14.09.2016 Views

Bussmann

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Electrical - Power Fuses<br />

<strong>Bussmann</strong> ®<br />

Dura-Lag <br />

Dual-Element, Time-Delay, Class RK5 Fuses<br />

DLN-R (250V)<br />

Dual-Element, Time-Delay – 10 seconds (minimum) at<br />

500% rated current<br />

Ampere Ratings: 1-600A<br />

Voltage Rating: 250Vac (or less), 125Vdc<br />

Current Limiting RK5 Fuses<br />

Interrupting Rating: 200,000A RMS Sym.<br />

(20,000A @125Vdc)<br />

Agency Information: Std. 248-12, Class RK5<br />

UL Listed, Guide JDDZ, File E4273<br />

CSA C22.2, No. 106-HRCI-R, File 53787<br />

Dimensions: See pages 2-3 for Class RK5 dimensional data.<br />

Catalog Numbers (250Vac/125Vdc)<br />

DLN-R-1 DLN-R-15 DLN-R-100<br />

DLN-R-2 DLN-R-20 DLN-R-125<br />

DLN-R-2⁄Ω DLN-R-25 DLN-R-150<br />

DLN-R-3 DLN-R-30 DLN-R-175<br />

DLN-R-3¤Ω¡º DLN-R-35 DLN-R-200<br />

DLN-R-4 DLN-R-40 DLN-R-225<br />

DLN-R-5 DLN-R-45 DLN-R-250<br />

DLN-R-6 DLN-R-50 DLN-R-300<br />

DLN-R-6⁄Ω¢ DLN-R-60 DLN-R-400<br />

DLN-R-8 DLN-R-70 DLN-R-600<br />

DLN-R-10<br />

DLN-R-12<br />

DLN-R-80<br />

DLN-R-90<br />

Carton Quantity and Weight<br />

Ampere<br />

Carton<br />

Weight*<br />

Ratings Qty. Lbs. Kg.<br />

⁄Ω¡º-30 10 0.56 0.252<br />

35-60 10 1.38 0.621<br />

70-100 5 1.56 0.702<br />

110-200 1 0.90 0.405<br />

225-400 1 1.80 0.810<br />

450-600 1 3.30 1.485<br />

*Weight per carton.<br />

Recommended fuseblocks for<br />

Class R 250V fuses<br />

See pages 47-49<br />

CE logo denotes compliance with European Union Low Voltage Directive<br />

(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact<br />

<strong>Bussmann</strong> Application Engineering at 636-527-1270 for more information.<br />

DLS-R (600V)<br />

Dual-Element, Time-Delay – 10 seconds (minimum) at<br />

500% rated current<br />

Ampere Ratings: 1-600A<br />

Voltage Rating: 600Vac (or less), 300Vdc<br />

Current Limiting RK5 Fuses<br />

Interrupting Rating: 200,000A RMS Sym.,<br />

(20,000A @ 300Vdc)<br />

Agency Information: Std. 248-12, Class RK5<br />

UL Listed, Guide JDDZ, File E4273<br />

CSA C22.2, No. 106-HRCI-R<br />

Dimensions: See pages 2-3 for Class RK5 dimensional data.<br />

Catalog Numbers (600Vac/300Vdc)<br />

DLS-R-1 DLS-R-12 DLS-R-100<br />

DLS-R-1flꭧ DLS-R-15 DLS-R-110<br />

DLS-R-2 DLS-R-17⁄Ω DLS-R-125<br />

DLS-R-2⁄Ω DLS-R-20 DLS-R-150<br />

DLS-R-3 DLS-R-25 DLS-R-175<br />

DLS-R-3⁄Ω DLS-R-30 DLS-R-200<br />

DLS-R-4 DLS-R-35 DLS-R-225<br />

DLS-R-5 DLS-R-40 DLS-R-250<br />

DLS-R-6 DLS-R-45 DLS-R-300<br />

DLS-R-6⁄Ω¢ DLS-R-50 DLS-R-350<br />

DLS-R-7 DLS-R-60 DLS-R-400<br />

DLS-R-8 DLS-R-70 DLS-R-500<br />

DLS-R-9 DLS-R-80 DLS-R-600<br />

DLS-R-10<br />

DLS-R-90<br />

Carton Quantity and Weight<br />

Ampere<br />

Carton<br />

Weight*<br />

Ratings Qty. Lbs. Kg.<br />

⁄Ω¡º-30 10 1.62 0.729<br />

35-60 10 3.00 1.35<br />

70-100 5 3.00 1.35<br />

110-200 1 1.41 0.635<br />

225-400 1 3.13 1.409<br />

450-600 1 5.28 2.376<br />

*Weight per carton.<br />

Recommended fuseblocks for<br />

Class R 600V fuses<br />

See pages 50-52<br />

CE logo denotes compliance with European Union Low Voltage Directive<br />

(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact<br />

<strong>Bussmann</strong> Application Engineering at 636-527-1270 for more information.<br />

Data Sheet: 1021 (0-600) Data Sheet: 1022 (0-600)<br />

14 For complete specification data, call <strong>Bussmann</strong> Information Fax ~ 636.527.1450