CAUTION<br />

Dust covers are an effective way to limit the entry of dust<br />

<strong>in</strong>to smoke detector sens<strong>in</strong>g chambers. However, they may<br />

not completely prevent airborne dust particles from enter<strong>in</strong>g<br />

the detector. Therefore, System Sensor recommends the<br />

removal of detectors before beg<strong>in</strong>n<strong>in</strong>g construction or other<br />

dust produc<strong>in</strong>g activity.<br />

Be sure to remove the dust covers from any sensors that<br />

were left <strong>in</strong> place dur<strong>in</strong>g construction as part of return<strong>in</strong>g<br />

the system to service.<br />

CAUTION<br />

<strong>Smoke</strong> detectors are not to be used with detector guards<br />

unless the comb<strong>in</strong>ation has been evaluated and found<br />

suitable for that purpose.<br />

Test<strong>in</strong>g<br />

Before test<strong>in</strong>g, notify the proper authorities that the smoke<br />

detector system is undergo<strong>in</strong>g ma<strong>in</strong>tenance and will temporarily<br />

be out of service. Disable the zone or system undergo<strong>in</strong>g<br />

ma<strong>in</strong>tenance to prevent unwanted alarms. <strong>Detectors</strong><br />

must be tested after <strong>in</strong>stallation and as part of periodic<br />

ma<strong>in</strong>tenance. Test <strong>2151</strong> and <strong>2151</strong>T as follows:<br />

NOTE: Before test<strong>in</strong>g the detector, check to ensure the<br />

LEDs bl<strong>in</strong>k. If they do not, the detector has lost power<br />

(check the wir<strong>in</strong>g) or it is defective (return it for repair).<br />

A. Test Magnet (p/n M02-04-01 or M02-09-00)<br />

1. Place the magnet aga<strong>in</strong>st the cover <strong>in</strong> the location<br />

designated by the raised mark to activate the test feature<br />

(see Figure 1).<br />

2. The LEDs should latch ON with<strong>in</strong> 5 seconds <strong>in</strong>dicat<strong>in</strong>g<br />

alarm and annunciat<strong>in</strong>g the panel.<br />

B. Aerosol Generator (Gem<strong>in</strong>i 501)<br />

Set the generator to represent 4% to 5%/ft. obscuration<br />

as described <strong>in</strong> the Gem<strong>in</strong>i 501 Manual. Us<strong>in</strong>g the bowlshaped<br />

applicator, apply aerosol until unit alarms.<br />

C. Direct Heat Method (Hair Dryer of 1000-1500 watts) <strong>2151</strong>T only<br />

A hair dryer of 1000-1500 watts should be used to test<br />

the thermistors. Direct the heat toward either of the two<br />

thermistors, hold<strong>in</strong>g the heat source approximately 12<br />

<strong>in</strong>ches from the detector <strong>in</strong> order to avoid damag<strong>in</strong>g the<br />

plastic hous<strong>in</strong>g. The detector will reset only after it has<br />

had sufficient time to cool. Make sure both thermistors<br />

are tested <strong>in</strong>dividually.<br />

Notify the proper authorities that the system is back on l<strong>in</strong>e.<br />

<strong>Detectors</strong> that fail these tests should be cleaned as described<br />

under MAINTENANCE and retested. If the detectors still<br />

fail these tests, they should be returned for repair.<br />

Clean<strong>in</strong>g<br />

Before remov<strong>in</strong>g the detector, notify the proper authorities<br />

that the smoke detector system is undergo<strong>in</strong>g ma<strong>in</strong>tenance<br />

Figure 1. Bottom and side views show<strong>in</strong>g position of test magnet:<br />

Magnet Test<br />

Marker<br />

Test Magnet<br />

Position<br />

LED Status<br />

Indicators<br />

C0145-00<br />

Magnet Test<br />

Marker<br />

Test Magnet<br />

Position<br />

D100-101-00 2 I56-2806-001R