5 SERIES <strong>500R11</strong> INSTALLATION MANUAL<br />
Reference Calculations<br />
Heating Calculations:<br />
HE<br />
LWT = EWT -<br />
gpm x 500<br />
Cooling Calculations:<br />
HR<br />
LWT = EWT +<br />
gpm x 500<br />
HC<br />
LAT = EAT +<br />
cfm x 1.08<br />
TH = HC + HW<br />
LAT (DB) = EAT (DB) -<br />
LC = TC - SC<br />
SC<br />
S/T =<br />
TC<br />
SC<br />
cfm x 1.08<br />
Legend<br />
Abbreviations and Definitions<br />
cfm = airflow, cubic feet/minute<br />
EWT = entering water temperature, Fahrenheit<br />
gpm = water flow in gallons/minute<br />
WPD = water pressure drop, psi and feet of water<br />
EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb)<br />
HC = air heating capacity, MBtu/h<br />
TC = total cooling capacity, MBtu/h<br />
SC = sensible cooling capacity, MBtu/h<br />
kW = total power unit input, kilowatts<br />
HR = total heat of rejection, MBtu/h<br />
HE = total heat of extraction, MBtu/h<br />
HWC = hot water generator capacity, MBtu/h<br />
EER = Energy Efficient Ratio<br />
= Btu output/Watt input<br />
COP = Coefficient of Performance<br />
= Btu output/Btu input<br />
LWT = leaving water temperature, °F<br />
LAT = leaving air temperature, °F<br />
TH = total heating capacity, MBtu/h<br />
LC = latent cooling capacity, MBtu/h<br />
S/T = sensible to total cooling ratio<br />