Results of a bad earth<br />
A bad earth circuit – i.e. one with too large a resistance – can sometimes have more<br />
disastrous effects than having no earth at all. This is shown in the illustration, where<br />
the earth-fault circuit has a high resistance mainly due to a bad contact at point A.<br />
earthed<br />
neutral<br />
Figure 6.24 Bad earth path<br />
fuse<br />
consumer’s terminals<br />
fault to appliance casing<br />
<strong>Chapter</strong> 6 Basic electrical circuitry <strong>and</strong> applications<br />
A<br />
bad<br />
earth<br />
The severity of shock will depend mainly upon the surroundings, the condition of<br />
the person receiving the shock <strong>and</strong> the type of supply. When the current starts to<br />
flow, the high resistance connection will heat up <strong>and</strong> this could be a fire hazard. Also,<br />
because the current flowing may not be high enough to blow the fuse or trip the<br />
circuit breaker, the appliance casing remains live.<br />
Results of a good earth path<br />
A good earth path, that is a low resistance one, will allow a high current to flow. This<br />
will cause the protective device to operate quickly, thereby isolating the circuit <strong>and</strong><br />
giving protection against electric shock.<br />
earthed<br />
neutral<br />
Figure 6.25 Good earth path<br />
high current<br />
blows fuse<br />
consumer’s terminals<br />
fault to appliance casing<br />
A<br />
good low<br />
resistance<br />
earth path<br />
143