ENGINEERING RECOMMENDATION G83/1MATERIALS & SAFETY - R&D T R 11 6 4 3 page 4 of 4RECONNECTION TIMESParameter Under/Over voltage Under/Over Frequency Loss of mainsMinimum value 180 seconds 180 seconds 180 secondsActual setting 185 seconds 185 seconds 185 secondsRecorded value >180 seconds >180 seconds >180 secondsSHORT CIRCUIT CURRENT CONTRIBUTIONAs Photovoltaic SSEGs are inverter connected, they are deemed to automatically comply with clause 5.8and no further <strong>test</strong>s are required.COMMENTS<strong>Type</strong> <strong>verification</strong> <strong>test</strong> <strong>sheet</strong> <strong>for</strong> <strong>Fronius</strong> <strong>IG</strong> <strong>TL</strong> <strong>3.0</strong>_TR11643.docBackup: <strong>Fronius</strong> <strong>IG</strong> <strong>TL</strong> UK