<strong>Belimo</strong> VRP<br />
Pressure Independent Control Characteristic<br />
Pressure differential<br />
1000<br />
Pa<br />
800<br />
600<br />
400<br />
200<br />
V min<br />
� V<br />
Volume flow<br />
‡ max set value =<br />
‡ min set value =<br />
‡ max M<br />
‡ min M<br />
·<br />
Vmax set value =<br />
=<br />
‡ max S<br />
‡ max M<br />
‡ max<br />
‡ nom<br />
‡ min<br />
‡ max<br />
‡ max S<br />
‡ min S<br />
.<br />
. 100 %<br />
. 100 %<br />
‡ nom M<br />
‡ nom S<br />
V max<br />
� V<br />
20 40 60 80 100<br />
% of ‡ nom<br />
. 100 %<br />
3<br />
Volume Flow Control<br />
The volume flow controller works independently of<br />
the duct pressure, i.e. pressure fluctuations cause no<br />
changes to volume flow<br />
To prevent the volume flow control becoming unstable, a<br />
dead zone is allowed within which the damper does not<br />
move. This dead zone and the accuracy of site measurements<br />
lead to volume flow deviation �‡ shown opposite.<br />
If the conditions given in the sales brochure (static minimum<br />
pressure differential, inlet flow conditions etc.) are<br />
not observed, greater deviations must be expected.<br />
V · max Setting<br />
The ‡ max value corresponds to the volume flow which is<br />
set with a 10 VDC control signal or ‡ max override control.<br />
The setting range is from 30 to 100 %. The percentage<br />
figures relate to ‡ nom.<br />
V · min Setting<br />
The ‡ min value corresponds to the volume flow which is<br />
set with a 2 VDC control signal or ‡ min override control.<br />
‡ min may be set between 0 and 80 % of ‡ max. The percentage<br />
figures relate to the ‡ max volume flow setting. If<br />
‡ min is set to 0 %, a tight shut off of the damper is not<br />
guaranteed. The controller closes the damper until the<br />
actual value signal is 2 VDC corresponding to 0 l/s.<br />
Measurement tolerances mean that a leakage air flow is<br />
present. Override control should be used for tight shut<br />
off.<br />
Slave Control<br />
The VRP only provides for ratio control, i.e. the supply<br />
and extract air must be in the same ratio under all<br />
operating conditions.<br />
The volume flow ratio is set using the ‡ max adjustment<br />
knob on the slave controller, according to the formula<br />
shown opposite. Where the volume flows are the same<br />
and the units of equal size, the setting will be 100 %.<br />
The setting range is from 30 to 100 %. If ‡ max set value<br />
>100 %, the master and slave functions must be reversed.<br />
As a rule, the ‡ min adjustment knob on the slave<br />
is set to 0 %.