General characteristicsOperating conditionsPartition class and loss of service continuity categoryb Partition class of compartments accessible for maintenance (i.e. cable box,voltage transformer compartment, etc.): PM (1)b Loss of service continuity category: LSC2A (2) , but no maintenance requiredon core unitsProtection indexb All external faces of the switchgear: IP3Xb Between compartments: IP2Xb Main circuit and all HV parts: IP67 (except M06A metering cubicles).Mechanical impact strengthb IK07 for standard version.Floodingb Service continuity ensured for 3 days of fl ooding for all functions(except air insulated metering M06A)b After fl ooding, accessories, auxiliaries and relays may require maintenanceor replacement.Vibrationsb IEC 60721 > level 3M4 for standard versionb IACS-E10 for special marine version (*) .Seismic withstand (*)Standard equipment complies with IEC WG 17C/424 (future IEC 62271-210)and MV qualifi cation requirements:b Severity (§ 5 table 1):v AFloor III, ZPA = 10 m/s 2 , 5% damping.b Acceptance class (§4 1.1):v Class 2 (3) .Environmental characteristicsAltitudeTemperature(indoor version)Condensation / humidityChemical / pollutionDustFire and extinguishabilityb Up to 3000 m, no particular precautions except screenedcable connectionsb Over 3000 m, standard precautions: shielded cableconnections and 10% dielectric derating every 1000 mb Storage: from – 40°C to + 80°Cb Operation: from – 25°C to + 40°C(normal conditions) IEC 60721 - level 3K6b Operation: from – 40°C to + 65°C(consult us for special precautions)b IEC 60721 > level 3K6 & 3Z7b IEC 60721 > level 3C2b IEC 60721 > level 3S2b Test at 850°C according to IEC 60695-2-10 /-11 /-12Ring Main Unit versionMade of 2 to 5 functions (except M06A) assembled and tested in factory, deliveredready-to-connect on the network. Please consult us.Outdoor versionConsult us for specifi c outdoor IP54 version.(*) Consult us for availability(1) PM class according to IEC 62271-200: metallic partitioning between compartments.(2) LSC2A (loss of service continuity) according to IEC 62271-200: this category offers thepossibility of keeping other compartments energised when opening a main circuit compartment.(3) Class 2: permanent deformations are acceptable provided that the do not impair the functionalityof the equipment. The equipment shall properly operate during an after the seismic event andno maintenance is required.36 AMTED310010EN

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!