26.06.2015 Views

INDIVIDUAL CONTROL BY INDIVIDUAL VAV - APACS from Argon Air

INDIVIDUAL CONTROL BY INDIVIDUAL VAV - APACS from Argon Air

INDIVIDUAL CONTROL BY INDIVIDUAL VAV - APACS from Argon Air

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>INDIVIDUAL</strong> <strong>CONTROL</strong> <strong>BY</strong> <strong>INDIVIDUAL</strong> <strong>VAV</strong><br />

Hans F. Levy, P.E., Life member of ASHRAE<br />

President, <strong>Argon</strong> Corporation<br />

www.argonair.com<br />

4968 Tamiami Trail North<br />

Naples, FL 34103<br />

information@argonair.com<br />

239.430.7876<br />

239.430.7877 Fax<br />

INTRODUCTION<br />

Individual control is needed and can be cost<br />

effective. “Thermal Comfort,”Chapter 8 in the<br />

ASHRAE Handbook of Fundamentals, 2001,<br />

indicates vast differences between people’s<br />

needs for thermal comfort, strongly indicating<br />

the need for individual control. Metabolic heat<br />

generation varies in a ratio as high as ten to<br />

one (Table 4, Chapter 8, ASHRAE Handbook<br />

of Fundamentals, 2001.) The system<br />

described below was installed in a bank in 20<br />

work areas. In a two year period there was not<br />

a single complaint. Occupants and<br />

management enjoyed 100% satisfaction.<br />

Fanger et al. (1973, 1985, 1986 and 1989)<br />

demonstrate in many studies that personal<br />

comfort will lead to greater employee<br />

productivity, greater satisfaction and lower<br />

turnover. Note that typical employee costs<br />

today are $3000/sm/yr ($300/sf/yr), versus<br />

$300/sm/yr ($30/sf/yr) for other building costs.<br />

Therefore the results of individual control are<br />

great savings in personnel costs, the greatest<br />

cost of an office building operation.<br />

DISCUSSION<br />

Since maintaining different temperatures in<br />

close quarters is impractical, varying air<br />

velocity (<strong>VAV</strong>) through personal air outlets,<br />

adjustable by occupants, is the best method of<br />

providing personal control. This requires<br />

redesign of office buildings. Accomplishing<br />

delivery of personal air flow to every<br />

workstation is also impractical, except by<br />

means of raised access floor, which is now<br />

widely and increasingly used in office<br />

buildings.<br />

The effectiveness of this approach was tested<br />

and proven at the University of California at<br />

Berkeley by Fred Bauman, et al., and<br />

published as “Lab Test of <strong>APACS</strong>,”24 April<br />

2000. The tests show that by varying the<br />

airflow, occupants can effect a change to<br />

achieve individual thermal comfort.<br />

TEST CONDITIONS<br />

Tests were designed to compare heat removal<br />

by moving air compared to changes in ambient<br />

temperature. The tests covered two room<br />

temperature setpoints (26 and 28°C [79 and<br />

82°F]) and both horizontal and vertical<br />

mounting positions of the <strong>Argon</strong> Personal <strong>Air</strong><br />

Conditioning System (<strong>APACS</strong>). For each room<br />

temperature a reference test was first<br />

performed in which the mannequin was tested<br />

with no air flow <strong>from</strong> the <strong>APACS</strong> unit. Cooling<br />

tests were performed at different air volumes<br />

and temperatures at both the 26°C (79°F) and<br />

28°C (82°F) room temperatures. The majority<br />

of tests were done at the 26°C (79°F) room<br />

temperature with horizontal position of the<br />

<strong>APACS</strong>, for which the supply temperatures<br />

studied were 21°C, 23°C, and 25°C (70°F,<br />

73°F, and 77°F). At 28°C (82°F) room<br />

temperature with horizontal position and 26°C<br />

(79°F) room temperature with vertical position,<br />

only the 21°C (70°F) supply temperature was<br />

studied. Four air supply volumes were tested<br />

to cover the range of supply rates expected<br />

<strong>from</strong> the <strong>APACS</strong> unit. The volumes tested<br />

were 10, 30, 50 and 70 cfm (5, 14, 24, and 33<br />

L/s). All volumes were tested at the 26°C<br />

(79°F) room temperature setpoint with<br />

horizontal position, while only the 30 and 70<br />

cfm (14 and 33 L/s) rates were tested for the<br />

28°C (82°F)/horizontal and 26°C<br />

(79°F)/vertical tests. The <strong>APACS</strong> unit was<br />

tested under focused air flow direction,<br />

meaning the air supply was directed toward<br />

the mannequin in a way that maximized the<br />

overall (whole-body) cooling rate. Tests were<br />

designed to measure worst case conditions.<br />

The study only tested for sensible cooling. As<br />

reported in the test document, prior tests with a<br />

wet mannequin indicate that the cooling effect<br />

would be at least doubled (“Lab Test of<br />

<strong>APACS</strong>,”p. 11). The result is that, if the<br />

occupant can vary airflow, he can increase or<br />

decrease the heat removal over a wide range,<br />

with the same results as changing the


temperature of the air. The study shows that<br />

the cooling effect range is up to 8°C or 14°F. In<br />

other words, with a room temperature of 28°C<br />

(82°F) an occupant can change his<br />

environment <strong>from</strong> the ambient temperature to<br />

20°C (68°F) with full airflow, and he can do this<br />

without affecting his neighbor. This range<br />

offers enough variety to make everyone<br />

comfortable and happy under almost any<br />

circumstance. As the test data clearly show, it<br />

is not necessary to change the ambient<br />

temperature to provide personal comfort. The<br />

tests also show that it is practical to ramp the<br />

temperature up to utilize stored cooling in the<br />

building and to reduce peak demand as well as<br />

required equipment capacity.<br />

Figure 1<br />

<strong>Air</strong> speed required to offset increased<br />

temperature. The air speed increases in the<br />

amount necessary to maintain the same total<br />

heat transfer <strong>from</strong> the skin. This figure applies<br />

to increase in temperature above those<br />

allowed in the summer comfort zone with both<br />

t r and t a increasing equally. The starting point<br />

of the curves at 0.2 m/s (40 fpm) corresponds<br />

to the recommended air speed limit for the<br />

summer comfort zone at 26°C (79°F) and<br />

typical ventilation (i.e., turbulence intensity<br />

between 30% and 60%). Acceptance of the<br />

increased air speed requires occupant control<br />

of the local speed. [ANSI/ASHRAE 55-1992,<br />

p. 9, Fig. 3]<br />

DESIGN<br />

The concept of using air movement for control<br />

instead of temperature change is not new. It<br />

has been used in airplanes and automobiles<br />

for many years. However, the limited space in<br />

vehicles, and the need to move sufficient air to<br />

effect the necessary cooling, results in too high<br />

a velocity, which feels drafty. In general there<br />

is not sufficient space to limit the velocity to an<br />

average of less than 1 m/s (200fpm). This is<br />

approximately two miles per hour and meets<br />

ANSI/ASHRAE 55-1992 (see Fig. 1). In offices<br />

there is usually more than enough space to<br />

move sufficient air while adhering to the above<br />

limits.<br />

In order to limit the air velocity as described<br />

above, to provide air to the occupants below<br />

room temperature, and not to lose the<br />

effectiveness of the moving air, the air must be<br />

discharged very near the person. The ideal<br />

distance is in the vicinity of 30 centimeters<br />

(one foot) or less. This proximity also provides<br />

the individual occupant with immediate<br />

response to changing environmental<br />

conditions or personal comfort preference.<br />

Being close to the occupant also increases<br />

ventilation efficiency. ANSI/ASHRAE Standard<br />

62-1999, “Ventilation for Acceptable Indoor <strong>Air</strong><br />

Quality,”(Second Public Review, August<br />

2001), p. 6, suggests a zone air distribution<br />

effectiveness greater than 1.0 for low velocity<br />

displacement ventilation. This means a<br />

substantial reduction in required outside air<br />

and a very substantial energy saving. This<br />

arrangement permits the use of a simple<br />

manual damper control within easy reach of<br />

the occupant.<br />

Figure 2<br />

Desk air terminal (vertical)<br />

Giving everyone personal control with a<br />

personal air outlet leads to a question: what to<br />

do with common space. A simple solution is to<br />

combine the personal outlet with a room outlet<br />

that keeps direct room air away <strong>from</strong> the<br />

occupant. The introduction of room air needs<br />

to be far enough <strong>from</strong> the occupant so that it<br />

2


does not interfere with the personal control.<br />

The combined airflow is designed to meet the<br />

cooling load of the person, the workstation and<br />

the adjacent area. If properly designed, the<br />

occupant can turn off the personal air supply<br />

without materially affecting total airflow. With<br />

this arrangement total airflow is relatively<br />

constant. Overall room temperature is then<br />

controlled <strong>from</strong> a space thermostat which can<br />

control the capacity of the air handler to meet<br />

the load requirements (see Figs. 2, 3 and 4).<br />

energy consumption stems <strong>from</strong> the higher<br />

operating room temperatures and the reduced<br />

fresh air requirement.<br />

Figure 4<br />

Floor/desk air terminal (horizontal)<br />

Figure 3<br />

Partition air terminal<br />

The room outlet can be a floor grille outside<br />

the workstation, or a separate grille mounted<br />

either in the furniture or in a space partition<br />

pointing to open space. This outlet may also<br />

exhaust through the top of furniture partitions<br />

(as was done at the bank installation<br />

mentioned above). The latter arrangements<br />

eliminate floor grilles and leave the floor clear<br />

for furniture placement and easier<br />

housekeeping.<br />

Fan air terminals are used in the access floor<br />

plenum 1) to produce the necessary static<br />

pressure for personal and room air outlets, 2)<br />

to eliminate air leakage out of the building<br />

(buildings are not airtight), and 3) to reduce<br />

distribution ductwork. They must be efficient,<br />

with low noise levels and a trouble free, long<br />

life. The additional energy use by these fans is<br />

offset by reduced energy consumption in the<br />

main air handler. The system reduces overall<br />

energy consumption by eliminating air leakage<br />

and reducing total fan horsepower because of<br />

greatly reduced ductwork. Additional reduced<br />

This arrangement also makes balancing the<br />

system much simpler. Fans can be added for<br />

additions in load at any time. For relocation<br />

and remodeling of workstations the fans can<br />

be easily moved, since there is no need to<br />

fasten them in place. They are simply located<br />

on the sub floor where needed.<br />

ANSI/ASHAE 55-1992, Para 5.1.6.3, stipulates<br />

a minimum underfloor temperature of 18°C<br />

(65°F). When supplying air at this temperature<br />

through a cooling coil, it is difficult to properly<br />

control humidity and impossible to use ice<br />

storage. The best strategy is to design the air<br />

handler cooling section to suit the chilled water<br />

or dx system and to bypass sufficient return air<br />

to get the leaving air temperature up to the<br />

desired temperature. This approach can use<br />

face and bypass dampers to control humidity<br />

and eliminates all saturated air <strong>from</strong> the space.<br />

Also, elimination of mixing in the occupied<br />

space produces a cleaner environment.<br />

Particles lighter that air will float up to high air<br />

returns and the system filters, instead of being<br />

recirculated by secondary air movement.<br />

CONCLUSION<br />

The system described above will air condition<br />

individual people instead of the building. It<br />

thus will eliminate dissatisfaction with thermal<br />

conditions (the number one complaint in most<br />

offices), lead to greater productivity and reduce<br />

the greatest cost in any office building, the<br />

3


payroll. By offering sustainability, reduced<br />

energy cost and a cleaner environment, it is<br />

the basis for a more efficient, more productive<br />

“green building.”<br />

ACKNOWLEDGEMENTS<br />

Special thanks for the development of the<br />

system go to Hank Spoormaker, PE, now<br />

deceased, who conceived of the zero pressure<br />

plenum twenty years ago in Johannesburg,<br />

South Africa. Appreciation also goes to Fred<br />

Bauman, UC Berkeley, whose support and<br />

diligent testing helped crystallize a lot of the<br />

concepts, and last, but not least, to Peter Betz<br />

and many others whose belief in a better<br />

system helped me to carry the ball.<br />

CODES AND STANDARDS<br />

ASHRAE. 1989. Ventilation for Acceptable<br />

Indoor <strong>Air</strong> Quality. ANSI/ASHRAE<br />

Standard 62-1989.<br />

ASHRAE. 1992. Thermal Environmental<br />

Conditions for Human Occupancy.<br />

ANSI/ASHRAE Standard 55-1992.<br />

ASHRAE. 2001. ASHRAE Handbook of<br />

Fundamentals 2001.<br />

REFERENCES<br />

Akimoto, T., T. Nobe, S. Tanabe and K.<br />

Kimura. Floor-Supply Displacement <strong>Air</strong>-<br />

Conditioning: Laboratory Experiments.<br />

ASHRAE Transactions V. 105, Pt. 2. (SE-<br />

99-7-1).1999.<br />

Bauman, F., V. Inkarojrit, and Z. Hui. 2000.<br />

Laboratory Test of the <strong>Argon</strong> Personal <strong>Air</strong>-<br />

Conditioning System (<strong>APACS</strong>). Center for<br />

Environmental Design Research,<br />

University of California, Berkeley.<br />

Berglund, L.G. and A. Fobelets. A subjective<br />

human response to low level air currents<br />

and asymmetric radiation. ASHRAE<br />

Transactions 93(1):497-523. 1987.<br />

Blake-Thomas, G. Personally Controlled<br />

Environment: Today and Tomorrow –<br />

Putting People First. ASHRAE Seminar 24<br />

Winter Meeting. 1995.<br />

De Dear, R.J. and M. E. Fountain. Field<br />

Experiments on Occupant Comfort and<br />

Office Thermal Environments in a Hot-<br />

Humid Climate. ASHRAE Transactions V.<br />

100, Pt. 2. (OR-94-14-2 (3829) (RP-702))<br />

1994.<br />

Fanger, P.O. The variability of man’s preferred<br />

ambient temperature <strong>from</strong> day to day.<br />

Archives des Sciences Physiologiques<br />

27(4):A403. 1973.<br />

Fanger, P.O. and N.K. Christensen.<br />

Perception of draught in ventilated spaces.<br />

Ergonomics 29(2):215-35. 1986.<br />

Fanger, P.O., B.M. Ipsen, G. Langkilde, B.W.<br />

Olesen, N.K. Christensen and S. Tanabe.<br />

Comfort limits for asymmetric thermal<br />

radiation. Energy and Buildings. 1985.<br />

Fanger, P.O., A.K. Melikov, H. Hanzawa and J.<br />

Ring, J. Turbulence and draft. ASHRAE<br />

Journal 31(4):18-25. 1989.<br />

Fountain, M., E. Arens, R. de Dear, F. Bauman<br />

and K. Miura. Locally controlled air<br />

movement preferred in warm isothermal<br />

environments. ASHRAE Transactions V.<br />

100, Pt. 2. (OR-94-14-1) 1994.<br />

Kroner, W. M., and J. Stark-Martin.<br />

Environmentally responsive workstations<br />

and office-worker productivity. ASHRAE<br />

Transactions V. 100, Pt. 2. (OR-94-8-3)<br />

1994.<br />

Lorsch, H.G. and O. A. Abdou. The impact of<br />

the building indoor environment on<br />

occupant productivity –Part 1: Recent<br />

studies, measures and costs. ASHRAE<br />

Transactions V. 100, Pt. 2. (OR-94-8-2)<br />

1994<br />

Melikov, A.K., R. Arakelian, L. Halkjaer and<br />

P.O. Fanger. Spot cooling –Part 2:<br />

Recommendations for design of spotcooling<br />

systems. ASHRAE Transactions<br />

V. 100, Pt. 2. (OR-94-14-4 (3831) (RP-<br />

518))1994.<br />

Rohles, F.H. A human factors approach to<br />

performance and productivity. ASHRAE<br />

Transactions V. 100, Pt. 2. (OR-94-8-1).<br />

1994.<br />

Shute, R.W. Integrating access floor plenums<br />

for HVAC air distribution. ASHRAE<br />

Journal. October 1992.<br />

Sodec, F., and R. Craig. The underfloor air<br />

supply system –the European experience.<br />

ASHRAE Transactions V. 96, Pt. 2. (SL-<br />

907-4) 1990.<br />

Spoormaker, H.J. Low-pressure underfloor<br />

HVAC System. ASHRAE Transactions V.<br />

96, Pt. 2. (SL-90-7-2) 1990.<br />

Toftum, J., and P.O. Fanger. <strong>Air</strong> humidity<br />

requirements for human comfort.<br />

ASHRAE Transactions V. 105, Pt. 2. (SE-<br />

99-5-1) 1999.<br />

4

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!