9.7.4 Low outlet water temperature protection at COOL (Code: AL03)At cool mode, if ST≤AL01, all the compressors will be stopped, other parts will keep their original state. Acontinuous blink warning code AL03 will appear on the LCD, until ST≥AL01+AL02, the unit will turn to its normalwork.9.7.5 The outdoor side low outlet water temperature protection at HEAT (Code:AL04)When SF03=1, in heat mode working, if STO≤AL01, all the compressors will be stopped, other parts will keeptheir original state. A continuous blink warning code AL04 will appear on the LCD, until STO≥AL01+AL02, the unitwill turn to its normal work.9.7.6 High outlet water temperature protection at HEAT (Code: AL05)In heat mode, ST≥AL03, all the compressors will be stopped, other parts will keep their original state. Acontinuous blink code AL05 will appear on the LCD, until ST≤AL03+AL04, the unit will turn to its normal work.9.7.7 Water flow switch protection (Code: AL17)At normal working condition, if there is no signal from water flow switch within AL05 after starting the outdoorside water pump, a continuous blink warning code AL017 will appear on the LCD.During unit working, when check FS=OFF, all the compressors will be stopped, other parts will keep their originalstate, a continuous blink warning code AL017 will appear on the LCD.9.7.8 Low evaporate temperature protection (Code: AL20)The protection function will be valid at COOL mode as well as at HEAT mode when SF03=1During normal working, if ET≤AL08, all the compressors will be stopped, other parts will keep their original state,a continuous blink warning code AL20 will appear on the LCD.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!