On air cooled machines the proper charging procedure is by a calculated weigh inmethod. Charging to a full sight glass on air cooled machines will likely result inover charging as the elbows in the liquid line as well as the liquid line solenoidvalve still produce some flashing even with the correct charge. As fans arecycling the sight glass will also display some bubbling.8.0 Filter DriersASR modules have longer refrigerant pipe runs and higher refrigerant charges.These modules are built with a factory installed liquid line filter drier. The filterdriers are a solid core sweat fitting replaceable type. In the case of a compressormotor burn or water contamination in the system, it is recommended to also installa suction filter drier.9.0 Superheat / SubcoolingAirstack uses a mechanical type expansion valve on all modules. By turning thevalve adjustment clockwise superheat is increased.ASR modules will need to have the superheat set in the field during start up. 10 –12 degrees is also the desired setting.Subcooling is necessary in the system to prevent flash gas as the refrigerant entersthe expansion valve. Airstack condensers are sized so that subcooling of theliquid refrigerant will take place with no separate subcooler being needed. Thegeneral range of subcooling seen is 7- 15 degrees.10.0 Pressure Relief ValveA 400 psig pressure relief valve is standard with all ASR modules The reliefvalve is installed on the receiver and has a 5/8” flare connection.11.0 Annual MaintenanceMost of the annual maintenance requirements for Airstack Chillers involve propershut-down of the machine, and cleaning of the heat exchangers.Preventative Maintenace bulletin #021594PM and Heat Exchanger CleaningProcedures bulletin #091594CP describe the recommended procedures for bothprocesses. Airstack has available the 151A Cleaning Kit to assist with thisprocess. Please see the 151A Cleaning Kit bulletin # 090195CK for more details.All of these bulletins are part of the standard O&M manual package.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!