5-2 Communication <strong>RECO</strong> <strong>PLC</strong> <strong>ISP200</strong>-R/<strong>G2</strong><br />

5.2 Parameterization of the COM Interface<br />

5.3 BT Bus<br />

From PC or<br />

BTV20/30<br />

BT bus<br />

IKB0031<br />

Max. 50 m<br />

BT bus<br />

IKB0031<br />

Max. 50 m<br />

Up to 2 additonal<br />

operator terminals<br />

in the BT bus<br />

As a standard, the multimode COM user interface is delivered as an<br />

RS232 interface. The parameters for RS422/RS485 operation are set by<br />

programming the OPEN_COM standard <strong>PLC</strong> function block and by<br />

assigning the COM FB input correspondingly. More detailed information<br />

can be found in the <strong>PLC</strong> programming instructions (DOK-CONTRL-<br />

WINPCL*_VRS*-AW0_-EN-P).<br />

The BT bus can be used to connect up to four operator terminals of type<br />

BTM15/16 or BTA20. The total maximum length of the BT bus may be up<br />

to 50 m. This applies both to the connection of only one device and to the<br />

connection of the permissible maximum number of 4 devices. It is not<br />

possible to quickly access the I/O data of the operator terminals from the<br />

<strong>PLC</strong> (e.g. %IBP*.*).<br />

The address assignments required for programming can be found in the<br />

respective documents of the devices to be connected.<br />

BT bus<br />

BT bus<br />

Fig. 5-3: BT bus overview<br />

DOK-CONTRL-MTS-R0*.2<strong>G2</strong>-PR01-EN-P