Electrical Control Valves Series EX4, EX5, EX6, EX7, EX8<br />

Technical Data<br />

Compatibility * HCFCs, HFCs, mineral Protection accordance to EX4/EX5/EX6/EX7: IP68 with <strong>Alco</strong><br />

MOPD (maximum operating EX4/EX5/EX6/EX7: 35 bar<br />

and POE lubricants IEC 529, DIN 40050 supplied cable connector assembly<br />

pressure differential) EX8: 25 bar Vibration for non-connec- 4 g<br />

EX8: IP65 with DIN plug<br />

Max. working pressure, PS EX4/EX5/EX6/EX7: 45 bar ted and fastened valve (0 to 1000 Hz, 1 octave /min.)<br />

Medium temperature range<br />

EX8: 35 bar Shock 20g at 11 ms<br />

80g at 1 ms<br />

Uni-flow version TS: -50 ... +100°C Net weight 0.5kg (EX4), 0.52 kg (EX5), 0.60 kg (EX6)<br />

Bi-flow version TS: -40 ... +80°C 1.8 kg (EX7), 2.5 kg (EX8)<br />

Ambient temperature -40 ... +55°C Full travel time EX4/EX5/EX6: 1.5 seconds<br />

CE marking EX4/EX5 not required EX7: 3.2 seconds, EX8: 5.2 seconds<br />

Salt spray test<br />

EX6/EX7/EX8 required, Cat I, Module A Seat leakage Positive shut-off better than solenoid valve<br />

non-corrosion stainless steel body<br />

Humidity 5 to 95% R.H. External leakage ≤ 3 gram / year<br />

Connections Package and delivery EX4/EX5/EX6/EX7: without electrical<br />

EX4/EX5/EX6/EX7 ODF stainless steel fittings (individual) connector<br />

EX8 plated Rotalock ODF fittings EX8: with DIN plug and a pair of<br />

*) Valves are not released for use with inflammable refrigerants.<br />

rotalock connections<br />

Block Diagrams<br />

Superheat Control with EC3-X33 (see page 34) Refrigerant Mass Flow Control with EXD-U (see page 35)<br />

optional display unit ECD-002<br />

1 ECN-N60 sensor<br />

4 PT4 pressure transmitter<br />

6 Supply / Digital Input<br />

9 Alarm out<br />

11 EX4..EX8 valve<br />

12 Suction pressure 4..20mA out<br />

13 ECD-002 Display unit<br />