13.07.2015 Views

Cooper B-Line Strut Systems - Dixie Construction Products

Cooper B-Line Strut Systems - Dixie Construction Products

Cooper B-Line Strut Systems - Dixie Construction Products

SHOW MORE
SHOW LESS
  • No tags were found...

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

DESIGN LOAD DATA (For typical channel-fitting connections when USED IN PAIRS).90° FittingsReference DataChannelThickness Lbs. kN Lbs. kN Lbs. kN Lbs. kN Lbs. kN Lbs. kN12 ga. (2.6) 1500 (6.67) 1000 (4.45) 2000 (8.90) 1500 (6.67) 1500 (6.67) 1000 (4.45)14 ga. (1.9) 1000 (4.45) 650 (2.89) 1500 (6.67) 1150 (5.12) 1000 (4.45) 650 (2.89)16 ga. (1.5) 750 (3.34) 500 (2.22) 900 (4.00) 650 (2.89) 1000 (4.45) 500 (2.22)Reference DataDesign load data includes a safety factor of 2.5 (safety factor = ratio of ultimate load to design load).90° Fittings Flat FittingsChannelThickness Lbs. kN Lbs. kN Lbs. kN Lbs. kN Lbs. kN Lbs. kN12 ga. (2.6) 2500 (11.12) 2000 (8.90) 3000 (13.34) 2500 (11.12) 1000 (4.45) 1000 (4.45)14 ga. (1.9) 2000 (8.90) 1650 (7.34) 2000 (8.90) 1650 (7.34) 500 (3.56) 800 (3.56)16 ga. (1.5) 1500 (6.67) 1250 (5.56) 1500 (6.67) 1250 (5.56) 600 (2.67) 600 (2.67)217

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!