GRAFIK Eye ® Preset Local Lighting ControlsGRAFIK Eye control units can be connectedto any of the three configurable links.ZONE 2ZONE 4ZONE 6CU WIRE ONLYZONE 1ZONE 3ZONE 5HOTSSACLASS 21 2 3 4USA CLASS 2IEC PELVNEUTRALPin 1 - One 1.0mm (#18 AWG) for common2Pin 2 - Do not connectPins 3 and 4 - One pair 1.0-0.5mm (#18-22 AWG)2twisted/shielded for dataWire to otherWPM/GRX control unitsFigure 5 – connection to processorZONE 2ZONE 4ZONE 6HOTSSACU WIRE ONLYCLASS 21 2 3 4USA CLASS 2IEC PELVZONE 1ZONE 3ZONE 5NEUTRALZONE 2ZONE 4ZONE 6HOTSSACU WIRE ONLYCLASS 21 2 3 4USA CLASS 2IEC PELVZONE 1ZONE 3ZONE 5NEUTRALCOMPONENTSFigure 6 – connection to other GRAFIK Eye control unitsNotes:Connection between #2 terminals is not made between GRAFIKEye control units and the <strong>HomeWorks</strong> ® processor.Connection between #2 terminals is not made between twoGRAFIK Eye control units.A maximum of 8 GRX and WPM may be wired to one processorlink.<strong>Technical</strong> Support: hwisupport@lutron.com4.13