Electronic Smart Starter ESC-255 / ESC-325<br />
The electronic Smart Starter ESC-255 / ESC-325<br />
is used for switching, protection and starting<br />
current limitation of single phase compressors in<br />
refrigeration and air-conditioning applications<br />
Features<br />
• For motors with up to 25A / 32A max. operating<br />
current<br />
• Limitation of starting current to less than 45A<br />
• Self adjusting to motor current - no manual<br />
adjustment or calibration necessary<br />
• Many motor protection functions:<br />
-Low voltage shut down<br />
-Locked rotor recognition and shutdown<br />
-Delay function to limit number of motor starts<br />
per hour<br />
• Self diagnostics<br />
• Indicator LED<br />
• Thyristor protected contactor for long life<br />
• No extra motor contactor needed<br />
• Easy Installation<br />
ESC-255<br />
Standards:<br />
• per Low Voltage Directive<br />
(EN 60947-1/EN 60947-5-1)<br />
• EN 60947-4-2 Contactors and motor starters - AC<br />
semiconductor motor controllers and starters<br />
Flicker (EN 61000-3-3 / IEC-1000-3-11)<br />
• Safety and environmental requirements for<br />
refrigeration systems and heat pumps (EN 378)<br />
Selection Chart ESC<br />
Type Part No. Max. compressor running current<br />
Smart Starter ESC-255 805 175 25A<br />
Smart Starter ESC-325 805 176 32A<br />
including mounting clip, plug, connectors, operating instructions<br />
Technical Data<br />
Operating voltage<br />
Compressor starting current<br />
Operating temperature<br />
Storage temperature<br />
Start capacitor<br />
230 V 50 Hz nominal<br />
limited to max. 45A<br />
-20 ... +65°C non condensing<br />
-40 ... +85°C non condensing<br />
200 ... 240 uF<br />
Weight<br />
400 g<br />
Protection acc. IEC 529 IP 20<br />
Max. vibration<br />
4 g (at 10 … 1000 Hz)<br />
Time delay after stop<br />
3 min<br />
Wiring Diagram<br />
Start Current vs Time<br />
(a) Motor without current limitation<br />
(b) Large motor with ESC Smart Starter<br />
(c) Small motor with ESC Smart Starter<br />
ESC Contacts:<br />
R = Output motor run winding<br />
RC = Output run capacitor<br />
L1 = 230V / 50Hz power input<br />
S = Sensor line to start winding<br />
ON = Start input<br />
(ON if connected to 230V)<br />
N = Neutral line<br />
50 A2.5.1/0706/E