26.06.2015 Views

Individual Thermal Comfort Control with Desk-Mounted and Floor ...

Individual Thermal Comfort Control with Desk-Mounted and Floor ...

Individual Thermal Comfort Control with Desk-Mounted and Floor ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Center for Environmental Design Research<br />

Center for the Built Environment<br />

(University of California, Berkeley)<br />

Year 1999<br />

Paper Tsuzuki1999 IndivTherm<strong>Comfort</strong><br />

<strong>Individual</strong> <strong>Thermal</strong> <strong>Comfort</strong> <strong>Control</strong><br />

<strong>with</strong> <strong>Desk</strong>-<strong>Mounted</strong> <strong>and</strong> <strong>Floor</strong>-<strong>Mounted</strong><br />

Task/Ambient Conditioning (TAC)<br />

Systems<br />

K. Tsuzuki ∗ Edward Arens †<br />

Fred Bauman ‡<br />

D. Wyon ∗∗<br />

∗ National Institute of Bioscience <strong>and</strong> Human-Technology<br />

† University of California, Berkeley<br />

‡ University of California, Berkeley<br />

∗∗ Johnson <strong>Control</strong>s Inc.<br />

This paper is posted at the eScholarship Repository, University of California.<br />

http://repositories.cdlib.org/cedr/cbe/ieq/Tsuzuki1999 IndivTherm<strong>Comfort</strong><br />

Copyright c○1999 by the authors.


Proceedings: Indoor Air 99, August 8-13, Edinburgh, 7pp.<br />

INDIVIDUAL THERMAL COMFORT CONTROL WITH<br />

DESK-MOUNTED AND FLOOR-MOUNTED<br />

TASK/AMBIENT CONDITIONING (TAC) SYSTEMS<br />

K Tsuzuki 1 , E A Arens 2 , F S Bauman 2 <strong>and</strong> D P Wyon 3<br />

1 National Institute of Bioscience <strong>and</strong> Human-Technology, Higashi, Tsukuba, Japan<br />

2 Center for Environmental Design Research, University of California, Berkeley, CA, USA<br />

3 Johnson <strong>Control</strong>s Inc., Milwaukee, WI, USA<br />

ABSTRACT<br />

Three very different task/ambient conditioning (TAC) systems were investigated in a climate<br />

chamber. Two desk-mounted TACs, the "Personal Environmental Module" (PEM), intended<br />

for US offices, <strong>and</strong> the "Clima<strong>Desk</strong>" (CDESK), intended for European offices, were<br />

compared experimentally <strong>with</strong> a floor-mounted unit, the "Task Air Module" (TAM). All<br />

three provide some individual control of cooling, while PEM <strong>and</strong> CDESK also provide<br />

individual control of heating. They were installed <strong>with</strong> floor-ducted supply air (19-25°C) in<br />

st<strong>and</strong>ard office cubicles in a climate chamber, <strong>and</strong> their effect on the heat loss from a 16-<br />

section heated thermal mannequin was measured at various room temperatures (19-25°C).<br />

The individual control provided by each unit, in terms of the change in room air temperature<br />

that would have affected whole-body heat loss equivalently, was PEM: 9K, CDESK: 3K,<br />

TAM: 5K. The "thermal asymmetry" caused by each unit is given as the rate of heat loss<br />

from each body section.<br />

INTRODUCTION<br />

<strong>Individual</strong> control of the thermal microclimate at each workplace has a number of important<br />

advantages, in comparison <strong>with</strong> conventional heating <strong>and</strong> cooling, which has to assume that<br />

all occupants have the same thermal requirements <strong>and</strong> usually leads to >20% dissatisfied.<br />

Even though individual neutral temperatures differ between occupants <strong>and</strong> occasions <strong>and</strong> are<br />

strongly affected by activity, clothing <strong>and</strong> fatigue, <strong>with</strong> sufficient individual control of the<br />

thermal microclimate it is theoretically possible to achieve the ideal, in which all building<br />

occupants are 100% comfortable all the time. The payback in terms of reduced call-out<br />

frequency alone has been shown to be very large [1]. Substantial additional payback will be<br />

achieved in the form of increased occupant satisfaction (thermal comfort), reduced frequency<br />

of SBS symptoms, <strong>and</strong> increased productivity [2]. With the inter-individual variability<br />

observed in a study of 200 Swedish office workers wearing their own clothes (SD=1.17K),<br />

individual control equivalent to changing room temperature ±2K would satisfy >90%, ±2.3K<br />

would satisfy >95%, <strong>and</strong> ±3K would satisfy 99% [3]. The present experiment was carried out<br />

to determine whether any existing task/ambient conditioning systems may be said to provide a<br />

degree of individual microclimate control approaching or exceeding these values for an office<br />

worker seated at a desk, <strong>and</strong> under what conditions of supply air flow, supply air temperature<br />

<strong>and</strong> room temperature.


Proceedings: Indoor Air 99, August 8-13, Edinburgh, 7pp.<br />

METHODS<br />

Four 2.3 x 1.9 m office cubicles <strong>with</strong> 1.7 m high partitions, <strong>with</strong> open doorways, were<br />

installed in a controlled environment chamber (CEC) in a university laboratory. The CEC has<br />

a 5.5 x 5.5 m floor area <strong>and</strong> a 2.5 m ceiling height [4]. Room temperature is controlled by<br />

means of conventional supply <strong>and</strong> return air vents in the ceiling. St<strong>and</strong>ard office equipment,<br />

including a desk <strong>with</strong> a heat source simulating a PC, was installed in 3 of the cubicles, <strong>and</strong> a<br />

different TAC was installed in each of these. Each TAC was provided <strong>with</strong> the requisite<br />

amount of conditioned supply air from ducts beneath the raised access floor.<br />

PEM: The Personal Environmental Module mixes room air from beneath the desk <strong>with</strong> a<br />

nominally 6-71 L/s supply air flow so as to achieve the required supply air temperature. The<br />

fan speed is variable <strong>and</strong> the supply air emerges from two vents 0.3 m above the desk surface,<br />

at the back corners. These vents can be rotated 360° about a vertical axis <strong>and</strong> have vanes<br />

which can direct the air flow ±30° from the horizontal. Supply air flows of 9.5-71 L/s were<br />

used in the present study. A 200 W electrically heated panel st<strong>and</strong>s vertically on the floor in a<br />

position determined by the occupant. An infra-red movement sensor on the control panel,<br />

which st<strong>and</strong>s on the desk surface, normally keeps the unit switched on while the workplace is<br />

occupied.<br />

CDESK: The Clima<strong>Desk</strong> nominally supplies 0-7 L/s of supply air to two laminar-flow vents<br />

under the desk surface, 0.6 m behind the front edge. The fan speed is variable <strong>and</strong> these vents<br />

can be rotated ±30° horizontally to either impinge on the occupant or pass close by. 0-100%<br />

of the air flow can be directed to a third laminar-flow vent at the front edge which is directed<br />

upwards 7° backwards from the vertical, i.e. slightly away from the occupant, to minimize the<br />

resultant cooling effect. Supply air flows of 3.5-7.1 L/s were used in the present study. A<br />

200 W electrically heated panel, 0.8 x 0.6 m <strong>and</strong> capable of maintaining any required surface<br />

temperature up to 50°C, is fixed to the underside of the desk surface, i.e. horizontal <strong>and</strong> just<br />

above the occupant's thighs. An infra-red movement sensor on the panel underneath the desk<br />

normally keeps the unit switched on while the workplace is occupied.<br />

TAM: Each Task Air Module, measuring 0.6 m by 0.6 m, can be located at any position in a<br />

raised access floor system simply by exchanging it <strong>with</strong> a solid floor panel of equal size. An<br />

adjustable-speed fan/motor assembly draws air from the sub-floor plenum <strong>and</strong> supplies it to<br />

the room through four 127-mm diameter discharge grills. Fixed individual vanes in the grills<br />

are inclined at 40° from vertical. A rotary speed control knob is recessed into one grill <strong>and</strong><br />

each grill can be rotated 360°, allowing office workers to control both the direction <strong>and</strong><br />

quantity of air supplied from the module. When the fan is switched on, the TAM can deliver<br />

43-85 L/s from a zero or very low pressure floor plenum. Supply air flows of 23.6-85 L/s<br />

were used in the present study.<br />

<strong>Thermal</strong> mannequin: A 16-section heated thermal mannequin was used to simulate a person<br />

seated at each of the desks <strong>with</strong> a TAC unit in turn. The mannequin was dressed in a tightfitting<br />

lightweight set of clothing covering all but head <strong>and</strong> h<strong>and</strong>s, <strong>with</strong> a total (clothing plus<br />

air layer) whole-body insulation value of 0.181 m 2 K/W (1.17 Clo). It could be soaked <strong>with</strong><br />

distilled water to determine the maximum rate of evaporative cooling when sweating. The<br />

mannequin simulates a female occupant <strong>with</strong> hair length just below the ears. It maintains a<br />

constant skin temperature distribution characteristic of an occupant in thermal neutrality at all<br />

times <strong>and</strong> the electrical power per unit surface area (W/m 2 ) that must be supplied to each<br />

section to maintain the set skin temperature at equilibrium is an accurate <strong>and</strong> reproducible


Proceedings: Indoor Air 99, August 8-13, Edinburgh, 7pp.<br />

estimate of an occupant's rate of heat loss from that body section in the same microclimate.<br />

An occupant's whole-body rate of heat loss is estimated as the area-weighted sum of the<br />

sectional rates of heat loss. The mannequin was always placed centrally, 0.1 m from the front<br />

edge of the desk, seated in an upright posture on a typical typist's chair, i.e. a minimally<br />

upholstered chair <strong>with</strong> a small lumbar support, whose effective insulation was equivalent to<br />

an additional 0.023 m 2 K/W (0.15 Clo), <strong>with</strong> arms slightly bent <strong>and</strong> h<strong>and</strong>s <strong>and</strong> forearms resting<br />

on the desk surface.<br />

Experimental conditions: Desired room air <strong>and</strong> supply air temperatures were maintained<br />

constant by the CEC control system. A number of combinations of room air temperature <strong>and</strong><br />

supply air temperature in the range of 19-25°C were studied. For each test condition,<br />

preliminary experiments were carried out to optimize airflow direction, fan speed, <strong>and</strong> heater<br />

setting to achieve maximum cooling <strong>and</strong> heating, respectively. Supply air flow was measured<br />

using a series of long, small-diameter, straight pipes <strong>with</strong> pitot tubes <strong>and</strong> venturi flow meters<br />

mounted beneath the floor. In some of the test conditions, the partitions between the cubicles<br />

were removed. Detailed results are given in [5].<br />

RESULTS<br />

Sectional <strong>and</strong> whole-body rates of heat loss from the mannequin were measured under a<br />

variety of conditions [5]. They were converted to EHT-values [6] by means of reference<br />

exposures <strong>with</strong> the same clothing <strong>and</strong> posture (Equivalent Homogeneous Temperature or EHT<br />

is defined as the temperature of a uniform space, <strong>with</strong> all surface temperatures equal to air<br />

temperature <strong>and</strong> no air movement other than the self-convection of the mannequin, in which<br />

the rate of heat loss from a given body section would be the same as was actually measured<br />

under the experimental conditions). This index reduces any combination of environmental<br />

variables into a single temperature that can be readily understood, as it is closely related to<br />

typical indoor experience. Figs. 1-3 present the sectional rates of heat loss in the form of<br />

profile diagrams of EHT (the change in EHT from reference conditions [same room<br />

temperature <strong>with</strong> no TAC airflow] caused by the device in use) for the settings found to yield<br />

the highest degree of individual control of whole-body EHT, for PEM, CDESK <strong>and</strong> TAM,<br />

respectively.<br />

DISCUSSION<br />

All three devices provide individual control of cooling. The amount of cooling was<br />

dependent primarily on the air supply volume <strong>and</strong> direction, <strong>and</strong> to a lesser degree on the<br />

supply air temperature, the proximity of the supply device to the mannequin, <strong>and</strong> the room air<br />

temperature. The maximum amount of individual control of cooling provided by each unit, in<br />

terms of the change in room air temperature that would have affected whole-body heat loss<br />

equivalently <strong>with</strong>out local air movement, was PEM: 7K, TAM: 5K, CDESK: 1K. These<br />

values were achieved <strong>with</strong> the supply air directed toward the mannequin in such a way as to<br />

maximize the convective heat loss from the mannequin. PEM provided the highest cooling<br />

rate, as it delivers a high volume of air directly onto the chest, head, <strong>and</strong> arms of the<br />

mannequin. Although TAM has a higher maximum supply volume than PEM, its air supply<br />

comes from a location further away, at floor level <strong>and</strong> to the left side of the mannequin,<br />

reducing the cooling effect on the body that can be achieved. CDESK naturally provided the<br />

smallest cooling impact, as the maximum supply volume is only 10% of that of PEM or<br />

TAM.


Proceedings: Indoor Air 99, August 8-13, Edinburgh, 7pp.<br />

Change in EHT (K)<br />

-20.0 -15.0 -10.0 -5.0 0.0 5.0 10.0<br />

HEAD<br />

LEFT UPPER ARM<br />

RIGHT UPPER ARM<br />

LEFT FOREARM<br />

RIGHT FOREARM<br />

Heating<br />

Troom = 20.5°C<br />

Total EHT = +2.2K<br />

LEFT HAND<br />

RIGHT HAND<br />

CHEST<br />

BACK<br />

Cooling at 71 L/s<br />

PELVIS<br />

Tsupply = 19.5°C<br />

Troom = 25.0°C<br />

LEFT THIGH<br />

Total EHT = -7.1K<br />

RIGHT THIGH<br />

LEFT LOWER LEG<br />

Cooling at 35.4 L/s<br />

RIGHT LOWER LEG<br />

Tsupply = 18.8°C<br />

Troom = 25.2°C<br />

LEFT FOOT<br />

Total EHT = -4.3K<br />

RIGHT FOOT<br />

Figure 1. Mannequin profile diagram for PEM:<br />

Change in EHT from reference conditions<br />

Change in EHT (K)<br />

-20.0 -15.0 -10.0 -5.0 0.0 5.0 10.0<br />

HEAD<br />

LEFT UPPER ARM<br />

RIGHT UPPER ARM<br />

LEFT FOREARM<br />

Heating<br />

Troom = 19.9°C<br />

Total EHT = +1.8K<br />

RIGHT FOREARM<br />

LEFT HAND<br />

RIGHT HAND<br />

CHEST<br />

BACK<br />

PELVIS<br />

LEFT THIGH<br />

RIGHT THIGH<br />

LEFT LOWER LEG<br />

RIGHT LOWER LEG<br />

LEFT FOOT<br />

Cooling at 7.1 L/s<br />

Tsupply = 18.3°C<br />

Troom = 25.1°C<br />

Total EHT = -1.3K<br />

RIGHT FOOT<br />

Figure 2. Mannequin profile diagram for CDESK:<br />

Change in EHT from reference conditions<br />

Change in EHT (K)<br />

-20.0 -15.0 -10.0 -5.0 0.0 5.0 10.0<br />

HEAD<br />

LEFT UPPER ARM<br />

RIGHT UPPER ARM<br />

LEFT FOREARM<br />

Cooling at 85 L/s,<br />

Tsupply = 19.0°C<br />

Troom = 25.9°C<br />

Total EHT = -5.1K<br />

RIGHT FOREARM<br />

LEFT HAND<br />

RIGHT HAND<br />

CHEST<br />

BACK<br />

PELVIS<br />

LEFT THIGH<br />

RIGHT THIGH<br />

LEFT LOWER LEG<br />

RIGHT LOWER LEG<br />

LEFT FOOT<br />

RIGHT FOOT<br />

Figure 3. Mannequin profile diagram for TAM:<br />

Change in EHT from reference conditions


Proceedings: Indoor Air 99, August 8-13, Edinburgh, 7pp.<br />

Since all three TAC units deliver air that impacts only certain parts of the human body, some<br />

amount of thermal asymmetry does occur. The sectional results for the mannequin display the<br />

magnitude of this asymmetry, which is largest for the maximum cooling rates obtained for<br />

PEM. In fact, some of the individual body parts directly exposed to the high velocity supply<br />

air (head, chest, right upper arm, right forearm [Fig. 1]) experience EHTs that are below<br />

16°C, which is taken here as a practical lower limit for long-term exposure (health regulations<br />

in many countries m<strong>and</strong>ate at least 16°C for homes <strong>and</strong> sedentary work, as that temperature<br />

requires for thermal neutrality a clothing insulation of 1.5 clo, i.e., 50% above normal indoor<br />

clothing, which is difficult to exceed <strong>with</strong>out adding blankets or items of outdoor clothing).<br />

The EHT measured under reference (still air) conditions in the nominally 25 °C room was<br />

actually closer to 26 °C, so all values of delta EHT greater than 10K would be below 16 °C.<br />

The next highest cooling rate obtained for PEM at the 50% flow rate of 35.4 L/s did not<br />

produce any individual sectional EHT values below 16°C <strong>and</strong> can therefore be considered as<br />

acceptable for long-term exposure. The maximum whole-body cooling in comparison to<br />

reference conditions for PEM at the 50% flow rate was 4.0-4.5K. The maximum cooling rate<br />

for TAM, although obtained at a higher flow rate of 85 L/s, produced some individual<br />

sectional EHT values that were very close to but not below 16°C. The whole-body cooling<br />

for the TAM at this maximum condition was 5.0-5.5K below reference, suggesting that 5K of<br />

cooling is a good estimate for the maximum cooling rate suitable for long-term exposures.<br />

For short-term cooling, of course, the maximum cooling rate of 7K for PEM can be used.<br />

Both PEM <strong>and</strong> CDESK provide individual control of heating, while TAM does not. Figures 1<br />

<strong>and</strong> 2 show the different effects that the heating panels for PEM <strong>and</strong> CDESK have on the<br />

mannequin. The PEM heater was placed on the floor to the right of the mannequin producing<br />

the largest increases in EHT for the right thigh, lower leg, <strong>and</strong> foot. The CDESK heater was<br />

under the desk <strong>and</strong> had the largest effect on both thighs <strong>and</strong> the pelvic region. Although the<br />

radiant heating panels for PEM <strong>and</strong> CDESK are located in different orientations, they both<br />

provided about 2K of heating, in terms of the change in room air temperature that would have<br />

affected whole-body heat loss equivalently. Therefore, the total range of equivalent wholebody<br />

temperature control (heating plus cooling) provided by each device was PEM: 9K,<br />

TAM: 5K, <strong>and</strong> CDESK: 3K.<br />

At its lowest flow rate, 9.4 L/s, PEM focused still provided a 1-2K whole-body cooling effect,<br />

similar in magnitude to that provided by CDESK at its maximum flow rate, 7.1 L/s. While<br />

these cooling rates may not be high enough to satisfy the needs of a warm occupant wanting<br />

to recover quickly to equilibrium <strong>with</strong> the environment, they may be satisfactory for a<br />

majority of situations in which the occupant requires only minor adjustment of the local<br />

thermal environment. In ventilation effectiveness experiments carried out in parallel [7],<br />

significant improvements in air change effectiveness <strong>and</strong> pollutant removal efficiency were<br />

measured when 100% outside air was provided to PEM or CDESK at these same low flow<br />

rates. Future TAC systems should therefore include the possibility of using quite low air<br />

supply volumes.<br />

PEM <strong>and</strong> TAM were also tested <strong>with</strong> a "defocused" flow direction in which the supply air<br />

was directed away from the mannequin in such a way as to maximize air circulation <strong>with</strong>in<br />

the partitioned workstation. Under these conditions, PEM provided up to 2-3K whole-body<br />

cooling effect, while TAM provided almost no measurable cooling. The stronger influence of<br />

PEM is due to the horizontal flow direction of the desk-mounted nozzles, which is more<br />

easily contained by the partition configuration. In comparison, TAM supplies air at a 40-<br />

degree upward angle, making it more difficult for the partitions to contain the air movement.


Proceedings: Indoor Air 99, August 8-13, Edinburgh, 7pp.<br />

When the partitions were removed, PEM defocused provided approximately 1K of wholebody<br />

cooling, while TAM provided no cooling at all.<br />

The wet mannequin tests determined the rate of evaporative (latent) cooling provided by these<br />

TAC units when the mannequin had a fully wetted surface. The evaporative cooling rate was<br />

very large in comparison to the sensibly cooled (dry) mannequin results. At 0.20 skin<br />

wettedness, the maximum fraction of the skin that can be wet <strong>and</strong> remain acceptable, the<br />

combined evaporative <strong>and</strong> sensible cooling would for most of the tests have more than<br />

doubled the total whole-body cooling rate measured <strong>with</strong> the dry surface.<br />

CONCLUSIONS<br />

TACs are capable of delegating considerable control of heat balance to the individual<br />

occupant. Among the three TACs tested, the change in room temperature that would have<br />

affected whole-body heat loss equivalently (EHT) ranged from 3-9K. Although thermal<br />

control is somewhat reduced at lower flow rates, significant improvements in ventilation<br />

effectiveness are observed when 100% outside air is supplied through the desk-mounted TAC<br />

units, making this operating condition an important feature of future TACs.<br />

ACKNOWLEDGMENTS<br />

This work was funded primarily by Johnson <strong>Control</strong>s, Inc., Milwaukee, WI, <strong>and</strong> partially by<br />

the Center for the Built Environment, University of California, Berkeley, CA. The authors<br />

also wish to acknowledge the technical support of Jorn Toftum, Visiting Resarcher from the<br />

Danish Technical University, Charlie Huizenga, Research Specialist <strong>with</strong> the Center for<br />

Environmental Design Research, <strong>and</strong> Zhang Hui, Tim Stockwell, <strong>and</strong> Alan Smart, all students<br />

in the Department of Architecture at the University of California, Berkeley.<br />

REFERENCES<br />

1. Federspiel, C C. 1998. Statistical analysis of unsolicited thermal sensation complaints in<br />

commercial buildings. ASHRAE Transactions, Vol. 104 (1B), pp 912- 923.<br />

2. Wyon, D P. 1996. <strong>Individual</strong> microclimate control: required range, probable benefits <strong>and</strong><br />

current feasibility. Proceedings of Indoor Air '96, Vol. 1, pp 1067-1072.<br />

3. Wyon, D P. 1996. Indoor environmental effects on productivity. Proceedings of IAQ<br />

’96: Paths to better building environments. W. Kroner, ed. Atlanta: ASHRAE, pp 5-15.<br />

4. Bauman, F, Zhang, H, Arens, E, <strong>and</strong> Benton, C. 1993. Localized comfort control <strong>with</strong> a<br />

desktop task conditioning system: laboratory <strong>and</strong> field measurements. ASHRAE<br />

Transactions, Vol. 99 (2), pp 733-749.<br />

5. Bauman, F, Tsuzuki, K, Zhang, H, et al. 1999. Experimental comparison of three<br />

individual control devices: thermal mannequin tests. Center for Environmental Design<br />

Research, University of California, Berkeley, CA.<br />

6. Wyon, D P. 1989. The use of thermal manikins in environmental ergonomics. Sc<strong>and</strong>. J<br />

Work, Env. Health, 15 (Supplement), pp 84-94.<br />

7. Faulkner, D, Fisk, W J, Sullivan, D P <strong>and</strong> Wyon, D P. 1999. Ventilation efficiencies of<br />

task/ambient conditioning systems <strong>with</strong> desk-mounted air supplies. Proceedings of<br />

Indoor Air '99 (In press).

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!