SWITCH: SPST<br />
CONTACT RATINGS:<br />
40 AMP TUNGSTEN 120VAC<br />
40 AMP RESISTIVE<br />
120-277VAC SINGLE PHASE<br />
40 AMP GENERAL PURPOSE<br />
120-277VAC SINGLE PHASE<br />
20 AMP INDUCTIVE<br />
120VAC, 277VAC<br />
SINGLE PHASE<br />
1000VA PILOT DUTY<br />
120-277VAC<br />
2 HP (24 FLA) 120VAC;<br />
5HP (28 FLA) 240VAC<br />
TIMING MOTOR :<br />
120VAC 60Hz<br />
POWER CONSUMPTION :<br />
3 WATTS MAX.<br />
<strong>TORK</strong> <strong>MODEL</strong> <strong>W100</strong><br />
SEVEN DAY CALENDAR DIAL TIME SWITCH<br />
Disconnect power at main panel prior to installing or servicing this time switch or<br />
the equipment connected to it.<br />
Connect in accordance with national and local electrical codes.<br />
Supply Connections: Use gauge specified (AWG # 8-14) suitable for 75 degrees C<br />
(167 degrees F)<br />
INSTALLATION AND OPERATING INSTRUCTIONS<br />
TO SET ON AND OFF TIMES: ON and OFF trippers close and<br />
open all circuits simultaneously. Dial is graduated in one hour intervals.<br />
There must be an ON and an OFF tripper for each day of the<br />
week operations are desired. Place tripper on dial edge as shown in<br />
diagram. Set point of each tripper at the desired operating time.<br />
Hold tripper securely against dial and tighten knurled screw firmly<br />
by hand. (Do not use pliers).<br />
NOTE: Trippers are inter-changeable. With the knurl screw inserted<br />
in the side marked ON, it will become an ON tripper. If the tripper is<br />
turned over and the screw inserted in the side marked OFF, it<br />
becomes an OFF tripper.<br />
Be certain to select the proper day and notice whether the selected time is AM or PM. Minimum ON<br />
time is 1 hour. Minimum OFF time is 2 hours. (There must be at least six hours between any two<br />
OFF trippers).<br />
TO SET DIAL TO TIME: Turn dial COUNTER-CLOCKWISE until correct time of day and day of week<br />
is indicated by time pointer. For ACCURATE OPERATION, care must be used in setting dial to time.<br />
Each notch advances the dial approximately 15 minutes. DO NOT FORCE DIAL BACKWARDS.<br />
TO OMIT A DAY: Remove both ON and OFF trippers from the dial for the day or days to be omitted.<br />
FOR MANUAL OPERATION OF CONTACTS: Press down lever on right of nameplate to close circuit.<br />
Press down lever on left of nameplate to open it.<br />
LI-598(A)<br />
H<br />
N<br />
MOTOR<br />
MOTEUR<br />
<strong>TORK</strong> ®<br />
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542<br />
FAX: 914-664-5052<br />
▲<br />
L 1 X 2<br />
Typical connections for 120VAC<br />
OFF<br />
TRIPPER<br />
ON<br />
TRIPPER<br />
MANUAL<br />
OFF<br />
LEVER<br />
A M<br />
WED<br />
MIDNIGHT<br />
S E T<br />
TUE<br />
NOON<br />
P M A M<br />
OFF<br />
MIDNIGHT<br />
ON<br />
T I<br />
M E<br />
N<br />
9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 11<br />
10 8 6 4 2 12 10 8<br />
➤<br />
P M<br />
LOAD<br />
CHARGE<br />
CARGA<br />
ON<br />
MIDNIGHT<br />
A M<br />
TIME<br />
POINTER<br />
P M<br />
9 7 5 3 1 11 9 7 5<br />
6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4<br />
O<br />
F<br />
F<br />
O<br />
<strong>TORK</strong> N➤<br />
TIME<br />
MANUAL<br />
ON<br />
LEVER
SWITCH: SPDT<br />
CONTACT RATINGS:<br />
40 AMP TUNGSTEN 120VAC<br />
40 AMP RESISTIVE<br />
120-277VAC SINGLE PHASE<br />
40 AMP GENERAL PURPOSE<br />
120-277VAC SINGLE PHASE<br />
20 AMP INDUCTIVE<br />
120VAC, 277VAC<br />
SINGLE PHASE<br />
1000VA PILOT DUTY<br />
120-277VAC<br />
2 HP (24 FLA) 120VAC;<br />
5HP (28 FLA) 240VAC<br />
TIMING MOTOR :<br />
120VAC 60Hz<br />
POWER CONSUMPTION :<br />
3 WATTS MAX.<br />
<strong>TORK</strong> <strong>MODEL</strong> W120<br />
SEVEN DAY CALENDAR DIAL TIME SWITCH<br />
Disconnect power at main panel prior to installing or servicing this time switch or<br />
the equipment connected to it.<br />
Connect in accordance with national and local electrical codes.<br />
Supply Connections: Use gauge specified (AWG # 8-14) suitable for 75 degrees C<br />
(167 degrees F)<br />
INSTALLATION AND OPERATING INSTRUCTIONS<br />
TO SET ON AND OFF TIMES: ON trippers close circuit A. OFF<br />
trippers close circuit B. Dial is graduated in one hour intervals.<br />
There must be an ON and an OFF tripper for each day of the week<br />
operations are desired. Place tripper on dial edge as shown in diagram.<br />
Set point of each tripper at the desired operating time. Hold<br />
tripper securely against dial and tighten knurled screw firmly by<br />
hand. (Do not use pliers).<br />
NOTE: Trippers are inter-changeable. With the knurl screw inserted<br />
in the side marked ON, it will become an ON tripper. If the tripper is<br />
turned over and the screw inserted in the side marked OFF, it<br />
becomes an OFF tripper.<br />
H<br />
N<br />
L 1 X 2<br />
LOAD A<br />
CHARGE A<br />
CARGA A<br />
MOTOR<br />
MOTEUR<br />
OFF<br />
TRIPPER<br />
ON<br />
TRIPPER<br />
TIME<br />
POINTER<br />
Be certain to select the proper day and notice whether the selected time is AM or PM. Minimum ON<br />
time is 1 hour. Minimum OFF time is 2 hours. (There must be at least six hours between any two<br />
OFF trippers).<br />
TO SET DIAL TO TIME: Turn dial COUNTER-CLOCKWISE until correct time of day and day of week<br />
is indicated by time pointer. For ACCURATE OPERATION, care must be used in setting dial to time.<br />
Each notch advances the dial approximately 15 minutes. DO NOT FORCE DIAL BACKWARDS.<br />
TO OMIT A DAY: Remove both ON and OFF trippers from the dial for the day or days to be omitted.<br />
FOR MANUAL OPERATION OF CONTACTS: Press down lever on right of nameplate to close circuit.<br />
Press down lever on left of nameplate to open it.<br />
<strong>TORK</strong> ®<br />
LI-602(A)<br />
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542<br />
FAX: 914-664-5052<br />
▲<br />
▼<br />
MANUAL<br />
OFF<br />
LEVER<br />
A M<br />
WED<br />
MIDNIGHT<br />
S E T<br />
TUE<br />
NOON<br />
P M A M<br />
OFF<br />
MIDNIGHT<br />
ON<br />
T I<br />
M E<br />
N<br />
9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 11<br />
10 8 6 4 2 12 10 8<br />
LOAD B<br />
CHARGE B<br />
CARGA B<br />
➤<br />
P M<br />
ON<br />
MIDNIGHT<br />
A M<br />
P M<br />
9 7 5 3 1 11 9 7 5<br />
6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4<br />
O<br />
F<br />
F<br />
H<br />
N<br />
TIME<br />
O<br />
N<br />
<strong>TORK</strong> ➤<br />
MANUAL<br />
ON<br />
LEVER
SWITCH: DPST<br />
CONTACT RATINGS:<br />
40 AMP TUNGSTEN 120VAC<br />
40 AMP RESISTIVE<br />
120-277VAC SINGLE PHASE<br />
40 AMP GENERAL PURPOSE<br />
120-277VAC SINGLE PHASE<br />
20 AMP INDUCTIVE<br />
120VAC, 277VAC<br />
SINGLE PHASE<br />
1000VA PILOT DUTY<br />
120-277VAC<br />
2 HP (24 FLA) 120VAC;<br />
5HP (28 FLA) 240VAC<br />
TIMING MOTOR :<br />
208-277VAC 60Hz<br />
POWER CONSUMPTION :<br />
3 WATTS MAX.<br />
H<br />
H<br />
<strong>TORK</strong> <strong>MODEL</strong> W202<br />
SEVEN DAY CALENDAR DIAL TIME SWITCH<br />
L<br />
MOTOR<br />
MOTEUR<br />
1 X 2<br />
LOAD<br />
CHARGE<br />
CARGA<br />
Disconnect power at main panel prior to installing or servicing this time switch or<br />
the equipment connected to it.<br />
Connect in accordance with national and local electrical codes.<br />
Supply Connections: Use gauge specified (AWG # 8-14) suitable for 75 degrees C<br />
(167 degrees F)<br />
INSTALLATION AND OPERATING INSTRUCTIONS<br />
TO SET ON AND OFF TIMES: ON and OFF trippers close and<br />
open all circuits simultaneously. Dial is graduated in one hour intervals.<br />
There must be an ON and an OFF tripper for each day of the<br />
week operations are desired. Place tripper on dial edge as shown in<br />
diagram. Set point of each tripper at the desired operating time.<br />
Hold tripper securely against dial and tighten knurled screw firmly<br />
by hand. (Do not use pliers).<br />
NOTE: Trippers are inter-changeable. With the knurl screw inserted<br />
in the side marked ON, it will become an ON tripper. If the tripper is<br />
turned over and the screw inserted in the side marked OFF, it<br />
becomes an OFF tripper.<br />
OFF<br />
TRIPPER<br />
ON<br />
TRIPPER<br />
TIME<br />
POINTER<br />
Be certain to select the proper day and notice whether the selected time is AM or PM. Minimum ON<br />
time is 1 hour. Minimum OFF time is 2 hours. (There must be at least six hours between any two<br />
OFF trippers).<br />
TO SET DIAL TO TIME: Turn dial COUNTER-CLOCKWISE until correct time of day and day of week<br />
is indicated by time pointer. For ACCURATE OPERATION, care must be used in setting dial to time.<br />
Each notch advances the dial approximately 15 minutes. DO NOT FORCE DIAL BACKWARDS.<br />
TO OMIT A DAY: Remove both ON and OFF trippers from the dial for the day or days to be omitted.<br />
FOR MANUAL OPERATION OF CONTACTS: Press down lever on right of nameplate to close circuit.<br />
Press down lever on left of nameplate to open it.<br />
<strong>TORK</strong> ®<br />
LI-599(A)<br />
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542<br />
FAX: 914-664-5052<br />
H<br />
N<br />
MOTOR<br />
MOTEUR<br />
L 1 X 2<br />
MANUAL<br />
OFF<br />
LEVER<br />
A M<br />
WED<br />
MIDNIGHT<br />
S E T<br />
TUE<br />
NOON<br />
P M A M<br />
OFF<br />
MIDNIGHT<br />
ON<br />
T I<br />
M E<br />
N<br />
9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 11<br />
10 8 6 4 2 12 10 8<br />
➤<br />
P M<br />
ON<br />
MIDNIGHT<br />
A M<br />
P M<br />
9 7 5 3 1 11 9 7 5<br />
6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4<br />
O<br />
F<br />
F<br />
CHARGE<br />
CARGA<br />
LOAD LOAD<br />
Typical for 208-240VAC supply. Typical for 277VAC supply.<br />
TIME<br />
O<br />
N<br />
<strong>TORK</strong> ➤<br />
CHARGE<br />
CARGA<br />
MANUAL<br />
ON<br />
LEVER
SWITCH: DPDT<br />
CONTACT RATINGS:<br />
40 AMP TUNGSTEN 120VAC<br />
40 AMP RESISTIVE<br />
120-277VAC SINGLE PHASE<br />
40 AMP GENERAL PURPOSE<br />
120-277VAC SINGLE PHASE<br />
20 AMP INDUCTIVE<br />
120VAC, 277VAC<br />
SINGLE PHASE<br />
1000VA PILOT DUTY<br />
120-277VAC<br />
2 HP (24 FLA) 120VAC;<br />
5HP (28 FLA) 240VAC<br />
TIMING MOTOR :<br />
120VAC 60Hz<br />
POWER CONSUMPTION :<br />
3 WATTS MAX.<br />
<strong>TORK</strong> <strong>MODEL</strong> W220<br />
SEVEN DAY CALENDAR DIAL TIME SWITCH<br />
FRONT<br />
FRENTE<br />
ARRIÉRE<br />
ESPLADA<br />
FRONT<br />
Disconnect power at main panel prior to installing or servicing this time switch or<br />
the equipment connected to it.<br />
Connect in accordance with national and local electrical codes.<br />
Supply Connections: Use gauge specified (AWG # 8-14) suitable for 75 degrees C<br />
(167 degrees F)<br />
INSTALLATION AND OPERATING INSTRUCTIONS<br />
TO SET ON AND OFF TIMES: ON trippers close circuits 1 and 3.<br />
OFF trippers close circuits X and 5. Dial is graduated in one hour<br />
intervals. There must be an ON and an OFF tripper for each day of<br />
the week operations are desired. Place tripper on dial edge as<br />
shown in diagram. Set point of each tripper at the desired operating<br />
time. Hold tripper securely against dial and tighten knurled screw<br />
firmly by hand. (Do not use pliers).<br />
NOTE: Trippers are inter-changeable. With the knurl screw inserted<br />
in the side marked ON, it will become an ON tripper. If the tripper is<br />
turned over and the screw inserted in the side marked OFF, it<br />
becomes an OFF tripper.<br />
OFF<br />
TRIPPER<br />
ON<br />
TRIPPER<br />
TIME<br />
POINTER<br />
Be certain to select the proper day and notice whether the selected time is AM or PM. Minimum ON<br />
time is 1 hour. Minimum OFF time is 2 hours. (There must be at least six hours between any two<br />
OFF trippers).<br />
TO SET DIAL TO TIME: Turn dial COUNTER-CLOCKWISE until correct time of day and day of week<br />
is indicated by time pointer. For ACCURATE OPERATION, care must be used in setting dial to time.<br />
Each notch advances the dial approximately 15 minutes. DO NOT FORCE DIAL BACKWARDS.<br />
TO OMIT A DAY: Remove both ON and OFF trippers from the dial for the day or days to be omitted.<br />
FOR MANUAL OPERATION OF CONTACTS: Press down lever on right of nameplate to close circuit.<br />
Press down lever on left of nameplate to open it.<br />
<strong>TORK</strong> ®<br />
LI-603(A)<br />
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542<br />
FAX: 914-664-5052<br />
H<br />
REAR<br />
N<br />
L<br />
MOTOR<br />
MOTEUR<br />
1 X 2<br />
L 3 5 4<br />
MANUAL<br />
OFF<br />
LEVER<br />
A M<br />
WED<br />
MIDNIGHT<br />
S E T<br />
TUE<br />
NOON<br />
P M A M<br />
OFF<br />
MIDNIGHT<br />
ON<br />
T I<br />
M E<br />
N<br />
9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 11<br />
10 8 6 4 2 12 10 8<br />
➤<br />
LOADS<br />
CHARGE<br />
CARGA<br />
LOADS<br />
CHARGE<br />
CARGA<br />
Typical connections for 120VAC.<br />
P M<br />
ON<br />
MIDNIGHT<br />
A M<br />
P M<br />
9 7 5 3 1 11 9 7 5<br />
6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4<br />
O<br />
F<br />
F<br />
H<br />
N<br />
H<br />
N<br />
TIME<br />
O<br />
N<br />
<strong>TORK</strong> ➤<br />
MANUAL<br />
ON<br />
LEVER
SWITCH: DPDT<br />
CONTACT RATINGS:<br />
40 AMP TUNGSTEN 120VAC<br />
40 AMP RESISTIVE<br />
120-277VAC SINGLE PHASE<br />
40 AMP GENERAL PURPOSE<br />
120-277VAC SINGLE PHASE<br />
20 AMP INDUCTIVE<br />
120VAC, 277VAC<br />
SINGLE PHASE<br />
1000VA PILOT DUTY<br />
120-277VAC<br />
2 HP (24 FLA) 120VAC;<br />
5HP (28 FLA) 240VAC<br />
TIMING MOTOR :<br />
120VAC 60Hz<br />
POWER CONSUMPTION :<br />
3 WATTS MAX.<br />
SYNCHRONOUS POWER WITH RESERVE:<br />
Should your power supply be interrupted, this switch<br />
will continue to operate on time for several hours.<br />
<strong>TORK</strong> <strong>MODEL</strong> W220L<br />
SEVEN DAY CALENDAR DIAL TIME SWITCH<br />
FRONT<br />
FRENTE<br />
ARRIÉRE<br />
ESPLADA<br />
FRONT<br />
Disconnect power at main panel prior to installing or servicing this time switch or the equipment<br />
connected to it.<br />
Connect in accordance with national and local electrical codes.<br />
Supply Connections: Use gauge specified (AWG # 8-14) suitable for 75 degrees C (167 degrees F)<br />
INSTALLATION AND OPERATING INSTRUCTIONS<br />
TO SET ON AND OFF TIMES: ON trippers close circuits 1 and 3.<br />
OFF trippers close circuits X and 5. Dial is graduated in one hour<br />
intervals. There must be an ON and an OFF tripper for each day of<br />
the week operations are desired. Place tripper on dial edge as<br />
shown in diagram. Set point of each tripper at the desired operating<br />
time. Hold tripper securely against dial and tighten knurled screw<br />
firmly by hand. (Do not use pliers).<br />
NOTE: Trippers are inter-changeable. With the knurl screw inserted<br />
in the side marked ON, it will become an ON tripper. If the tripper is<br />
turned over and the screw inserted in the side marked OFF, it<br />
becomes an OFF tripper.<br />
OFF<br />
TRIPPER<br />
ON<br />
TRIPPER<br />
TIME<br />
POINTER<br />
Be certain to select the proper day and notice whether the selected time is AM or PM. Minimum ON<br />
time is 1 hour. Minimum OFF time is 2 hours. (There must be at least six hours between any two<br />
OFF trippers).<br />
TO SET DIAL TO TIME: Turn dial COUNTER-CLOCKWISE until correct time of day and day of week<br />
is indicated by time pointer. For ACCURATE OPERATION, care must be used in setting dial to time.<br />
Each notch advances the dial approximately 15 minutes. DO NOT FORCE DIAL BACKWARDS.<br />
TO OMIT A DAY: Remove both ON and OFF trippers from the dial for the day or days to be omitted.<br />
FOR MANUAL OPERATION OF CONTACTS: Press down lever on right of nameplate to close circuit.<br />
Press down lever on left of nameplate to open it.<br />
<strong>TORK</strong> ®<br />
LI-604(A)<br />
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542<br />
FAX: 914-664-5052<br />
H<br />
REAR<br />
N<br />
L<br />
MOTOR<br />
MOTEUR<br />
1 X 2<br />
L 3 5 4<br />
LOADS<br />
CHARGE<br />
CARGA<br />
Typical connections for 120VAC.<br />
MANUAL<br />
OFF<br />
LEVER<br />
A M<br />
WED<br />
MIDNIGHT<br />
S E T<br />
TUE<br />
NOON<br />
P M A M<br />
OFF<br />
MIDNIGHT<br />
ON<br />
T I<br />
M E<br />
N<br />
9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 11<br />
10 8 6 4 2 12 10 8<br />
➤<br />
LOADS<br />
CHARGE<br />
CARGA<br />
P M<br />
ON<br />
MIDNIGHT<br />
A M<br />
P M<br />
9 7 5 3 1 11 9 7 5<br />
6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4<br />
O<br />
F<br />
F<br />
H<br />
N<br />
H<br />
N<br />
TIME<br />
O<br />
N<br />
<strong>TORK</strong> ➤<br />
MANUAL<br />
ON<br />
LEVER
SWITCH: DPDT<br />
CONTACT RATINGS:<br />
40 AMP TUNGSTEN 120VAC<br />
40 AMP RESISTIVE<br />
120-277VAC SINGLE PHASE<br />
40 AMP GENERAL PURPOSE<br />
120-277VAC SINGLE PHASE<br />
20 AMP INDUCTIVE<br />
120VAC, 277VAC<br />
SINGLE PHASE<br />
1000VA PILOT DUTY<br />
120-277VAC<br />
2 HP (24 FLA) 120VAC;<br />
5HP (28 FLA) 240VAC<br />
TIMING MOTOR :<br />
208-277VAC 60Hz<br />
POWER CONSUMPTION :<br />
3 WATTS MAX.<br />
<strong>TORK</strong> <strong>MODEL</strong> W222<br />
SEVEN DAY CALENDAR DIAL TIME SWITCH<br />
FRONT<br />
FRENTE<br />
Timing<br />
motor<br />
supply<br />
TIMING MOTOR SUPPLY CAN BE TAKEN BY JUMPER<br />
WIRE FROM TERM. L TO 2 (FRONT TERM.) & L TO 4<br />
FROM BACK IF VOLTAGE IS THE SAME.<br />
ARRIÉRE<br />
ESPLADA<br />
FRONT<br />
Disconnect power at main panel prior to installing or servicing this time switch or<br />
the equipment connected to it.<br />
Connect in accordance with national and local electrical codes.<br />
Supply Connections: Use gauge specified (AWG # 8-14) suitable for 75 degrees C<br />
(167 degrees F)<br />
INSTALLATION AND OPERATING INSTRUCTIONS<br />
TO SET ON AND OFF TIMES: ON trippers close circuits 1 and 3.<br />
OFF trippers close circuits X and 5. Dial is graduated in one hour<br />
intervals. There must be an ON and an OFF tripper for each day of<br />
the week operations are desired. Place tripper on dial edge as<br />
shown in diagram. Set point of each tripper at the desired operating<br />
time. Hold tripper securely against dial and tighten knurled screw<br />
firmly by hand. (Do not use pliers).<br />
NOTE: Trippers are inter-changeable. With the knurl screw inserted<br />
in the side marked ON, it will become an ON tripper. If the tripper is<br />
turned over and the screw inserted in the side marked OFF, it<br />
becomes an OFF tripper.<br />
L<br />
L<br />
REAR<br />
MOTOR<br />
M<br />
MOTEUR<br />
L<br />
WATER<br />
HEATER<br />
1 X 2<br />
L 3 5 4<br />
OFF<br />
TRIPPER<br />
ON<br />
TRIPPER<br />
TIME<br />
POINTER<br />
Be certain to select the proper day and notice whether the selected time is AM or PM. Minimum ON<br />
time is 1 hour. Minimum OFF time is 2 hours. (There must be at least six hours between any two<br />
OFF trippers).<br />
TO SET DIAL TO TIME: Turn dial COUNTER-CLOCKWISE until correct time of day and day of week<br />
is indicated by time pointer. For ACCURATE OPERATION, care must be used in setting dial to time.<br />
Each notch advances the dial approximately 15 minutes. DO NOT FORCE DIAL BACKWARDS.<br />
TO OMIT A DAY: Remove both ON and OFF trippers from the dial for the day or days to be omitted.<br />
FOR MANUAL OPERATION OF CONTACTS: Press down lever on right of nameplate to close circuit.<br />
Press down lever on left of nameplate to open it.<br />
<strong>TORK</strong> ®<br />
LI-605(A)<br />
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542<br />
FAX: 914-664-5052<br />
L<br />
SERVICE PANEL<br />
L L<br />
FRONT<br />
FRENTE<br />
ARRIÉRE<br />
ESPLADA<br />
MANUAL<br />
OFF<br />
LEVER<br />
FRONT<br />
A M<br />
H<br />
REAR<br />
N<br />
WED<br />
MIDNIGHT<br />
S E T<br />
TUE<br />
NOON<br />
P M A M<br />
OFF<br />
MIDNIGHT<br />
ON<br />
T I<br />
M E<br />
N<br />
9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 11<br />
10 8 6 4 2 12 10 8<br />
➤<br />
P M<br />
ON<br />
MIDNIGHT<br />
A M<br />
P M<br />
9 7 5 3 1 11 9 7 5<br />
6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4<br />
O<br />
F<br />
F<br />
L<br />
L 3<br />
MOTOR<br />
MOTEUR<br />
1 X 2<br />
3<br />
5<br />
4<br />
LOADS<br />
CHARGE<br />
CARGA<br />
Typical for 207/240VAC supply. Typical for 277VAC supply.<br />
TIME<br />
O<br />
N<br />
<strong>TORK</strong> ➤<br />
4<br />
2<br />
LOADS<br />
CHARGE<br />
CARGA<br />
1<br />
MANUAL<br />
ON<br />
LEVER
SWITCH: 3PST<br />
CONTACT RATINGS:<br />
40 AMP TUNGSTEN 120VAC<br />
40 AMP RESISTIVE<br />
120-277VAC SINGLE PHASE<br />
40 AMP GENERAL PURPOSE<br />
120-277VAC SINGLE PHASE<br />
20 AMP INDUCTIVE<br />
120VAC, 277VAC<br />
SINGLE PHASE<br />
1000VA PILOT DUTY<br />
120-277VAC<br />
2 HP (24 FLA) 120VAC;<br />
5HP (28 FLA) 240VAC<br />
TIMING MOTOR :<br />
120VAC 60Hz<br />
POWER CONSUMPTION :<br />
3 WATTS MAX.<br />
<strong>TORK</strong> <strong>MODEL</strong> W300<br />
SEVEN DAY CALENDAR DIAL TIME SWITCH<br />
Disconnect power at main panel prior to installing or servicing this time switch or<br />
the equipment connected to it.<br />
Connect in accordance with national and local electrical codes.<br />
Supply Connections: Use gauge specified (AWG # 8-14) suitable for 75 degrees C<br />
(167 degrees F)<br />
INSTALLATION AND OPERATING INSTRUCTIONS<br />
TO SET ON AND OFF TIMES: ON and OFF trippers close and<br />
open all circuits simultaneously. Dial is graduated in one hour intervals.<br />
There must be an ON and an OFF tripper for each day of the<br />
week operations are desired. Place tripper on dial edge as shown in<br />
diagram. Set point of each tripper at the desired operating time.<br />
Hold tripper securely against dial and tighten knurled screw firmly<br />
by hand. (Do not use pliers).<br />
NOTE: Trippers are inter-changeable. With the knurl screw inserted<br />
in the side marked ON, it will become an ON tripper. If the tripper is<br />
turned over and the screw inserted in the side marked OFF, it<br />
becomes an OFF tripper.<br />
Be certain to select the proper day and notice whether the selected time is AM or PM. Minimum ON<br />
time is 1 hour. Minimum OFF time is 2 hours. (There must be at least six hours between any two<br />
OFF trippers).<br />
TO SET DIAL TO TIME: Turn dial COUNTER-CLOCKWISE until correct time of day and day of week<br />
is indicated by time pointer. For ACCURATE OPERATION, care must be used in setting dial to time.<br />
Each notch advances the dial approximately 15 minutes. DO NOT FORCE DIAL BACKWARDS.<br />
TO OMIT A DAY: Remove both ON and OFF trippers from the dial for the day or days to be omitted.<br />
FOR MANUAL OPERATION OF CONTACTS: Press down lever on right of nameplate to close circuit.<br />
Press down lever on left of nameplate to open it.<br />
LI-600(A)<br />
FRONT<br />
FRENTE<br />
MILIEU<br />
MEDIO<br />
ARRIÉRE<br />
ESPLADA<br />
FRONT<br />
L<br />
L<br />
L<br />
N<br />
L<br />
MIDDLE<br />
REAR<br />
MOTOR<br />
MOTEUR<br />
▲<br />
1 X<br />
▲<br />
3<br />
▲<br />
5<br />
LOADS<br />
CHARGE<br />
CARGA<br />
For use with 3 phase 4-wire 120/208VAC systems.<br />
OFF<br />
TRIPPER<br />
ON<br />
TRIPPER<br />
TIME<br />
POINTER<br />
<strong>TORK</strong> ®<br />
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542<br />
FAX: 914-664-5052<br />
2<br />
4<br />
6<br />
MANUAL<br />
OFF<br />
LEVER<br />
A M<br />
WED<br />
MIDNIGHT<br />
S E T<br />
TUE<br />
NOON<br />
P M A M<br />
OFF<br />
MIDNIGHT<br />
ON<br />
T I<br />
M E<br />
N<br />
9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 11<br />
10 8 6 4 2 12 10 8<br />
➤<br />
P M<br />
ON<br />
MIDNIGHT<br />
A M<br />
P M<br />
9 7 5 3 1 11 9 7 5<br />
6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4<br />
O<br />
F<br />
F<br />
TIME<br />
O<br />
N<br />
<strong>TORK</strong> ➤<br />
MANUAL<br />
ON<br />
LEVER
SWITCH: 3PST<br />
CONTACT RATINGS:<br />
40 AMP TUNGSTEN 120VAC<br />
40 AMP RESISTIVE<br />
120-277VAC SINGLE PHASE<br />
40 AMP GENERAL PURPOSE<br />
120-277VAC SINGLE PHASE<br />
20 AMP INDUCTIVE<br />
120VAC, 277VAC<br />
SINGLE PHASE<br />
1000VA PILOT DUTY<br />
120-277VAC<br />
2 HP (24 FLA) 120VAC;<br />
5HP (28 FLA) 240VAC<br />
TIMING MOTOR :<br />
208-277VAC 60Hz<br />
POWER CONSUMPTION :<br />
3 WATTS MAX.<br />
<strong>TORK</strong> <strong>MODEL</strong> W302<br />
SEVEN DAY CALENDAR DIAL TIME SWITCH<br />
Disconnect power at main panel prior to installing or servicing this time switch or<br />
the equipment connected to it.<br />
Connect in accordance with national and local electrical codes.<br />
Supply Connections: Use gauge specified (AWG # 8-14) suitable for 75 degrees C<br />
(167 degrees F)<br />
INSTALLATION AND OPERATING INSTRUCTIONS<br />
TO SET ON AND OFF TIMES: ON and OFF trippers close and<br />
open all circuits simultaneously. Dial is graduated in one hour intervals.<br />
There must be an ON and an OFF tripper for each day of the<br />
week operations are desired. Place tripper on dial edge as shown in<br />
diagram. Set point of each tripper at the desired operating time.<br />
Hold tripper securely against dial and tighten knurled screw firmly<br />
by hand. (Do not use pliers).<br />
NOTE: Trippers are inter-changeable. With the knurl screw inserted<br />
in the side marked ON, it will become an ON tripper. If the tripper is<br />
turned over and the screw inserted in the side marked OFF, it<br />
becomes an OFF tripper.<br />
Be certain to select the proper day and notice whether the selected time is AM or PM. Minimum ON<br />
time is 1 hour. Minimum OFF time is 2 hours. (There must be at least six hours between any two<br />
OFF trippers).<br />
TO SET DIAL TO TIME: Turn dial COUNTER-CLOCKWISE until correct time of day and day of week<br />
is indicated by time pointer. For ACCURATE OPERATION, care must be used in setting dial to time.<br />
Each notch advances the dial approximately 15 minutes. DO NOT FORCE DIAL BACKWARDS.<br />
TO OMIT A DAY: Remove both ON and OFF trippers from the dial for the day or days to be omitted.<br />
FOR MANUAL OPERATION OF CONTACTS: Press down lever on right of nameplate to close circuit.<br />
Press down lever on left of nameplate to open it.<br />
LI-601(A)<br />
FRONT<br />
FRENTE<br />
FRONT L 1 X<br />
MILIEU<br />
MEDIO<br />
ARRIÉRE<br />
ESPLADA<br />
L<br />
M<br />
▲<br />
▲<br />
MIDDLE 3<br />
L<br />
L<br />
N<br />
MOTOR<br />
MOTEUR<br />
▲<br />
REAR 5<br />
2<br />
4<br />
6<br />
LOADS<br />
CHARGE<br />
CARGA<br />
For use with 3 phase 4-wire 120/208V systems.<br />
FRONT<br />
FRENTE<br />
OFF<br />
TRIPPER<br />
ON<br />
TRIPPER<br />
MANUAL<br />
OFF<br />
LEVER<br />
TIME<br />
POINTER<br />
<strong>TORK</strong> ®<br />
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542<br />
FAX: 914-664-5052<br />
MILIEU<br />
MEDIO<br />
FRONT L 1 X<br />
H<br />
N<br />
A M<br />
WED<br />
MIDNIGHT<br />
S E T<br />
TUE<br />
NOON<br />
P M A M<br />
OFF<br />
MIDNIGHT<br />
ON<br />
T I<br />
M E<br />
N<br />
9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 1 11 9 7 5 3 11<br />
10 8 6 4 2 12 10 8<br />
➤<br />
M<br />
▲<br />
▲<br />
MIDDLE 3<br />
▲<br />
REAR 5<br />
ARRIÉRE<br />
ESPLADA<br />
MOTOR<br />
MOTEUR<br />
P M<br />
ON<br />
MIDNIGHT<br />
A M<br />
P M<br />
9 7 5 3 1 11 9 7 5<br />
6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4 2 12 10 8 6 4<br />
O<br />
F<br />
F<br />
2<br />
4<br />
6<br />
LOADS<br />
CHARGE<br />
CARGA<br />
Typical connections for 277VAC supply.<br />
TIME<br />
O<br />
N<br />
<strong>TORK</strong> ➤<br />
MANUAL<br />
ON<br />
LEVER