PANELBOARD 'DPLS'<br />

(NEW)<br />

SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: MLO TYPE: LIGHTING / APPLIANCE<br />

BUS AMPACITY: 200 AMPERES A.I.C. RATING: 65,000A MOUNTING: SURFACE<br />

NEUTRAL BUS AMPACITY: 200 AMPERES BRANCH: LIFE SAFETY ENCLOSURE: NEMA 1<br />

CKT. LOAD (KVA) WIRE DEVICE DEVICE WIRE LOAD (KVA) CKT.<br />

NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.<br />

1 EGRESS LTG. 0.8 12 12 2 1 20 20 1 2 12 12 0.5 FACP 2<br />

3 EGRESS LTG. 1.3 12 12 2 1 20 20 1 2 12 12 0.1 SPRINKLER BELL 4<br />

5 EGRESS LTG. 1.0 12 12 2 1 20 20 1 SPARE 6<br />

7 SPARE 1 20 20 1 SPARE 8<br />

9 SPARE 1 20 20 1 SPARE 10<br />

11 SPARE 1 20 20 1 SPARE 12<br />

13 SPARE 1 20 100 3 FUTURE, PANEL "3LS" 14<br />

15 SPARE 1 20<br />

17 SPACE ONLY<br />

19 SPACE ONLY SPACE ONLY 20<br />

21 SPACE ONLY SPACE ONLY 22<br />

23 SPACE ONLY SPACE ONLY 24<br />

25 SPACE ONLY SPACE ONLY 26<br />

27 SPACE ONLY SPACE ONLY 28<br />

29 SPACE ONLY SPACE ONLY 30<br />

31 SPACE ONLY SPACE ONLY 32<br />

33 SPACE ONLY SPACE ONLY 34<br />

35 SPACE ONLY SPACE ONLY 36<br />

37 SPACE ONLY SPACE ONLY 38<br />

39 SPACE ONLY SPACE ONLY 40<br />

41 SPACE ONLY SPACE ONLY 42<br />

NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY<br />

1. WITH EQUIPMENT GROUND BUS. A = 1.3 KVA 3.1 KVA LIGHTING (INTERIOR AND EXTERIOR)<br />

2. - B = 1.4 KVA 0.0 KVA RECEPTACLES (GENERAL PURPOSE)<br />

3. - C = 1.0 KVA 0.0 KVA RECEPTACLES (EQUIPMENT)<br />

4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)<br />

5. - PHASE B: 12 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)<br />

6. - TOTAL CONNECTED LOAD 0.6 KVA MISCELLANEOUS<br />

7. - 10 AMPERES 3.7 KVA TOTAL CONNECTED LOAD<br />

PANELBOARD '1Q1'<br />

(NEW)<br />

SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: MLO TYPE: LIGHTING / APPLIANCE<br />

BUS AMPACITY: 225 AMPERES A.I.C. RATING: 22,000 AMPERES MOUNTING: SURFACE<br />

NEUTRAL BUS AMPACITY: 225 AMPERES BRANCH: EQUIPMENT ENCLOSURE: NEMA 1<br />

CKT. LOAD (KVA) WIRE DEVICE DEVICE WIRE LOAD (KVA) CKT.<br />

NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.<br />

1 TERMINAL BOXES 1.0 12 12 2 1 20 15 3 2 0.9 0.9 0.9 EF-1 2<br />

3 TERMINAL BOXES 1.0 12 12 2 1 20<br />

5 TERMINAL BOXES 1.0 12 12 2 1 20<br />

7 TERMINAL BOXES 1.0 12 12 2 1 20 15 3 2 0.8 0.8 0.8 CHWP-1 8<br />

9 TERMINAL BOXES 1.0 12 12 2 1 20<br />

11 TERMINAL BOXES 1.0 12 12 2 1 20<br />

13 TERMINAL BOXES 1.0 12 12 2 1 20 15 3 2 0.8 0.8 0.8 CHWP-2 14<br />

15 TERMINAL BOXES 1.0 12 12 2 1 20<br />

17 ELEVATOR CONTROL - P3 1.0 2 1 20<br />

19 ELEVATOR CONTROL - P4 1.0 2 1 20 15 3 2 0.6 0.6 0.6 CP - 1 20<br />

21 ELEVATOR CONTROL - S1 1.0 2 1 20<br />

23 HUMIDIFIER - H1 0.1 2 1 20<br />

25 ELEVATOR CONTROL - S2 1.0 2 1 20 15 3 2 1.1 1.1 1.1 HTP - 1 26<br />

27 RCP-1 0.3 2 1 20<br />

29 SP-1 1.1 2 1 20<br />

31 SP-2 1.1 2 1 20 15 2 2 0.8 0.8 SSCU-1 32<br />

33 EF-2 0.7 2 1 20<br />

35 BAS 0.5 2 1 20 20 1 SPARE 36<br />

37 SPARE FOR MECHANICAL USE 1.0 12 12 2 1 20 20 1 SPARE 38<br />

39 SPARE FOR MECHANICAL USE 1.0 12 12 2 1 20 20 1 SPARE 40<br />

41 SPARE FOR MECHANICAL USE 1.0 12 12 2 1 20 20 1 SPARE 42<br />

NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY<br />

1. WITH EQUIPMENT GROUND BUS. A = 12.1 KVA 0.0 KVA LIGHTING (INTERIOR AND EXTERIOR)<br />

2. SEE EQUIPMENT CONNECTION <strong>SCHEDULE</strong> FOR CONDUCTOR, RACEWAY SIZES. B = 11.0 KVA 0.0 KVA RECEPTACLES (GENERAL PURPOSE)<br />

3. - C = 9.9 KVA 8.1 KVA RECEPTACLES (EQUIPMENT)<br />

4. - HIGHEST CONNECTED PHASE(S) 17.4 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)<br />

5. - PHASE A: 101 AMPERES 4.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)<br />

6. - TOTAL CONNECTED LOAD 3.5 KVA MISCELLANEOUS<br />

7. - 92 AMPERES 33.0 KVA TOTAL CONNECTED LOAD<br />

SWITCHBOARD 'QSB'<br />

(NEW)<br />

SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: MLO TYPE: SWITCHBOARD<br />

BUS AMPACITY: 2000 AMPERES A.I.C. RATING: 65,000 AMPERES MOUNTING: FLOOR<br />

NEUTRAL BUS AMPACITY: 2000 AMPERES BRANCH: EQUIPMENT ENCLOSURE: NEMA 1<br />

UNIT<br />

DEVICE FEEDER/ BRANCH CIRCUIT LOAD (KVA)<br />

NO. NAMEPLATE POLE FRAME(A) TRIP(A) # SIZE GND CONDUIT TOTAL PH. A PH. B PH. C NOTES ADDITIONAL COMMENTS<br />

1 PANEL '1Q1' 3 225 150 33.0 12.1 11.0 9.9 2<br />

2 AHU-1R 3 100 70 11.1 3.7 3.7 3.7 3<br />

3 AHU-1S 3 225 175 27.0 9.0 9.0 9.0 3<br />

4 SPARE, FUTURE PANEL 3 225 225<br />

5 SPARE, FUTURE PANEL 3 225 225<br />

6 SPARE, FUTURE PANEL 3 225 225<br />

7 SPARE, FUTURE PANEL 3 225 225<br />

8 SPARE, FUTURE PANEL 3 225 225<br />

9 SPARE, FUTURE PANEL 3 225 225<br />

10 SPARE, FUTURE PANEL 3 225 225<br />

11 SPARE 3 225 225<br />

12 SPARE 3 225 225<br />

13 SPARE 3 100 100<br />

14 SPARE 3 100 100<br />

15 ELEVATOR - P3 3 200 200 48.9 16.3 16.3 16.3 3<br />

16 ELEVATOR - P4 3 200 200 48.9 16.3 16.3 16.3 3<br />

17 ELEVATOR - S1 3 400 400 97.2 32.4 32.4 32.4 3<br />

18 ELEVATOR - S2 3 400 400 97.2 32.4 32.4 32.4 3<br />

NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY<br />

1. WITH EQUIPMENT GROUND BUS. A = 122.2 KVA 0.0 KVA LIGHTING (INTERIOR AND EXTERIOR)<br />

2. SEE POWER RISER DIAGRAM FOR CONDUCTOR, RACEWAY SIZES. B = 121.1 KVA 0.0 KVA RECEPTACLES (GENERAL PURPOSE)<br />

3. SEE EQUIPMENT CONNECTION <strong>SCHEDULE</strong> FOR CONDUCTOR, RACEWAY SIZES. C = 120.0 KVA 8.1 KVA RECEPTACLES (EQUIPMENT)<br />

4. - HIGHEST CONNECTED PHASE(S) 55.5 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)<br />

5. - PHASE A: 1019 AMPERES 296.2 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)<br />

6. - TOTAL CONNECTED LOAD 3.5 KVA MISCELLANEOUS<br />

7. - 1009 AMPERES 363.3 KVA TOTAL CONNECTED LOAD<br />

PANELBOARD '1C1'<br />

(NEW)<br />

SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: TYPE: LIGHTING / APPLIANCE<br />

BUS AMPACITY: 225 AMPERES A.I.C. RATING: 22,000A MOUNTING: SURFACE<br />

NEUTRAL BUS AMPACITY: 225 AMPERES BRANCH: CRITICAL ENCLOSURE: NEMA 1<br />

CKT. LOAD (KVA) WIRE DEVICE DEVICE WIRE LOAD (KVA) CKT.<br />

NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.<br />

1 LTG: A172, A173, A174 0.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: 2<br />

3 LTG: AC102-104,AC107,AC106,AC111 1.9 12 12 2 1 20 20 1 2 12 12 0.7 REC: 4<br />

5 LTG: A171,A170,AS101,A103,A105,A107 1.4 12 12 2 1 20 20 1 2 12 12 0.7 REC: 6<br />

7 LTG: A102,4,6,A155-163,A150-153 1.6 12 12 2 1 20 20 1 2 12 12 0.7 REC: 8<br />

9 LTG: A120,A,B,C,A141,A142,A144,A,B 1.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: 10<br />

11 LTG: A121,A123,A125,A127,A129 1.4 12 12 2 1 20 20 1 2 12 12 0.7 REC: 12<br />

13 LTG: A108,A110,A112,A114,A116,A118 1.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: 14<br />

15 LTG: A131,A133,A134,A122,A124,A126 1.6 12 12 2 1 20 20 1 2 12 12 0.7 REC: 16<br />

17 LTG: AC001 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: 18<br />

19 LTG: EXTERIOR 0.6 12 12 2 1 20 20 1 2 12 12 0.4 REC: 20<br />

21 LTG: A100 0.3 12 12 2 1 20 20 1 2 12 12 0.3 INTERCOM 22<br />

23 MOTORIZED DOOR 1.1 12 12 2 1 20 20 1 SPARE 24<br />

25 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.4 REC: 26<br />

27 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.4 REC: 28<br />

29 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: REFRIGERATOR 30<br />

31 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: 32<br />

33 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: 34<br />

35 SECURITY CAMERA PWR SUPPLY 0.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: 36<br />

37 REC: A141 0.7 12 12 2 1 20 20 1 2 12 12 0.7 REC: 38<br />

39 REC: A120B 0.4 12 12 2 1 20 20 1 2 12 12 0.4 REC: 40<br />

41 REC: A120C 0.7 12 12 2 1 20 20 1 2 12 12 0.7 REC: 42<br />

NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY<br />

1. WITH EQUIPMENT GROUND BUS. A = 12.3 KVA 13.3 KVA LIGHTING (INTERIOR AND EXTERIOR)<br />

2. - B = 12.5 KVA 13.3 KVA RECEPTACLES (GENERAL PURPOSE)<br />

3. - C = 11.4 KVA 2.7 KVA RECEPTACLES (EQUIPMENT)<br />

4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)<br />

5. - PHASE B: 105 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)<br />

6. - TOTAL CONNECTED LOAD 6.9 KVA MISCELLANEOUS<br />

7. - 101 AMPERES 36.2 KVA TOTAL CONNECTED LOAD<br />

PANELBOARD '1C1' (NEW) SECTION 2<br />

CKT. LOAD (KVA) WIRE DEVICE DEVICE WIRE LOAD (KVA) CKT.<br />

NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.<br />

43 SPARE 1 20 20 1 2 12 12 1.0 REC: PYXIS 44<br />

45 SPARE 1 20 20 1 2 12 12 1.0 REC: PYXIS 46<br />

47 SPARE 1 20 20 1 SPARE 48<br />

49 SPARE 1 20 20 1 SPARE 50<br />

51 SPARE 1 20 20 1 SPARE 52<br />

53 SPARE 1 20 20 1 SPARE 54<br />

55 SPARE 1 20 20 1 SPARE 56<br />

57 SPARE 1 20 20 1 SPARE 58<br />

59 SPARE 1 20 20 1 SPARE 60<br />

61 SPARE 1 20 20 1 SPARE 62<br />

63 SPARE 1 20 20 1 SPARE 64<br />

65 SPARE 1 20 20 1 SPARE 66<br />

67 SPARE 1 20 20 1 SPARE 68<br />

69 SPARE 1 20 20 1 SPARE 70<br />

71 SPARE 1 20 20 1 SPARE 72<br />

73 SPARE 1 20 20 1 SPARE 74<br />

75 SPARE 1 20 20 1 SPARE 76<br />

77 SPARE 1 20 20 1 SPARE 78<br />

79 SPARE 1 20 20 1 SPARE 80<br />

81 SPARE 1 20 20 1 SPARE 82<br />

83 SPARE 1 20<br />

PANELBOARD 'DPC'<br />

(NEW)<br />

SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: TYPE: LIGHTING / APPLIANCE<br />

BUS AMPACITY: 1000 AMPERES A.I.C. RATING: 65,000A MOUNTING: SURFACE<br />

NEUTRAL BUS AMPACITY: 1000 AMPERES BRANCH: NORMAL ENCLOSURE: NEMA 1<br />

CKT. LOAD (KVA) WIRE DEVICE DEVICE WIRE LOAD (KVA) CKT.<br />

NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.<br />

1 PANEL '1C1' 12.3 12.5 11.4 2 3 225 225 3 SPARE, FUTURE PANEL 2<br />

7 SPARE, FUTURE PANEL 3 225 225 3 SPARE, FUTURE PANEL 8<br />

13 SPARE, FUTURE PANEL 3 225 225 3 SPARE, FUTURE PANEL 14<br />

19 SPARE, FUTURE PANEL 3 225 225 3 SPARE, FUTURE PANEL 20<br />

25 SPARE 3 100 225 3 SPARE 26<br />

31 SPARE 3 100 225 3 SPARE 32<br />

37 SPARE 1 20 20 1 SPARE 38<br />

39 SPARE 1 20 20 1 SPARE 40<br />

41 SPARE 1 20 20 1 SPARE 42<br />

NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY<br />

1. WITH EQUIPMENT GROUND BUS. A = 12.3 KVA 13.3 KVA LIGHTING (INTERIOR AND EXTERIOR)<br />

2. SEE POWER RISER DIAGRAM FOR CONDUCTOR, RACEWAY SIZES. B = 12.5 KVA 13.3 KVA RECEPTACLES (GENERAL PURPOSE)<br />

3. - C = 11.4 KVA 2.7 KVA RECEPTACLES (EQUIPMENT)<br />

4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)<br />

5. - PHASE B: 105 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)<br />

6. - TOTAL CONNECTED LOAD 6.9 KVA MISCELLANEOUS<br />

7. - 101 AMPERES 36.2 KVA TOTAL CONNECTED LOAD<br />

PANELBOARD '1N1' (NEW) SECTION 1<br />

SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: TYPE: LIGHTING / APPLIANCE<br />

BUS AMPACITY: 225 AMPERES A.I.C. RATING: 22,000A MOUNTING: SURFACE<br />

NEUTRAL BUS AMPACITY: 225 AMPERES BRANCH: NORMAL ENCLOSURE: NEMA 1<br />

CKT. LOAD (KVA) WIRE DEVICE DEVICE WIRE LOAD (KVA) CKT.<br />

NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.<br />

1 LTG: A172, A173, A174 0.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: EWC 2<br />

3 LTG: AC101,AC111,AC175,AC106,AC107 1.1 12 12 2 1 20 20 1 2 12 12 0.9 REC: 4<br />

5 LTG: A171,A170,AS101,A103,A105,A107 1.4 12 12 2 1 20 20 1 2 12 12 1.3 REC: 6<br />

7 LTG: A102,A104,A106,A155-163 1.6 12 12 2 1 20 20 1 2 12 12 1.1 REC: 8<br />

9 LTG: AC102,A117,AC103,AC105,AC105 1.0 12 12 2 1 20 20 1 2 12 12 1.3 REC: 10<br />

11 LTG: AC102, DIMMING AND DAY 1.5 12 12 2 1 20 20 1 2 12 12 0.9 REC: 12<br />

13 LTG: AC103, DIMMING & DAY,A123,A12 1.7 12 12 2 1 20 20 1 2 12 12 0.9 REC: 14<br />

15 LTG: A001 AND ELEV PIT 0.3 12 12 2 1 20 20 1 2 12 12 1.1 REC: 16<br />

17 LTG: EXTERIOR 12 12 2 1 20 20 1 2 12 12 0.7 REC: 18<br />

19 REC: AC001, A001 0.5 12 12 2 1 20 20 1 2 12 12 1.4 REC: 20<br />

21 BOLLARDS 0.5 10 10 2 1 20 20 1 2 12 12 1.2 REC: MICROWAVE 22<br />

23 SPARE 1 20 20 1 2 12 12 1.2 REC: COFFEE MAKER 24<br />

25 REC: DAYROOM 0.2 12 12 2 1 20 20 1 2 12 12 1.4 REC: 26<br />

27 REC: DAYROOM 0.2 12 12 2 1 20 20 1 2 12 12 1.1 REC: 28<br />

29 REC: DAYROOM 0.7 12 12 2 1 20 20 1 2 12 12 0.9 REC: 30<br />

31 REC: DAYROOM 0.5 12 12 2 1 20 20 1 2 12 12 0.9 REC: 32<br />

33 REC: A117 (TV) 0.2 12 12 2 1 20 20 1 2 12 12 0.5 REC: 34<br />

35 REC: A115 0.9 12 12 2 1 20 20 1 2 12 12 0.4 REC: 36<br />

37 REC: A113 0.7 12 12 2 1 20 20 1 2 12 12 0.5 REC: 38<br />

39 REC: A111 0.7 12 12 2 1 20 20 1 2 12 12 0.5 REC: 40<br />

41 REC: A109 1.1 12 12 2 1 20 20 1 2 12 12 0.5 REC: 42<br />

NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY<br />

1. WITH EQUIPMENT GROUND BUS. A = 22.8 KVA 10.4 KVA LIGHTING (INTERIOR AND EXTERIOR)<br />

2. - B = 17.7 KVA 44.7 KVA RECEPTACLES (GENERAL PURPOSE)<br />

3. - C = 18.2 KVA 3.1 KVA RECEPTACLES (EQUIPMENT)<br />

4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)<br />

5. - PHASE A: 190 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)<br />

6. - TOTAL CONNECTED LOAD 0.5 KVA MISCELLANEOUS<br />

7. - 163 AMPERES 58.7 KVA TOTAL CONNECTED LOAD<br />

PANELBOARD '1N1' (NEW) SECTION 2<br />

CKT. LOAD (KVA) WIRE DEVICE DEVICE WIRE LOAD (KVA) CKT.<br />

NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.<br />

43 REC: A118 0.9 12 12 2 1 20 20 1 2 12 12 1.4 REC: 44<br />

45 REC: A116 0.7 12 12 2 1 20 20 1 2 12 12 0.4 REC: 46<br />

47 REC: A114 0.7 12 12 2 1 20 20 1 2 12 12 0.5 REC: 48<br />

49 REC: A112 0.7 12 12 2 1 20 20 1 2 12 12 0.7 REC: 50<br />

51 REC: A121 0.5 12 12 2 1 20 20 1 2 12 12 0.4 REC: 52<br />

53 REC: A123 0.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: A134 54<br />

55 REC: A107 0.9 12 12 2 1 20 20 1 2 12 12 0.9 REC: A133 56<br />

57 WASHING MACHINE: A107 1.5 12 12 2 1 20 20 1 2 12 12 0.4 REC: A131 58<br />

59 ELECTRIC DRYER: A107 2.1 2.1 10 10 2 2 30 20 1 2 12 12 0.7 REC: A122 60<br />

20 1 2 12 12 0.7 REC: A124 62<br />

63 REC: A105 0.9 12 12 2 1 20 20 1 2 12 12 0.9 REC: A126 64<br />

65 SPARE 1 20 20 1 2 12 12 0.2 REC: TV 66<br />

67 REC: A172 0.7 12 12 2 1 20 20 1 2 12 12 0.9 REC: A129 68<br />

69 LTG: A100 0.8 12 12 2 1 20 20 1 2 12 12 0.7 REC: A127 70<br />

71 ELEV PIT LTG AND REC 0.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: A125 72<br />

73 SPARE 1 20 20 1 SPARE 74<br />

75 SPARE 1 20 20 1 SPARE 76<br />

77 SPARE 1 20 20 1 SPARE 78<br />

79 SPARE 1 20 20 1 SPARE 80<br />

81 SPARE 1 20 20 1 SPARE 82<br />

83 SPARE 1 20 20 1 SPARE 84<br />

SWITCHBOARD 'MSB'<br />

(NEW)<br />

SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: 3000A MCB TYPE: SWITCHBOARD<br />

BUS AMPACITY: 3000 AMPERES A.I.C. RATING: 65,000 AMPERES MOUNTING: FLOOR<br />

NEUTRAL BUS AMPACITY: 3000 AMPERES BRANCH: EQUIPMENT ENCLOSURE: NEMA 1<br />

UNIT<br />

DEVICE FEEDER/ BRANCH CIRCUIT LOAD (KVA)<br />

NO. NAMEPLATE POLE FRAME(A) TRIP(A) # SIZE GND CONDUIT TOTAL PH. A PH. B PH. C NOTES ADDITIONAL COMMENTS<br />

1 SWITCHBOARD - "QSB" 3 2000 2000 - - - - 361.7 121.4 120.3 120.0 2<br />

2 PANEL 'DPC' 3 1000 1000 - - - - 29.3 10.3 10.2 8.8 2<br />

3 PANEL '1N1' 3 225 225 - - - - 58.7 22.8 17.7 18.2 2<br />

4 SPARE, FUTURE PANEL 3 225 225<br />

5 SPARE, FUTURE PANEL 3 225 225<br />

6 SPARE, FUTURE PANEL 3 225 225<br />

7 SPARE, FUTURE PANEL 3 225 225<br />

8 SPARE, FUTURE PANEL 3 225 225<br />

9 SPARE, FUTURE PANEL 3 225 225<br />

10 SPARE, FUTURE PANEL 3 225 225<br />

11 SPARE 3 225<br />

12 SPARE 3 225<br />

13 SPARE 3 100<br />

14 SPARE 3 100<br />

NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY<br />

1. WITH EQUIPMENT GROUND BUS. A = 154.5 KVA 23.7 KVA LIGHTING (INTERIOR AND EXTERIOR)<br />

2. SEE POWER RISER DIAGRAM FOR CONDUCTOR AND RACEWAY SIZES. B = 148.3 KVA 58.0 KVA RECEPTACLES (GENERAL PURPOSE)<br />

3. - C = 147.0 KVA 13.9 KVA RECEPTACLES (EQUIPMENT)<br />

4. - HIGHEST CONNECTED PHASE(S) 53.9 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)<br />

5. - PHASE A: 1287 AMPERES 296.2 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)<br />

6. - TOTAL CONNECTED LOAD 4.0 KVA MISCELLANEOUS<br />

7. - 1248 AMPERES 449.8 KVA TOTAL CONNECTED LOAD