3.1.7 Buildings designed for low temperature<br />

heating and high temperature cooling<br />

The buildings themselves are designed to have a low<br />

heating and cooling demand. Specifically, this involves<br />

constructing the buildings with very good thermal<br />

insulation and small ventilation losses, integrating<br />

mechanical ventilation with heat recovery, and limiting<br />

summer solar gains by means of effective shading. The<br />

characteristics of the buildings are summarised in Table 3.3.<br />

Limiting the heating and cooling demands in this way means<br />

that most of the remaining demand can theoretically be<br />

met by low exergy sources (this means heat demand is<br />

met by means of a low temperature heat supply, and the<br />

cooling demand by a high temperature cooling supply). It<br />

w<strong>as</strong> estimated that the mine <strong>water</strong> from different depths<br />

at Heerlen can be used to contribute significantly to these<br />

demands with only small temperature increments (and hence<br />

energy) required from supplementary systems.<br />

Table 3.3: Characteristics of buildings designed for low temperature heating and high temperature cooling<br />

Building Regulation NL Practice 2007 NL <strong>Mine</strong> <strong>water</strong> Lowex<br />

Thermal insulation<br />

Envelope Rc = 2.5<br />

Glazing U = 3.0<br />

Ventilation<br />

No system requirements<br />

Air tightness<br />

qv 10 < 200 (n50 = 3)<br />

Emission system<br />

No requirements<br />

HVAC system/efficiency<br />

No requirements (but in EPR)<br />

EPC dwellings<br />

0.8<br />

Heerleheide<br />

EC<br />

HH1<br />

24ºC<br />

Fig 3.5: Schematic view of the energy concept<br />

Thermal insulation<br />

Envelope Rc = 3.0<br />

Glazing U = 1.5<br />

Ventilation<br />

50% ME/50% MVHR<br />

Air tightness<br />

qv 10 = 100..150<br />

Emission system<br />

Radiators<br />

HVAC system/efficiency<br />

Condensing boilers<br />

Efficiency = 95%<br />

No cooling<br />

EPC dwellings<br />

0.8<br />

Thermal insulation<br />

Envelope Rc = 4.0<br />

Glazing U = 1.2<br />

Ventilation<br />

MVHR efficiency = 95%<br />

Air tightness<br />

qv 10 < 62.5 (n50