Reference Calculations<br />

Heating Calculations:<br />

HE<br />

LWT = EWT -<br />

gpm x 500<br />

Cooling Calculations:<br />

HR<br />

LWT = EWT +<br />

gpm x 500<br />

HC<br />

LAT = EAT +<br />

cfm x 1.08<br />

TH = HC + HW<br />

LAT (DB) = EAT (DB) -<br />

LC = TC - SC<br />

SC<br />

S/T =<br />

TC<br />

SC<br />

cfm x 1.08<br />

Legend<br />

Abbreviations and Definitions<br />

cfm = airflow, cubic feet/minute<br />

EWT = entering water temperature, Fahrenheit<br />

gpm = water flow in gallons/minute<br />

WPD = water pressure drop, psi and feet of water<br />

EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb)<br />

HC = air heating capacity, MBtu/h<br />

TC = total cooling capacity, MBtu/h<br />

SC = sensible cooling capacity, MBtu/h<br />

kW = total power unit input, kilowatts<br />

HR = total heat of rejection, MBtu/h<br />

HE = total heat of extraction, MBtu/h<br />

HWC = hot water generator capacity, MBtu/h<br />

EER = Energy Efficient Ratio<br />

= Btu output/Watt input<br />

COP = Coefficient of Performance<br />

= Btu output/Btu input<br />

LWT = leaving water temperature, °F<br />

LAT = leaving air temperature, °F<br />

TH = total heating capacity, MBtu/h<br />

LC = latent cooling capacity, MBtu/h<br />

S/T = sensible to total cooling ratio<br />

25