28.11.2012 Views

REI Mar-Apr 2012 - Renewable Energy Installer

REI Mar-Apr 2012 - Renewable Energy Installer

REI Mar-Apr 2012 - Renewable Energy Installer

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Test case<br />

Knowledge: Solar PV<br />

Jim Wallace of Seaward Solar unravels the confusion surrounding solar PV<br />

testing and the use of appropriate test equipment<br />

he enormous expansion of the<br />

T<br />

solar PV market has presented<br />

significant opportunities for<br />

installers and suppliers of solar<br />

PV equipment.<br />

For the installer faced with the question<br />

of what test instruments to use, the matter is<br />

therefore one of being able to identify exactly<br />

what is needed to fulfil their obligations to the<br />

customer and also satisfy the various industry<br />

standards and best working practices.<br />

The requirement for all installers of<br />

PV systems in the UK is to satisfy the<br />

Microgeneration Installation Standard: MIS<br />

3002 which requires that PV systems are<br />

installed in accordance with the DTI’s “Guide<br />

to the installation of PV systems, 2nd Edition<br />

2006.”<br />

In addition to the guidance given by the<br />

DTI, a British Standard BS EN 62446:2009<br />

Pass the test: <strong>Installer</strong>s are faced with a range of<br />

issues when testing<br />

Grid connected PV systems – Minimum<br />

requirements for system documentation,<br />

commissioning tests and inspection has<br />

been published, giving details of specific<br />

electrical tests that should be performed all<br />

on PV systems at the time of installation and<br />

commissioning.<br />

Fundamentally, a PV system is part<br />

of the electrical installation and therefore<br />

the electrical works should comply with<br />

the requirements of BS 7671 IEE Wiring<br />

Regulations 17th Edition, along with the<br />

particular requirements for the inspection<br />

and testing of DC circuits specified by BS EN<br />

62446.<br />

Earth continuity<br />

Where protective earthing and/or<br />

equipotential bonding conductors are fitted<br />

on the DC side of the installation, for example<br />

bonding of the array frame, the continuity<br />

should be tested. The connection to the<br />

main earthing terminal should be tested.<br />

An instrument which complies with the<br />

requirements of BS EN 61557-2 should be<br />

used.<br />

Open circuit voltage and polarity<br />

Prior to installation, it is good practise to<br />

measure the open circuit voltage of each PV<br />

module and compare the measured value with<br />

that on the rating plate to ensure that each<br />

module is functioning. It is much easier to<br />

correct problems or replace a faulty module<br />

before it is installed. It should be remembered<br />

that the data shown on the rating plate is<br />

taken under standard test conditions and<br />

values measured in the field may deviate from<br />

those shown on the rating plate. The polarity<br />

of the DC cables should also be checked to<br />

ensure it is correct.<br />

When the modules have been installed,<br />

the open circuit voltage of each string should<br />

be measured and compared with the expected<br />

value. The polarity should also be confirmed.<br />

For systems with multiple identical strings,<br />

the open circuit string voltages should be<br />

compared. For stable irradiance conditions the<br />

values should typically be within 5 per cent.<br />

The measured open circuit voltage for each<br />

string should also be recorded on a PV array<br />

test report.<br />

Voltages less than the expected values<br />

may indicate that one or more modules are<br />

connected with incorrect polarity or insulation<br />

faults. Higher voltages are usually the result of<br />

wiring errors.<br />

Short circuit current<br />

The string short circuit current is measured by<br />

applying a temporary short circuit across the<br />

DC terminals of the PV string and measuring<br />

the resultant DC current. The apparatus used<br />

to apply the short circuit must have a rating<br />

greater than the potential short circuit current<br />

and open circuit voltage.<br />

The temporary short circuit can be<br />

applied by a short circuit cable connected<br />

into a switching device already present in<br />

the string circuit, a suitably rated test box or<br />

a dedicated PV short circuit test instrument.<br />

When the temporary short circuit has been<br />

applied, the short circuit current can be<br />

measured using a suitably rated DC current<br />

clamp or in-line DC ammeter. In the case of<br />

a dedicated PV test instrument, such as the<br />

Seaward Solar PV100, the short circuit load<br />

and in-line DC ammeter are housed within the<br />

test instrument.<br />

For systems with multiple identical<br />

strings, the short circuit string currents should<br />

be compared. For stable irradiance conditions<br />

the values should typically be within 5 per<br />

cent. The measured short circuit current for<br />

each string should be recorded on a PV array<br />

test report.<br />

It should be remembered that applying or<br />

removing a short circuit on a live PV system<br />

is potentially hazardous. Care should be taken<br />

to avoid risk of electric shock or damage<br />

due to electrical arcing. The installer should<br />

therefore give careful consideration as to how<br />

this test is to be performed and ideally use an<br />

instrument which is capable of automatically<br />

applying a short circuit and measuring<br />

accurately the current during the test.<br />

www.renewableenergyinstaller.co.uk | 65

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!