sales@novatech-usa.com CALL Toll Free: 1-866-433-6682 or 1-281-359-8538<strong>Controller</strong> powers up butdisplays "9999 Err"Conductivity over maximum rangeReduce the system conductivity.Probe wiring incorrectBad Conductivity probeReset limit by pressing the M (Mode) button whenconductivity is back in range.Check probe wiring (see Figure 3, Page8)Replace sensorConductivityreading on controllerdoes not match ahand-held reading.Conductivity reading iswithin specification.Due to variations in hand-held meters, conductivitystandard solutions, temperature compensation, and thecontroller’s accuracy of +/- 2% of scale, the reading onthe controller may not match that of your hand-heldtester.72-910-0217REV. Lwww.novatech-usa.com FAX Toll Free: 1-866-433-6684 or 1-281-359-0084