BLOWDOWN SEPARATOR (Optional)The blowdown separator design incorporates an internal water seal at the outlet, whichpermits the operator to introduce cold water from the bottom to mix with the hot water fromthe boiler blowdown. This reduces the outlet water temperature for safe discharge.If the separator is less than half full of water after the boiler is blown down, cold tap watermust be added to bring the water level to the half-way mark before the next blowdown.The vent must be piped, full size, to a safe location so that steam flashing off the blowdownwill not injure individuals or damage equipment.Do not reduce the outlet pipe or vent pipe size coming off of the tank.BLOWDOWN SEPARATORFigure 9FM-148 COLUMBIA BOILER COMPANY, REV 6-06- 43 -