Packaged Air Conditioner Installations<strong>Humidifiers</strong> frequently must be <strong>in</strong>stalled <strong>in</strong> packaged centralstation air conditioners. This can present some unusuallocation requirements due to the close quarters with<strong>in</strong> thepackaged units.In the horizontal discharge draw-thru type packaged unitshown <strong>in</strong> Figure 35-1, the recommended location of thehumidifier is at the fan discharge. In some <strong>in</strong>stances thismay not be possible. Note that with the alternate location,the humidifier manifold is <strong>in</strong>stalled to discharge upward <strong>in</strong>tothe area of greatest air turbulence. This permits the air toachieve optimum mix<strong>in</strong>g before reach<strong>in</strong>g the fan blades. Ahigh-limit controller, set at 80%, should be located as shownwhen the humidifier is <strong>in</strong>stalled at the alternate location.Recommended humidifier locations for a vertical dischargedraw-thru type air conditioner (Figure 35-2) are identical to thehorizontal unit. If the alternate location must be used, a high-limitcontroller set at 80% is desirable. The humidifier manifold shoulddischarge upward, as with the horizontal discharge unit.Figure 35-1.Horizontal DischargeWith humidifier <strong>in</strong>stalled at recommended location, high-limit duct controller should beset at 90% RH maximum—alternate location at 80% RH maximum.Figure 35-2.Vertical DischargeDesigns, materials, weights and performance rat<strong>in</strong>gs are approximate and subject to change without notice. Visit armstrong<strong>in</strong>ternational.com for up-to-date <strong>in</strong>formation.<strong>Armstrong</strong> <strong>International</strong> - NAarmstrong<strong>in</strong>ternational.com<strong>Armstrong</strong> <strong>International</strong> - EUarmstrong<strong>in</strong>ternational.eu<strong>Armstrong</strong> <strong>International</strong> - Ch<strong>in</strong>aarmstrong<strong>in</strong>ternational.cn<strong>Armstrong</strong> <strong>International</strong> - Indiaarmstrong<strong>in</strong>ternational.<strong>in</strong><strong>Armstrong</strong> <strong>International</strong>, Koreaarm<strong>in</strong>tl.co.kr35
<strong>Steam</strong> <strong>Humidifiers</strong> <strong>in</strong> <strong>Central</strong> <strong>Systems</strong>, cont<strong>in</strong>ued…In a low pressure blow-thru type, multi-zone, packaged airconditioner (Figure 36-1), the recommendations are much thesame. However, to avoid overload<strong>in</strong>g the cold deck and to avoidimp<strong>in</strong>gement of discharge, the manifold is <strong>in</strong>stalled to dischargeupward <strong>in</strong>stead of directly <strong>in</strong>to the fan discharge.As with the draw-thru units, a high-limit controller set at 90%should be <strong>in</strong>stalled. In a high pressure blow-thru type packagedunit (Figure 36-2), aga<strong>in</strong> the recommended location is as close tothe fan as possible, with the manifold discharg<strong>in</strong>g directly <strong>in</strong>to thefan discharge. A high-limit controller set at 90% is desirable.In either high or low pressure systems, where the humidifieris <strong>in</strong>stalled at the alternate location, set the high-limit humiditycontroller at 80% RH.Figure 36-1.Low pressure systemFigure 36-2.High pressure systemDesigns, materials, weights and performance rat<strong>in</strong>gs are approximate and subject to change without notice. Visit armstrong<strong>in</strong>ternational.com for up-to-date <strong>in</strong>formation.36 <strong>Armstrong</strong> <strong>International</strong> - NAarmstrong<strong>in</strong>ternational.com<strong>Armstrong</strong> <strong>International</strong> - EUarmstrong<strong>in</strong>ternational.eu<strong>Armstrong</strong> <strong>International</strong> - Ch<strong>in</strong>aarmstrong<strong>in</strong>ternational.cn<strong>Armstrong</strong> <strong>International</strong> - Indiaarmstrong<strong>in</strong>ternational.<strong>in</strong><strong>Armstrong</strong> <strong>International</strong>, Koreaarm<strong>in</strong>tl.co.kr