3. Tests<br />

To each Buchholz relay a works-number is given mentioned in the test certificate. Furthermore the<br />

tests made with each Buchholz relay<br />

- Dielectric strength test<br />

(AC 2000 V against casing)<br />

- Leakage test<br />

(25 min with 80 o C warm Transformer oil at 0.25 MPa)<br />

- Functional test<br />

(damper setting, switching systems)<br />

are documented in the test certificate.<br />

The Buchholz relays are delivered in transport<br />

cardboards. In the cap nut of the test key there is a<br />

temporary lock for the switching system. This temporary<br />

lock has to be removed before the device is taken into<br />

operation.<br />

With each device we deliver<br />

- operating instructions<br />

- test certificate<br />

in the agreed language.<br />

Flow test<br />

7<br />

DIN EN ISO 9001:2000 certificate<br />

Functional and leakage test