Relay and Current Sensor in OneDirectly start/stop load and current sensing all in one package (no external ring is needed.) Wire colors to “Load”and “60 Hz ac” differ depending on the model being used. Configurations are either YELLOW & ORANGE,BLUE & YELLOW, or ORANGE & ORANGE.ControllerDigital InDigital OutStartStopRelaySolidStateSwitchTransducerInternal 20 AmpRIBX24BFRIBX24SBFRIBX24BARIBX24SBAInternal 10 AmpRIBXLCFRIBXLSFRIBXLCARIBXLSAInternal 5 AmpRIBXLCEARIBXLSEALoad60 Hz acMotor StarterAllows relay to control a motor starter while sensing current flowing to the motor.ControllerDigital Out3-PhaseLineVoltageStart/Stop RelayCurrent Sensor CircuitryMotorStarter24 VacMotorExternalSensor RingExternal Sensor RingRIBXLCRFRIBXLCRARIBXLCJFRIBXLCJARIBXLSRFRIBXLSRARIBXLSJFRIBXLSJADigital InSolid StateSwitchTransducerSensor only for 1.25 Amp to 150 Amp LoadUse sensor only devices without relay where start/stop is not required.3-PhaseLineVoltageMotorStarterMotorExternal Sensor RingRIBXRARIBXRFControllerDigital OutDigital InCurrent Sensor CircuitrySolid StateSwitchTransducerExternalSensor Ring800.888.5538 : www.<strong>Functional</strong><strong>Devices</strong>.com1


Panel Mounted Relay and Internal SensorStart/Stop Relays with Internal Current Sensors measure current flow through the relay contacts, no external ring isneeded. Senses current as low as .50 Amp.PanelControllerDigital InDigital OutRIBMX20 AmpMax LoadInternal 20 AmpRIBMX24BFRIBMX24SBFRIBMX24BARIBMX24SBAStart/Stop RelayCurrent Sensor CircuitrySolid StateSwitchTransducer60 Hz acInterlocking LoadsSome RIBX current sensor relays can be used to sense 1 or more loads to turn on another.24 VacSourceCurrent Sensor CircuitrySolid StateSwitchRIBXStart/Stop RelayTransducer60 Hz acExternal SensorLaundromatExhaust FanDryer 1Internal 10 AmpRIBXLCRFRIBXLCRARIBXLCJFRIBXLCJARIBXLSRFRIBXLSRARIBXLSJFRIBXLSJADryer 2Interlocking Loads (No Transformer)Self-powered Current Sensors of the RIBX Series and relays of the Dry Contact Input RIB® Series may beapplied to interlock Load 2 to Load 1.Current sensing maybe internal or externalLoad WireRIBX SERIESCurrent Sensor OnlyCurrentSensorStatusLoad 1Low Voltage(Class II)2 <strong>Functional</strong> <strong>Devices</strong>, <strong>Inc</strong>. : American Made. American Owned.Dry Contact InputRIB® SeriesLocal Power120, 240, 277 VacLoad 2Dry Contact Input RelaysRIB21CDCRIB01BDCRIB01SBDCRIB02BDCRIB02SBDCRIBM01ZNDCRIBM02ZNDCRIBM013PNDCRIBD01BDC (Time Delay)RIBD02BDC (Time Delay)RIBD01BDC-DOB (Time Delay)RIBD02BDC-DOB (Time Delay)Current SensorsRIBXKF RIBXFRIBXKTF RIBXARIBXKA RIBXRFRIBXKTA RIBXRARIBXGA RIBXJFRIBXGF RIBXJARIBXGTA RIBMXFRIBXGTF RIBMXARIBXGFL RIBMXRFRIBXGTFL RIBMXRA


Damper Motor Control with True-HOAThe damper motor can be stopped in mid position for debugging. When auto/manual selector is in auto, relay controlsthe load. When in manual, use the manual switch to control the load.24 Vac FromControllerWht/BluWht/YelWht/Blk(not used)Auto / <strong>Manual</strong> SelectorAutoN/CClosed<strong>Manual</strong> SwitchOpenManN/OClosedORANGEYELLOWBLUELine (120 Vac)Open(120 Vac)NeutralClose(120 Vac)DamperMotor10 & 15 AmpRIBU1SCRIBH1SCRIBTU1SCRIBTH1SCRIBMU1SCRIBMH1SC20 AmpRIB2401SBCRIB2402SBCRIBT2401SBCRIBT2402SBCRIBM2401SBCRIBM2402SBCRIBU1S vs. RIBU1SCStock model RIBU1SC for relay control applications that require true-HOA on either N/O or N/C. No jumpers and nowrong orders.24 Vac FromControllerWht/BluWht/Yel24 Vac FromControllerWht/BluWht/YelRIBU1SRIBU1SC120 VacOrangeOrange120 VacYellowOrange (N/O)Blue (N/C)RIBU1S has a lower costbut if N/C is desired onrelay, it must be specifiedwhen ordering.LOADRIBU1SC is an alternativeto the RIBU1S that allowsone item to be ordered - noneed to specify N/O or N/C.LOAD10 & 15 AmpRIBU1SCRIBH1SCRIBTU1SCRIBTH1SCRIBMU1SCRIBMH1SC20 AmpRIB2401SBCRIB2402SBCRIBT2401SBCRIBT2402SBCRIBM2401SBCRIBM2402SBCN/O or N/C, you choose<strong>Manual</strong> Analog Override SwitchInitial installation or trouble shooting can be smoother and much less costly by adding the RIBMNA1D0. It allows you tomanually control an analog output without accessing complicated algorithms in a controller. An indicator is provided forvisual confirmation of percentage output. When you are finished, you can switch back to auto to put the controller backin control.24 Vac/dcAnalog OutRIBMNA1D0ControllerDigital InDry Contact Feedback Signal(when device is in manual position)Analog OutLoad800.888.5538 : www.<strong>Functional</strong><strong>Devices</strong>.com3


Limit Extra Transformers with Dry Contact Input RelaysEliminate the expense of extra transformer(s) and associated wiring.BeforeDRYCONTACTSEnclosureAfterDRYControllerCont. Pwr.D.O.1D.O.2D.O.3EnclosureControllerCont. Pwr.24 Vac24 Vac24 Vac40VA40VA100VA120 Vac120 VacRIBU1C'sDry ContactInput RIB'sEnclosed RelaysRIB21CDCRIB01BDCRIB01SBDCRIB02BDCRIB02SBDCRIBD01BDC (Time Delay)RIBD02BDC (Time Delay)RIBD01BDC-DOB (Time Delay)RIBD02BDC-DOB (Time Delay)Track RelaysRIBM01ZNDCRIBM02ZNDCRIBM013PNDCCONTACTSD.O.1D.O.2D.O.3Detect Water Levels with Dry Contact Input RelaysIf the water touches the wires, the relay will turn on (closes COMMON to N/O and opens COMMON to N/C.)Uses UL Approved low-voltage to sense water and activate relay.Water PanDry Contact Input RelayControlCircuitRelay120-277 Vac PowerLoadAny typical non-corrosiveprobes may be used.Enclosed RelaysRIB21CDCRIB01BDCRIB01SBDCRIB02BDCRIB02SBDCRIBD01BDC (Time Delay)RIBD02BDC (Time Delay)RIBD01BDC-DOB (Time Delay)RIBD02BDC-DOB (Time Delay)Track RelaysRIBM01ZNDCRIBM02ZNDCRIBM013PNDCMonitoring Switch Position with a ControllerDigital In 1 and 2 of the controller can be used to monitor the position of the HOA switch. The controller can beprogrammed to log the status of the HOA and provide a warning if the switch is in an override position.ControllerDigital OutCommonDigital In 1Digital In 2Common10-30Vac/dcCommon120 Vac Not UsedClosedSwitchAutoPole #2CommonRelaySwitchPole #1AutoCommon60 Hz acLoadEnclosed Relays10 AmpRIBU1SMRIBH1SMTrack Relays15 AmpRIBMU1SMRIBMH1SMRIBMNU1SMRIBMNH1SMDI 1 DI 2 ResultOpen Open Overridden OffOpen Closed AutoClosed Open Overridden OnClosed Closed Error Condition4 <strong>Functional</strong> <strong>Devices</strong>, <strong>Inc</strong>. : American Made. American Owned.


High Voltage Optoisolated RelaysOptoisolated relays help isolate noisy loads from the controller. Good for controlling power relays from analog outputs.ControllerPowerSupplyRelay60 Hz acLoadEnclosed RelaysRIBTE01BRIBTE02BRIBTE01SBRIBTE02SBRIBTE01PRIBTE02PTrack RelaysRIBME2401BRIBME2402BRIBME2401SBRIBME2402SBRIBME2401PRIBME2402PDigital Out(or Analog Out)OptoInputOpto RIB®Low Voltage Optoisolated RelaysOptoisolated relays help isolate noisy loads from the controller. Good for controlling power relays from low powerdigital or analog outputs.Controller24 Vac/dcAnalog or Digital OutPowerSupplyOptoInputRelay60 Hz acLoadEnclosed RelaysRIBTELCRIBTELSRIBTE24BRIBTE24SBRIBTE24PTrack RelaysRIBME2401BRIBME2402BRIBME2401SBRIBME2402SBRIBME2401PRIBME2402POpto RIB®Polarized RelaysRelays are polarized to work in a supervised system and may be turned on and off by reversing polarity.For fire alarm systems, smoke control systems, etc.LoadRIB24C-FACoil+ –LoadRIB24C-FACoil+ –Enclosed RelaysRIB12C-FARIB24C-FARIB12S-FARIB24S-FARIBT24B-FARIB24P-FATrack RelaysRIBMN12C-FARIBMN24C-FARIBMN12S-FARIBMN24S-FAControllerEnd ofLineResistorSignaling Circuit800.888.5538 : www.<strong>Functional</strong><strong>Devices</strong>.com5


Condense Work Space and Wiring (Power Control)Power Control Centers allow you to save large amounts of time, space, and wiring throughout your panel.BeforeThere is a lot of extra wiring in this enclosurewhich not only takes up space but also increasesthe difficulty and time associated with installation.AfterBy using one of <strong>Functional</strong> <strong>Devices</strong>' Power ControlCenters you will greatly reduce installation time, aswell as save space in your enclosure.Enclosed 4 AmpPSPT2RB4PSPW2RB4Enclosed 10 AmpPSPT2RB10PSPW2RB10ConduitPower Control Center is pre-wiredConduitEnclosureEnclosureSub-PanelSwitchFuseTo remainderof panelHNGHNGTo remainderof panelSub-PanelSwitch, Breaker &Indicator LightCondense Work Space and Wiring (Power Supplies)The PSC, PSH, and PSB Series Power Supplies allow you to save large amounts of time, space, and wiringthroughout your panel.BeforeThere is a lot of extra wiring in this enclosurewhich not only takes up space but also increasesthe difficulty and time associated with installation.AfterBy using one of <strong>Functional</strong> <strong>Devices</strong>' PowerSupplies you will greatly reduce installationtime, as well as save space in your enclosure.Power SuppliesAny models ending in “B10” in the PSC,PSH, or PSB Power Supply SeriesConduitPower Supplies are pre-wiredConduitEnclosureEnclosure24Vac Switch/Breaker24VacSub-PanelSwitchFuseTo remainderof panelHNGHNG120Vac from10A Switch &CB to remainder24Vacof panelPower SupplyMain Power10A Switch/CB & Indicator LightSub-Panel24VacIndicatorSwitch in a Box Enclosed ControlsPre-labeled 20 Amp switches are great for new installations or last minute corrections to controls jobs. Switch labelsmay be custom selected when ordering.2 PositionTo A/CPower InSummerWinterHeat(Winter)Cool(Summer)2 PositionSIB04SSIB05S3 PositionSIB02SSIBLS3 Position24 VacHandOffAutoCoilContactorControllerDigital Out24Vac TransformerDO From ControllerHandOffAutoContactor Coil6 <strong>Functional</strong> <strong>Devices</strong>, <strong>Inc</strong>. : American Made. American Owned.


Electronic Air CleanerModels RIBXGHF, RIBXGHTF, RIBXGHA, or RIBXGHTA can be used to control an electronic air cleaner based on whetheror not the blower motor is turned on.LOHIBlowerMotor120Vac SourceCRIBXGHF, RIBXGHTF,RIBXGHA, or RIBXGHTAWhen current drawnby Blower Motorexceeds RIBXGHthreshold, SPSTcontacts connect120Vac source toline input ofAir Cleaner.NeutralElectronic Air CleanerHumidifier ControlSolid and split core current sensors can be used along with a humidistat for control of a humidifier based on whetheror not the blower motor is turned on.BlowerMotor24VacCOMLOHICEnclosed MiniCurrent SensorHumidistatHumidifierEnclosed Mini Current SensorsRIBXKFRIBXKTFRIBXKARIBXKTARIBXGFRIBXGTFRIBXGARIBXGTAOccupancy Sensor on Open Protocol NetworkA LonMark® certified or a BACnet® compatible relay with a digital input can be used with an occupancy sensor in a roomand turn on and off loads based on that status. This saves the cost of buying a LonMark® compatible or BACnet®compatible occupancy sensor by utilizing the digital input on our device.Network24 Vac/dcLonMark® Certifed orBACnet® Compatible RelayClass II Dry Contact InputLonMark® Certified RelaysRIBTW2401B-LNRIBTW2402B-LNRIBTW2401SB-LNRIBTW2402SB-LNOccupancy SensorBACnet® Compatible RelaysRIBTW2401B-BCRIBTW2402B-BCLineNeutralOrgYelLoad800.888.5538 : www.<strong>Functional</strong><strong>Devices</strong>.com7


Loop-Powered RIBXK420 Series andRIBXG420 Series (High-Accuracy)Control Optoisolated Relay with4-20mA LoopAdd 250Ω across Optoisolated Relay 5-25 Vdc control input.Relay turns on at approximately 10mA and off at 8mA.Mini Current SensorMini Current SensorDC SupplyLoad WireDC SupplyLoad Wire- +*Add 250 Ohms for1-5 Vdc Analog InRED +BLACK -- +*Add 250 Ohms for1-5 Vdc Analog In250ΩRED +BLACK -- +4-20 mA Analog In*1-5 Vdc Analog InControllerEnclosed Mini Current SensorsRIBXK420-20RIBXK420-50RIBXK420-100RIBXG420-20RIBXG420-50RIBXG420-100Enclosed RelaysRIBTELCRIBTELSRIBTE24BRIBTE24SBRIBTE24PTrack RelaysRIBME2401BRIBME2402BRIBME2401SBRIBME2402SBRIBME2401PRIBME2402PEnclosed MiniCurrent SensorsRIBXK420-20RIBXK420-50RIBXK420-100RIBXG420-20RIBXG420-50RIBXG420-100Self-Calibrating Current SensorsThe self-calibrating current sensor begins its 30 second self calibration process the first time current is applied within the operatingrange. This procedure uses the user selected differential to set the trip threshold at a 15% or 25% level. Selection is completed priorto install using the appropriate DIP switch setting, keeping the installer’s hands away from possible shock hazard, as well as savinginstallation time.( OLD WAY )Danger!!!Line( NEW WAY )SafeLineSelf-Calibrating Current SensorsRIBXGA-SCALRIBXGTA-SCALOld<strong>Manual</strong> SensorNewRIBXGA-SCALOpen CoverMotorStarterClosed CoverMotorStarterLoadScrewdriverLoadHands and tools exposedto high voltage whileadjusting potentiometer ofcurrent sensorHands safely awayfrom high voltage becauseSCAL adjusts itself8 <strong>Functional</strong> <strong>Devices</strong>, <strong>Inc</strong>. : American Made. American Owned.


Echelon® Thermistor-In <strong>Application</strong>A thermistor is used to read the temperature of a room or area. That data is fed back to the LonWorks ® system. When thetemperature is out of range, the relay is commanded by the network, activating the exhaust fan, heater, or otherdevice. A current sensor is used to feed back load status to the network. If there is a command and status mismatch, thenetwork can issue an alarm to the operator’s console.FT-10 Network24 Vac/dcCOMLonMark® Compatible RelayDigital InputRelay OutputLineRIBX SeriesNeutralRoom or AreaThermistorExhaust FanorHeaterEnclosed RelayRIBTW24SB-LNT2RIBTW24SB-LNT3Track RelayRIBMW24SB-LNT2RIBMW24SB-LNT3Enclosed Mini Current SensorsRIBXKF RIBXGFRIBXKTF RIBXGTFRIBXKA RIBXGARIBXKTA RIBXGTARIBXGFLRIBXGTFLEchelon® Relay / Current Sensor <strong>Application</strong>Save time, money, and messy wiring. LonMark ® certified relay contains an internal current sensor for load status. Relay control andload status are easily accessible from the FT-10 Network.FT-10 Network24 Vac/dcCOMLonMark® Certified Relay & Current Sensor}InternalCurrentStatusExhaust FanA/C Line PowerHeaterEnclosed ModelRIBTWX2401SB-LNRIBTWX2402SB-LNTrack ModelRIBMNWX2401SB-LNRIBMNWX2402SB-LNRelayor800.888.5538 : www.<strong>Functional</strong><strong>Devices</strong>.com9


Time DelayLoad 2 stays on selected amount of time after load 1 goes off.In this example, voltage can beany voltage from 120-277 Vac.Time Delay RelaysRIBD2421CLoad 1(Thermostat ControlledHeater, for example)BluNeutralWht/BrnBluLoad 2(Circulating Fan,for example)YelWht/YelYelRIB®Select RIB® with coil inputappropriate to sense Load 1.RIBD2421CEchelon® Analog-In <strong>Application</strong>Simple and easy load control and status along with analog input provide everything needed to control andinterface to your HVAC application. Save the expense of a controller for smaller remote jobs or complete largerjobs, as well.FT-10 Network24 Vac/dcCOMRIBMW24SB-LNAI or RIBTW24SB-LNAIDigital InputRelay OutputLineRIBX SeriesNeutral+5Vdc or+10VdcCOMDifferentialPressureTransducerHVAC FanAir FilterEnclosed RelayRIBTW24SB-LNAITrack RelayRIBMW24SB-LNAIEnclosed Mini Current SensorsRIBXKF RIBXGFRIBXKTF RIBXGTFRIBXKA RIBXGARIBXKTA RIBXGTARIBXGFLRIBXGTFLActivate Load for Pre-Determined Time Using Dry Contact Input / Time DelayRelay and Normally Closed SwitchLocal PowerNeutralHotWht/BlkWht/BlkBlu• Activate (open) switch until load comes on.• Release switch.• Load will be powered until time delay exprires.NormallyClosedSwitch(Not provided)Wht/RedDryContactWiresYelFanEnclosed RelaysRIBD01BDCRIBD02BDCWht/BluRIBD01BDC – 120 Vac operationRIBD02BDC – 208-277 Vac operationOrgWire NutNeutral10 <strong>Functional</strong> <strong>Devices</strong>, <strong>Inc</strong>. : American Made. American Owned.AM578L 07.24.13