Single vs Block Data TransferHelp! I’m I m getting “could not create cacheblock”‣ This error occurs frequently when the <strong>FieldServer</strong> is configuredas a modbus slave‣ It means that the <strong>FieldServer</strong> has received a poll for addressesthat do not exist in the <strong>FieldServer</strong> under any one Server mapdescriptor.‣ The content of the error message will tell what poll wasreceived. The message can be interpreted as follows:T02> MODBUS_TCP : Could not create cache blockT02> Node:1 Addr:40001 Len:100Server Nodebeing polled<strong>Modbus</strong>Addressbeing polledLength of poll