Available upon special request<br />

• Power assembly with solder connection for<br />

external pressure equalization<br />

• Non-standard connection sizes see page 80.<br />

Accessories<br />

Type<br />

Part No.<br />

Gasket Set for L Series Valves X 13455 -1 027 579<br />

Service Tool for L Series X 99999 800 005<br />

Steel screws for following flange types:<br />

C501 , 9761 , 6346 , A576 Screw ST 32 803 573<br />

9152, 9153, 10331 , 10332 Screw ST 48 803 574<br />

Correction Tables for Series L<br />

Valve selection for desuperheating of<br />

suction gas:<br />

The required desuperheating capacity Q des<br />

has to be<br />

multiplied with the correction factors on page 68.<br />

Valve selection for desuperheating of suction gas<br />

in conjunction with hotgas-bypass regulation:<br />

The required bypass capacity Q Byp<br />

has to be multiplied<br />

with correction factor K ti<br />

per table below.<br />

Q des<br />

x K t<br />

x K∆p = Q n<br />

Q des<br />

: Required desuperheating capacity<br />

K t<br />

: Correction factor for evaporating and<br />

liquid temperature<br />

K∆p : Correction factor for pressure drop at valve<br />

Q n<br />

: Nominal valve capacity<br />

Q Byp<br />

x K ti<br />

= Q n<br />

Q Byp<br />

: Required bypass capacity<br />

K ti<br />

: Correction factor for evaporating<br />

temperature<br />

Q n<br />

: Nominal valve capacity<br />

Condensing Temperature Refrigerant<br />

Correction Factor K ti<br />

Bubble point Evaporating Temperature °C<br />

°C +10 +5 0 -10 -20 -30 -40 -50<br />

R 22 0,33 0,36 0,40 0,47 0,56 0,66 0,78 0,93<br />

+50 R 407 C 0,41 0,45 0,49 0,58 0,69<br />

(R 407C: +54 dew point) R 134a 0,38 0,42 0,44 0,54 0,64<br />

R 507 / R 404A 0,50 0,54 0,59 0,70 0,83 0,98 1,18 1,38<br />

R 22 0,26 0,29 0,32 0,38 0,46 0,55 0,66 0,78<br />

+40 R 407 C 0,32 0,35 0,39 0,46 0,55<br />

(R 407C: +45 dew point) R 134a 0,31 0,33 0,36 0,44 0,52<br />

R 507 / R 404A 0,38 0,42 0,45 0,54 0,64 0,76 0,90 1,08<br />

R 22 0,20 0,22 0,25 0,31 0,38 0,46 0,55 0,66<br />

+30 R 407 C 0,25 0,28 0,31 0,37 0,45<br />

(R 407C: +35 dew point) R 134a 0,24 0,26 0,29 0,35 0,43<br />

R 507 / R 404A 0,29 0,32 0,35 0,42 0,51 0,60 0,72 0,86<br />

R 22 0,15 0,17 0,19 0,25 0,31 0,38 0,46 0,56<br />

+20 R 407 C 0,19 0,21 0,24 0,30 0,37<br />

(R 407C: +26 dew point) R 134a 0,18 0,20 0,22 0,28 0,35<br />

R 507 / R 404A 0,22 0,25 0,27 0,33 0,40 0,48 0,58 0,70<br />

Correction factors based on 20K superheat suction gas at the<br />

inlet of compressor, discharge temperature 28K above isentropic<br />

compression and 1K subcooling.<br />

A2.5.1/0706/E<br />