<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32Introduction<strong>Brivo</strong>’s <strong>ACS</strong>-3100, <strong>ACS</strong>-3400, <strong>ACS</strong>-4100 and <strong>ACS</strong>-4400 model Access Control <strong>Systems</strong> aregenerally compatible with all industry standard 26 bit Wiegand <strong>Reader</strong>s. <strong>Brivo</strong>’s <strong>ACS</strong> productsare also compatible with 4 and 8 bit word-style Wiegand keypads, and some 34, 37 and 40 bitWiegand <strong>Reader</strong>s.<strong>Brivo</strong>’s <strong>ACS</strong> product family is designed to accommodate the latest updates in Wiegand reader bitformats; they are all are compatible with Wiegand devices that transmit up to 64 bit data.A current list of approved <strong>Reader</strong>s and <strong>Keypad</strong>s and a wiring guide and notes for each ismaintained on the <strong>Brivo</strong> web site at www.brivo.com.IF YOU HAVE A SPECIFIC MODEL OF READER/KEYPAD THAT IS NOT LISTED IN THISDOCUMENT OR ON OUR WEBSITE, PLEASE CONTACT CUSTOMER SERVICE AT1-866- BRIVO-4-U AND ASK IF YOUR MODEL CAN BE APPROVED FOR USE.© 2004, BRIVO SYSTEMS, INC. ALL RIGHTS


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32<strong>Brivo</strong> Approved <strong>Keypad</strong>s:Essex KTP162 (12VDC) – “8 bit word”Row#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 Red LED Control Yellow P5-34 +12VDC Red P5-4 P5-45 Ground Black P5-5 P5-56 Shield Tan P5-6 P5-67 Green LED Control Brown P5-7 P5-78 Dual LED Control Orange DO NOT CONNECT9 CCTV Trigger Blue DO NOT CONNECTSpecial notes and installation hints:WARNING: The jumper on the back of the keypad must be placed in the 12VDC position (off) priorto connection to power or un-repairable damage to the <strong>Keypad</strong> will occur.No Beeper control provided from <strong>ACS</strong>, (control not provided by the manufacturer).Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 2


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32Essex KTP163 (12VDC) – “8 bit word”Row#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 Red LED Control Yellow P5-34 +12VDC Red P5-4 P5-45 Ground Black P5-5 P5-56 Shield Tan P5-6 P5-67 Green LED Control Brown P5-7 P5-78 Dual LED Control Orange DO NOT CONNECT9 CCTV Trigger Blue DO NOT CONNECTSpecial notes and installation hints:WARNING: The jumper on the back of the keypad must be placed in the 12VDC position (off) priorto connection to power or un-repairable damage to the <strong>Keypad</strong> will occur.No Beeper control provided from <strong>ACS</strong>, (control not provided by the manufacturer).Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 3


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32<strong>Brivo</strong> Approved Combo Proximity/<strong>Keypad</strong> <strong>Reader</strong>sHID 5355 Proximity with <strong>Keypad</strong>Row#SignalNameConnectorPositionInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 TB1-3 P5-1 P5-12 Wiegand Data 1 TB1-4 P5-2 P5-23 Red LED Control TB1-7 P5-34 +12VDC TB1-1 P5-4 P5-45 Ground TB1-2 P5-5 P5-56 Shield TB1-5 P5-6 P5-67 Green LED Control TB1-6 P5-7 P5-78 Beeper Control TB1-8 P5-89 Hold/Card Present TB1-9 DO NOT CONNECT10 Tamper Common TB1-10 * *11 Tamper Select TB1-11 * *Special notes and installation hints:Switch SW1 Settings: # 3 in OFF Position, all others (1, 2, 4, 5, 6, 7, 8) in the ON position.These wires could be attached to the AUX input, and notification of “Tamper” would then be sent as anAUX notification to the users account, and the local relay could be used for annunciation.Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 4


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32Star RFK101 Proximity with <strong>Keypad</strong>Row#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 +12VDC Red P5-4 P5-44 Ground Black P5-5 P5-55 Green LED Control Brown P5-7 P5-76 Beeper Control Blue P5-8 P5-8Special notes and installation hints:All other wires in the cable harness are not used. Confirm that these wires have their ends terminated in afashion that will not allow them to come in contact with any electrical components or connections.The default setting for jumpers JP1 and JP2 is in the shorted position, this is the correct position forWiegand output.Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 5


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32<strong>Brivo</strong> Approved Proximity <strong>Reader</strong>sAdemco OMNIPROXRow # Signal Name ConnectorPosition1 WiegandData 02 WiegandData 13 Red LEDControlInstaller WireColor<strong>Brivo</strong> P5Connection 6Wire<strong>Brivo</strong>Connection 8WireGreen P5-1 P5-1White P5-2 P5-2N/A P5-3 P5-34 +12VDC Red P5-4 P5-45 Ground Black P5-5 P5-56 Shield Bare Wire P5-6 P5-67 LED Control Brown P5-7 P5-78 Tamper DO NOTCONNECTPurpleDO NOTCONNECTDO NOTCONNECTSpecial notes and installation hints:Single Mode Operation:Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 6


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32AWID Sentinel-Prox KP-6840Row#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 +12 VDC Red P5-4 P5-44 Ground Black P5-5 P5-55 Shield Drain wire CABLE SHIELD P5-6 P5-66 Green LED Control Brown P5-7 P5-77 Beeper Control Yellow P5-88 Hold Control Blue DO NOT CONNECT9 RS232 Output Orange DO NOT CONNECT10 RS232 Output Violet DO NOT CONNECTSpecial notes and installation hints:* This applies to KP-6840 <strong>Keypad</strong>-<strong>Reader</strong> with Revision D firmware for keypad output.Rows # 1, 2, 6, 7 and 8. These are logic level signals. Do not apply power to these wires.Row # 6. Let brown wire float for Red LED. Pull low for Green LED.Row # 7. Beeper sounds after each transaction without connecting yellow wire. Pull low for added beepif required.Rows # 9, and 10 are for simultaneous RS-232 output from the reader. They may be cut or tapedseparately.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 7


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32AWID Sentinel-Prox LR-911Row#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 +12 VDC Red P5-4 P5-44 Ground Black P5-5 P5-55 Shield Drain wireCABLE SHIELD;DO NOT GROUND6 Signal Ground BlueTo controller’sground terminalTo controller’sground terminal7 <strong>Reader</strong> Enabler Yellow<strong>Reader</strong>enabled whenpulled low<strong>Reader</strong>enabled whenpulled low8Receive Data(Serial RD line)OrangeDO NOT CONNECTUsed only withInstallation KitUsed only withInstallation Kit9 RS232 Output Violet DO NOT CONNECTSpecial notes and installation hints:Rows # 1, 2, 6, 7 and 8 are logic level signals. Do not apply power to these wires.Row # 6. Signal return wire. Connect to signal common or ground terminal on controller.Row # 7. <strong>Reader</strong> is in stand-by when this wire is floating; reader is enabled when this wire is grounded.Use a vehicle detector to enable the reader. If no detector, connect this wire to Ground.Row # 8. Used only with AWID’s SP-6820-LR installation test unit.Rows # 8 and 9 are for simultaneous RS-232 output from the reader. They may be cut or tapedseparately.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 8


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32AWID Sentinel-Prox MM-6800Row#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 +12 VDC Red P5-4 P5-44 Ground Black P5-5 P5-55 Shield Drain wire CABLE SHIELD P5-6 P5-66 Green LED Control Brown P5-7 P5-77 Beeper Control Yellow P5-88 Hold Control Blue DO NOT CONNECT9 RS232 Output Orange DO NOT CONNECT10 RS232 Output Violet DO NOT CONNECTSpecial notes and installation hints:Rows # 1, 2, 6, 7 and 8 are logic level signals. Do not apply power to these wires.Row # 6. Let brown wire float for Red LED. Pull low for Green LED.Row # 7. Beeper sounds after each transaction without connecting yellow wire. Pull low for added beepif required.Rows # 9 and 10 are for simultaneous RS-232 output from the reader. They may be cut or tapedseparately.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 9


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32AWID Sentinel-Prox MR-1824Row#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 +12 VDC Red P5-4 P5-44 Ground Black P5-5 P5-55 Shield Drain wire CABLE SHIELD P5-6 P5-66 Green LED Control Brown P5-7 P5-77 Beeper Control Yellow P5-88 Hold Control Blue DO NOT CONNECT9 RS232 Output Orange DO NOT CONNECT10 RS232 Output Violet DO NOT CONNECTSpecial notes and installation hints:Rows # 1, 2, 6, 7, and 8 are logic level signals. Do not apply power to these wires.Rows # 3 and 4. External power source is required for 600 mA peak current at 12 VDC. This sourcemust be regulated and linear (not switching).Row # 6. Let brown wire float for Red LED. Pull low for Green LED.Row # 7. Beeper sounds after each transaction without connecting yellow wire. Pull low for added beepif required.Rows # 9 and 10 are for simultaneous RS-232 output from the reader. They may be cut or tapedseparately.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 10


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32AWID Sentinel-Prox SP-6820Row#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 +12 VDC Red P5-4 P5-44 Ground Black P5-5 P5-55 Shield Drain wire CABLE SHIELD P5-6 P5-66 Green LED Control Brown P5-7 P5-77 Beeper Control Yellow P5-88 Hold Control Blue DO NOT CONNECT9 RS232 Output Orange DO NOT CONNECT10 RS232 Output Violet DO NOT CONNECTSpecial notes and installation hints:Rows # 1, 2, 6, 7 and 8 are logic levels. Do not apply power to these wires.Row # 6. Let brown wire float for Red LED. Pull low for Green LED.Row # 7. Beeper sounds after each transaction without connecting yellow wire. Pull low for added beepif required.Rows # 9 and 10 are for simultaneous RS-232 output from the reader. They may be cut or tapedseparately.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 11


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32AWID Sentinel-Prox SR-2400Row#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 +12 VDC Red P5-4 P5-44 Ground Black P5-5 P5-55 Shield Drain wire CABLE SHIELD P5-6 P5-66 Green LED Control Brown P5-7 P5-77 Beeper Control Yellow P5-88 unused Blue DO NOT CONNECT9 unused Orange DO NOT CONNECT10 unused Violet DO NOT CONNECTSpecial notes and installation hints:Rows # 1, 2, 6 and 7 are logic level signals. Do not apply power to these wires.Row # 6. Let brown wire float for Red LED. Pull low for Green LED.Row # 7. Beeper sounds after each transaction without connecting yellow wire. Pull low for added beepif required.Rows # 8, 9 and 10 are not used. They should be cut or taped separately.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 12


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32Casi-Rusco Model 940 Proximity <strong>Reader</strong>Row#Signal Name(Connection #)WireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 (J1-6) Green P5-1 P5-12 Wiegand Data 1 (J1-7) White P5-2 P5-23 Red LED Drive (J1-3) Blue P5-34 +12VDC (J1-1) Red P5-4 P5-45 Ground (J1-2) Black P5-5 P5-56 Green LED Drive (J1-4) Brown P5-7 P5-77 Beeper Control (J1-8) Violet P5-8 P5-88 Yellow LED Drive (J1-5) Orange DO NOT CONNECT9 Door DI (J1-10) Orange DO NOT CONNECT10 Exit DI (J1-11) Grey DO NOT CONNECTSpecial notes and installation hints:Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Set Switch Block SW-2 for the proper setting for the read range desired and cable length required back tothe <strong>Brivo</strong> Control Panel.Set Switches 5 and 6 to off to set the reader into Wiegand output mode.Set Switches 7 and 8 to the desired Beeper output level.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 13


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32Digi<strong>Reader</strong> Series DR4201 Proximity <strong>Reader</strong>Row#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Blue P5-1 P5-12 Wiegand Data 1 Orange P5-2 P5-23 Red LED Control Brown P5-34 +12VDC Red P5-4 P5-45 Ground Black P5-5 P5-56 Shield Bare wire P5-6 P5-67 Amber LED Control Yellow P5-7 P5-78 Beeper Control Blue P5-89 S-Net A Green DO NOT CONNECT10 S-Net B White DO NOT CONNECTSpecial notes and installation hints:Single Mode Operation:Functions that will be effected,Flashing RED Led, Lockdown mode, will show only as solid RED Led.Flashing AMBER Led, Unlock Hold, will show as alternating RED / Amber Flashing. This looksthe same as Too Many Invalid Keycodes during Unlock Hold.Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 14


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32HID iCLASS R40Row # Signal Name ConnectorPosition1 WiegandData 02 WiegandData 13 Red LEDControlInstaller WireColor<strong>Brivo</strong> P5Connection 6Wire<strong>Brivo</strong>Connection 8WireGreen P5-1 P5-1White P5-2 P5-2Brown P5-3 P5-34 +12VDC Red P5-4 P5-45 Ground Black P5-5 P5-56 Shield Bare Wire P5-6 P5-67 LED Control Orange P5-7 P5-78 Tamper Yellow P5-8 P5-8N/A Purple DO NOTCONNECTN/A Blue DO NOTCONNECTDO NOTCONNECTDO NOTCONNECTSpecial notes and installation hints:Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 15


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32HID 6005 ProxPointRow#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 Red LED Control Brown P5-34 +12VDC Red P5-4 P5-45 Ground Black P5-5 P5-56 Shield Bare wire P5-6 P5-67 Green LED Control Orange P5-7 P5-78 Beeper Control Yellow P5-89 Hold Control Blue DO NOT CONNECT10 Card Present Violet DO NOT CONNECTSpecial notes and installation hints:Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 16


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32HID 5395 ThinLine IIRow#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 Red LED Control Brown P5-34 +12VDC Red P5-4 P5-45 Ground Black P5-5 P5-56 Shield Bare wire P5-6 P5-67 Green LED Control Orange P5-7 P5-78 Beeper Control Yellow P5-89 Hold Control Blue DO NOT CONNECT10 Card Present Violet DO NOT CONNECTSpecial notes and installation hints:Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 17


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32HID 5365 Mini-ProxRow#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 Red LED Control Brown P5-34 +12VDC Red P5-4 P5-45 Ground Black P5-5 P5-56 Shield Bare wire P5-6 P5-67 Green LED Control Orange P5-7 P5-78 Beeper Control Yellow P5-89 Hold Control Blue DO NOT CONNECT10 Card Present Violet DO NOT CONNECTSpecial notes and installation hints:Any operations that require control of the RED LED, (control not provided by the manufacturer).Functions that will be effected,Flashing RED Led, Lockdown mode, will show only as solid RED Led.Flashing GREEN Led, Unlock Hold, will show as alternating RED / Green Flashing. This looksthe same as Too Many Invalid Keycodes during Unlock Hold.Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 18


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32HID 5355Row#SignalNameConnectorPositionInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 TB1-3 P5-1 P5-12 Wiegand Data 1 TB1-4 P5-2 P5-23 Red LED Control TB1-7 P5-34 +12VDC TB1-1 P5-4 P5-45 Ground TB1-2 P5-5 P5-56 Shield TB1-5 P5-6 P5-67 Green LED Control TB1-6 P5-7 P5-78 Beeper Control TB1-8 P5-89 Hold/Card Present TB1-9 DO NOT CONNECT10 Tamper Common TB1-10 * *11 Tamper Select TB1-11 * *Special notes and installation hints:Switch SW1 Settings: # 3 in OFF Position, all others (1, 2, 4, 5, 6, 7, 8) in the ON position.These wires could be attached to the AUX input, and notification of “Tamper” would then be sent as anAUX notification to the users account, and the local relay could be used for annunciation.Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 19


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32Keri MCR-403 InStar Proximity <strong>Reader</strong>Row#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23Red / Single LEDControlBrownP5-7 = SingleModeP5-3 = DualModeP5-7 = SingleMode4 +12VDC Red P5-4 P5-45 Ground Black P5-5 P5-56 Shield Bare wire P5-6 P5-67Green LED Control(Dual Mode Only)OrangeP5-7 = DualModeNo Connect =Single Mode8 Beeper Control Blue P5-8Special notes and installation hints:Single Mode Operation:Wire the brown wire for “RED” Led control to P5-7 (normally the Green Led control on the <strong>Brivo</strong> Panel).Functions that will be effected,Flashing RED Led, Lockdown mode, will show only as solid RED Led.Flashing GREEN Led, Unlock Hold, will show as alternating RED / Green Flashing. This looksthe same as Too Many Invalid Keycodes during Unlock Hold.Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 20


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32Keri P-500 Pyramid Proximity <strong>Reader</strong>sRow#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23Red / Single LEDControlBrownP5-7 = SingleModeP5-3 = DualModeP5-7 = SingleMode4 +12VDC Red P5-4 P5-45 Ground Black P5-5 P5-56 Shield Bare wire P5-6 P5-67Green LED Control(Dual Mode Only)OrangeP5-7 = DualModeNo Connect =Single Mode8 Beeper Control Blue P5-8Special notes and installation hints:Single Mode Operation:Wire the brown wire for “RED” Led control to P5-7 (normally the Green Led control on the <strong>Brivo</strong> Panel).Functions that will be effected,Flashing RED Led, Lockdown mode, will show only as solid RED Led.Flashing GREEN Led, Unlock Hold, will show as alternating RED / Green Flashing. This looksthe same as Too Many Invalid Keycodes during Unlock Hold.Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 21


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32Motorola Flex Pass 5421A+Row#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection<strong>Brivo</strong> P5Connection1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23Red / Single LEDControlBrownP5-7 = SingleModeP5-3 = DualModeP5-7 = SingleMode4 +12VDC Red P5-4 P5-45 Ground Black P5-5 P5-56 Shield Bare wire P5-6 P5-67Green LED Control(Dual Mode Only)OrangeP5-7 = DualModeNo Connect =Single Mode8 Beeper Control Blue P5-8Special notes and installation hints:Single Mode Operation:Wire the brown wire for “RED” Led control to P5-7 (normally the Green Led control on the <strong>Brivo</strong> Panel).Functions that will be affected,Flashing RED Led, Lockdown mode, will show only as solid RED Led.Flashing GREEN Led, Unlock Hold, will show as alternating RED / Green Flashing. This looksthe same as Too Many Invalid Keycodes during Unlock Hold.Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 22


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32Star Models RF-Tiny / RF-10 / RF-20 Proximity <strong>Reader</strong>sRow#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 +12VDC Red P5-4 P5-44 Ground Black P5-5 P5-55 Shield Bare wire P5-6 P5-66 Green LED Control Yellow P5-7 P5-77 Beeper Control Blue P5-8Special notes and installation hints:Any operations that require control of the RED LED, (control not provided by the manufacturer).Functions that will be effected,Flashing RED Led, Lockdown mode, will show only as solid RED Led.Flashing GREEN Led, Unlock Hold, will show as alternating RED / Green Flashing. This looksthe same as Too Many Invalid Keycodes during Unlock Hold.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 23


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32<strong>Brivo</strong> Approved Wiegand Swipe <strong>Reader</strong>sHID 310 Classic SwipeRow#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 +12VDC Red P5-4 P5-44 Ground Black P5-5 P5-55 Green LED Control Brown P5-7 P5-76 Hold Control Blue DO NOT CONNECTSpecial notes and installation hints:Any operations that require control of the RED LED or Beeper are not possible with this model, (controlnot provided by the manufacturer).Functions that will be effected,Flashing RED Led, Lockdown mode, will show only as solid RED Led.Flashing GREEN Led, Unlock Hold, will show as alternating RED / Green Flashing. This looksthe same as Too Many Invalid Keycodes during Unlock Hold.Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.SENSOR CARD Swipe <strong>Reader</strong> 30387Row # Signal Name ConnectorPositionInstaller WireColor<strong>Brivo</strong> P5Connection 6Wire<strong>Brivo</strong>Connection 8Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-24 +5VDC* CONNECT TO Red N/A N/AEXTERNAL 5VONLY5 Ground CONNECT TOEXTERNAL 5VONLYBlack N/A N/A© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 24


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.327 LED Control Brown P5-7 P5-79 Hold Control DO NOTBlue N/A N/ACONNECT*WARNING: THIS READER REQUIRES 5 VOLTS TO OPERATE AND SHOULD BE ONLYCONNECTED TO AN EXTERNAL 5 VOLT POWER SUPPLY. DO NOT POWER THIS READER WITHA BRIVO DOOR CARD OR DAMAGE WILL RESULT! <strong>Brivo</strong> Door Cards are designed to provide thestandard of 12 volts.Special notes and installation hints:All other wires in the cable harness are not used. Confirm that these wires have their ends terminated in afashion that will not allow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 25


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32<strong>Brivo</strong> Approved Barcode <strong>Reader</strong>sNorthern BR-7 Barcode <strong>Reader</strong>Row#SignalNameConnectorPositionInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 Purple P5-2 P5-23 +12VDC Red P5-4 P5-44 Ground Black P5-5 P5-55 ShieldBlack(Heat Shrink)P5-6 P5-66 Green LED Control Brown P5-7 P5-77 Hold/Card Present Blue P5-98 ASCII Select Line Orange DO NOT CONNECT9 BCD Select Line Yellow DO NOT CONNECTSpecial notes and installation hints:NOTE: Tested with Code39 Cards, reader will output a facility code of “000” and the number of thebarcode as the Card Number. All cards entered as Standard 26 bit format.Any operations that require control of the RED LED or Beeper are not possible with this model, (controlnot provided by the manufacturer).Functions that will be effected,Flashing RED Led, Lockdown mode, will show only as solid RED Led.Flashing GREEN Led, Unlock Hold, will show as alternating RED / Green Flashing. This looksthe same as Too Many Invalid Keycodes during Unlock Hold.Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 26


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32<strong>Brivo</strong> Approved Biometric DevicesBioscrypt, VSmart, ADB15Pin #SignalNameWireColor*InstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 WireHarness JacketBlue1 Wiegand D0 Out Green P5-1 P5-12 Wiegand D0 In Green/Wht DO NOT CONNECT.3 Wiegand D1 Out White P5-2 P5-24 Wiegand D1 In White/Blk DO NOT CONNECT.5 Line Trigger Gray DO NOT CONNECT.6 Wiegand Ground Black/Wht P5-5 P5-57 RS485(-) Blue/Black DO NOT CONNECT.8 RS485(+) Blue DO NOT CONNECT.9 RS232(Tx) Violet plug into cable harness**10 RS232(Rx) Violet/Wht plug into cable harness**11 Power Ground Black plug into cable harness** P5-5 P5-512 Signal Ground Black/Red P5-5 P5-513Power In(8-12VDC)Red plug into cable harness** P5-4 P5-414 N/A Red/White DO NOT CONNECT.15 Earth Ground Green/Yel P5-6 P5-6* Check the Veri-Series Setup <strong>Guide</strong> to verify “New Cable” was shipped with unit.** These wires are plugged into a four pin connector housing and attaches to the HID card readerSee the following bioscript .pdf documents:VeriSeries-Operations, Veri-Series Installation and Veri-Series Setup <strong>Guide</strong> manualsSpecial notes and installation hints:The bioscript reader comes with its own power supply and cables. Plug the 15 pin cable assembly intothe finger print reader. The unit communicates to a PC thru the RJ11 jack/cable on bottom side of thefinger print reader. The RJ11 connector plugs into a RJ11 to DB9 converter. The DB9 can now beplugged into the serial port on your PC.See the following bioscript .pdf documents:VeriSeries-Operations, Veri-Series Installation and Veri-Series Setup <strong>Guide</strong> manuals.LED functionality can be found in the manuals listed above.Confirm that the wires marked DO NOT CONNECT, have ends terminated in a fashion that will not allowthem to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 27


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32Bioscrypt, VeriProx, V,HDB15Pin #SignalNameWireColor*InstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand D0 Out Green P5-1 P5-12 Wiegand D0 In Green/Wht DO NOT CONNECT.3 Wiegand D1 Out White P5-2 P5-24 Wiegand D1 In White/Blk DO NOT CONNECT.5 Line Trigger Gray DO NOT CONNECT.6 Wiegand Ground Black/Wht P5-5 P5-57 RS485(-) Blue/Black DO NOT CONNECT.8 RS485(+) Blue DO NOT CONNECT.9 RS232(Tx) Violet plug into cable harness**10 RS232(Rx) Violet/Wht plug into cable harness**11 Power Ground Black plug into cable harness**12 Signal Ground Black/Red P5-5 P5-513Power In(8-12VDC)Redplug into cable harness**14 N/A Red/White DO NOT CONNECT.15 Earth Ground Green/Yel P5-6 P5-6* Check the Veri-Series Setup <strong>Guide</strong> to verify “New Cable” was shipped with unit.** These wires are plugged into a four pin connector housing and attaches to the HID card readerSee the following bioscript .pdf documents:VeriSeries-Operations, Veri-Series Installation and Veri-Series Setup <strong>Guide</strong> manualsSpecial notes and installation hints:The bioscript reader comes with its own power supply and cables. Plug the 15 pin cable assembly intothe finger print reader. The unit communicates to a PC thru the RJ11 jack/cable on bottom side of thefinger print reader. The RJ11 connector plugs into a RJ11 to DB9 converter. The DB9 can now beplugged into the serial port on your PC.See the following bioscript .pdf documents:VeriSeries-Operations, Veri-Series Installation and Veri-Series Setup <strong>Guide</strong> manualsLED functionality can be found in the manuals listed above.Confirm that the wires marked DO NOT CONNECT, have ends terminated in a fashion that will not allowthem to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 28


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32<strong>Brivo</strong> Approved Radio ReceiversAAID AA-R500P Wireless <strong>Reader</strong> And Wiegand ConverterAAID Security Solutions AA-R500P Wireless <strong>Reader</strong>RJ45Connector(Left PortPin #s)AA-R500PDescriptionWire Color(using AAIDsupplied cable)Wiegand Interface(Left Connector)Wiegand InterfaceDescription1 Not Used Orange/White Not Used Not Used2 RS232 TXD Orange RX RS232 Receive Pin3 Power Green/White +12 V +6 to 18V DC4 Ground Blue GND Ground Pin5 Not Used Blue/White Not Used Not Used6 Not Used Green Not Used Not Used7 Not Used Brown/White Not Used Not Used8 Not Used Brown Not Used Not UsedAAID Security Solutions AA-W100 RS232 to Wiegand ConverterRow #Wiegand InterfaceSignalNameWire ColorInstallerWire Color<strong>Brivo</strong> <strong>ACS</strong><strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 Green P5-1 P5-12 Wiegand Data 1 White P5-2 P5-23 +12VDC Red P5-4 P5-44 Ground Black P5-5 P5-5Special notes and installation hints:All other wires in the cable harness are not used. Confirm that these wires have their ends terminated in afashion that will not allow them to come in contact with any electrical components or connections.Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 29


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32Recognition SourceRecognition Source Wireless Universal Strike Interface (WUSI)<strong>Reader</strong>WUSIRow #Signal NameWire ColorTypicallyUsedWUSI ConnectionDescription123WiegandData 0WiegandData 1Red LEDControlGreenWhiteBrownDATA/DOCLK/D1RED_LED4 +12VDC Red 12VDC+5 Ground Black GND6 Shield Bare wire Not Used78Green LEDControlBeeperControlOrangeYellowGRN_LEDNot Used12VDC+GND+7 to 14V DCDC Ground© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 30


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32Recognition Source Panel Interface Module (PIM)<strong>Brivo</strong> <strong>ACS</strong> Series PanelPIMRow #Signal NamePIMConnectionDescription1 Wiegand Data 0 DATA/D02 Wiegand Data 1 CLK/D13 Red LED Control NOT USED4 +12VDC 12V+5 Ground GROUND(<strong>Brivo</strong> <strong>ACS</strong> Panels arecapable of powering the PIM)6 Shield NOT USED7 Green LED Control NOT USED8 Beeper Control NOT USED9 <strong>Keypad</strong> Hold NOT USED1011Common Strike RelayContact (P2 Pin 1)Normally C Strike RelayContact (P2 Pin 2)STK-NOSTK-COM12 NOT USED 12V-1314Request To Exit Input (P6Pin 3)Door Status Input (P6 Pin1)15 NOT USEDEXIT REQDOOR STATTROUBLEDADA/D0Special notes and installation hints:Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 31


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32Sentex CPWR Wiegand ReceiverRow#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Green LED Control Brown P5-7 P5-72 Wiegand Data 1 White P5-2 P5-23 Wiegand Data 0 Green P5-1 P5-24 +12VDC Red P5-4 P5-45 Ground Black P5-5 P5-56 Shield Bare P5-6 P5-6Special notes and installation hints:Settings for Switch “S1-FORMAT” in the CPWR. These set the Wiegand output to 26 bit standard output.#3 – off (left)#2 – off (left)#1 – ON (right)#0 – off (left)Settings for Switch “S1-BUTTON” in the CPWR. These set the pushbuttons on the transmitter (1-3) to beread by the receiver. This setting allows all three buttons to be used. Note they will all appear as thesame “credential” to the Access control panel. Button 4 will always appear to be unique from the firstthree. Refer to the Remote Users Manual provided with each Remote Control.#3 – ON (right)#2 – ON (right)#1 – ON (right)Settings for Switch “S1-BUTTON” in the CPWR. This sets the Facility Code to be the one transmittedfrom the Remote Control.#FFC – off (left)Confirm that the wires marked DO NOT CONNECT have their ends terminated in a fashion that will notallow them to come in contact with any electrical components or connections.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 32


<strong>Brivo</strong> <strong>ACS</strong> <strong>Reader</strong> <strong>Keypad</strong> <strong>Wiring</strong> <strong>Guide</strong> Version 1.32Get your device Approved:Proposed New Device: Row#SignalNameWireColorInstallerWire Color<strong>Brivo</strong> P5Connection6 Wire<strong>Brivo</strong> P5Connection8 Wire1 Wiegand Data 0 P5-1 P5-12 Wiegand Data 1 P5-2 P5-23 Red LED Control P5-34 +12VDC P5-4 P5-45 Ground P5-5 P5-56 Shield P5-6 P5-67 Green LED Control P5-7 P5-78 Beeper Control P5-89 Hold Control DO NOT CONNECTSpecial notes and installation hints:Use this page to document other devices that you would like <strong>Brivo</strong> <strong>Systems</strong>, Inc. to include in the list of<strong>Brivo</strong> Approved Devices. Then contact Customer Service at 1-866-BRIVO-4-U, and they will give youinstructions on how to submit the information, and a device to be tested.Maximum Wire Length (Panel to <strong>Reader</strong>) = 500 feet.© 2004, <strong>Brivo</strong> <strong>Systems</strong>, Inc. All rights reserved. Doc. #114A2582 Page 33

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!