<strong>Belimo</strong> VRP<br />

Pressure Independent Control Characteristic<br />

Pressure differential<br />

1000<br />

Pa<br />

800<br />

600<br />

400<br />

200<br />

V min<br />

� V<br />

Volume flow<br />

‡ max set value =<br />

‡ min set value =<br />

‡ max M<br />

‡ min M<br />

·<br />

Vmax set value =<br />

=<br />

‡ max S<br />

‡ max M<br />

‡ max<br />

‡ nom<br />

‡ min<br />

‡ max<br />

‡ max S<br />

‡ min S<br />

.<br />

. 100 %<br />

. 100 %<br />

‡ nom M<br />

‡ nom S<br />

V max<br />

� V<br />

20 40 60 80 100<br />

% of ‡ nom<br />

. 100 %<br />

3<br />

Volume Flow Control<br />

The volume flow controller works independently of<br />

the duct pressure, i.e. pressure fluctuations cause no<br />

changes to volume flow<br />

To prevent the volume flow control becoming unstable, a<br />

dead zone is allowed within which the damper does not<br />

move. This dead zone and the accuracy of site measurements<br />

lead to volume flow deviation �‡ shown opposite.<br />

If the conditions given in the sales brochure (static minimum<br />

pressure differential, inlet flow conditions etc.) are<br />

not observed, greater deviations must be expected.<br />

V · max Setting<br />

The ‡ max value corresponds to the volume flow which is<br />

set with a 10 VDC control signal or ‡ max override control.<br />

The setting range is from 30 to 100 %. The percentage<br />

figures relate to ‡ nom.<br />

V · min Setting<br />

The ‡ min value corresponds to the volume flow which is<br />

set with a 2 VDC control signal or ‡ min override control.<br />

‡ min may be set between 0 and 80 % of ‡ max. The percentage<br />

figures relate to the ‡ max volume flow setting. If<br />

‡ min is set to 0 %, a tight shut off of the damper is not<br />

guaranteed. The controller closes the damper until the<br />

actual value signal is 2 VDC corresponding to 0 l/s.<br />

Measurement tolerances mean that a leakage air flow is<br />

present. Override control should be used for tight shut<br />

off.<br />

Slave Control<br />

The VRP only provides for ratio control, i.e. the supply<br />

and extract air must be in the same ratio under all<br />

operating conditions.<br />

The volume flow ratio is set using the ‡ max adjustment<br />

knob on the slave controller, according to the formula<br />

shown opposite. Where the volume flows are the same<br />

and the units of equal size, the setting will be 100 %.<br />

The setting range is from 30 to 100 %. If ‡ max set value<br />

>100 %, the master and slave functions must be reversed.<br />

As a rule, the ‡ min adjustment knob on the slave<br />

is set to 0 %.