Modbus & EI Bisynch Addresses<strong>Series</strong> <strong>2000</strong> <strong>Communications</strong> <strong>Handbook</strong>) Digital Input 1 Configuration 2400 version 3 2200 version 2Modbus Bisynch Modbus BisynchO Identity 4: Logic 12352 k0 12352 k09. Input functions 12355 k3 12355 k3192: None193: Manual mode select194: Remote setpoint select195: Setpoint 2 select196: PID set 2 select197: Integral hold198: One-shot self tuneenable199: Adaptive tune enable200: Acknowledge alarms201: Select full access level202: Keylock203: Up button204: Down button205: Scroll button206: Page button207: Run208: Hold209: Run/Hold210: Reset211: Skip212: Holdback enabled213: Least significant BCDdigit214: 2 nd digit215: 3 rd digit216: 4 th digit217: 5 th digit218: Most significant digit219: Setpoint rate limit enable220: Prog. Waits at end ofsegment223: Run/Hold224: Reset/Run225: Standby226: PV select227: Advance to end ofsegment240: Amps192: None193: Man194: Rem195: SP 2197: Int Hld200: Ack202: K/lock210: Reset225: Stby240: Amps5-34 <strong>Series</strong> <strong>2000</strong> <strong>Communications</strong> <strong>Handbook</strong> Part No HA026230 Issue 2.0 Feb-00