D-AEnd of control sequence start positionAs soon as the sequence switch has reached the start position – therebyswitching itself off – the flame detector and extraneous light test will start again.During the burner off periods, the flame supervision circuit is live.A faulty flame signal of a few seconds will initiate lockout.Short ignition pulses of the UV tube, caused for instance by cosmic radiation, donot lead to lockout.Times «TSA´», «t3´» and «t4´» only exist with burner controls of the 01 series.13/20Siemens Building TechnologiesCC1N<strong>7451</strong>enHVAC Products 11.06.2003