pump should increase, then the DPCV<br />
will close in order <strong>to</strong> take out the<br />
excess pressure. If the pressure<br />
available should reduce, then the<br />
DPCV will open so that more pressure<br />
be<strong>comes</strong> available.<br />
Moreover, because the DPCV’s are<br />
located close <strong>to</strong> the terminals, the<br />
pressures they control are relatively<br />
low – typically 0.2 – 0.5 bar. Crucial<br />
good valve author<strong>it</strong>y can be achieved<br />
every time.