Bussmann
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
British, European, & Canadian Standard Industrial Fuses<br />
HRC Form II Current Limiting Fuses<br />
<strong>Bussmann</strong> ®<br />
Dimensional Data<br />
G<br />
F<br />
A<br />
D<br />
E<br />
J<br />
B<br />
H07C (Offset Blades)<br />
H<br />
C<br />
HRC Form II Current Limiting Fuses<br />
Voltage Rating: 600Vac or less, 250Vdc<br />
Construction: Ceramic Body<br />
Interrupting Rating: 200,000A RMS Symmetrical<br />
Agency Information:<br />
CSA C22.2 No.106M1992; BS88:2, IEC269:2<br />
Applications<br />
• HRC FORM II fuses are often used to protect motor control<br />
circuits, together with contactors and overload protection<br />
relays.<br />
• Type 2 coordination - per IEC 947-4.<br />
G<br />
G<br />
K<br />
G<br />
H<br />
H<br />
F<br />
A<br />
C<br />
C<br />
A<br />
F<br />
F<br />
A<br />
E<br />
D<br />
D<br />
K<br />
D<br />
J<br />
B<br />
E<br />
B<br />
B<br />
K07C/K07CR/<br />
L14C/M14C<br />
(Offset Blades)<br />
L09C/M09C/P09C<br />
(Center Blades)<br />
P11C/R11C<br />
(Center Blades)<br />
CE logo denotes compliance with European Union Low Voltage Directive<br />
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact<br />
<strong>Bussmann</strong> Application Engineering at 636-527-1270 for more information.<br />
C<br />
H<br />
E<br />
Current<br />
Ratings Catalog<br />
Dimensions in Inches and (mm)<br />
CSA<br />
(Amps) Number A B C D E F G H J K Category<br />
2 2H07C<br />
4 4H07C<br />
6 6H07C<br />
10 10H07C 1.38 .56 3.38 .38 .06 2.88 .22 .31 .56 —<br />
15 15H07C (35) (14) (85) (9) (1.2) (73) (5.6) (8) (14) — HRCII-C<br />
20 20H07C<br />
25 25H07C<br />
30 30H07C<br />
40 40K07C<br />
50 50K07C<br />
60 60K07C<br />
2.19<br />
(56)<br />
.88<br />
(22)<br />
3.44<br />
(87)<br />
.5<br />
(13)<br />
.06<br />
(1.2)<br />
2.88<br />
(73)<br />
.22<br />
(5.6)<br />
.31<br />
(8)<br />
.88<br />
(22)<br />
—<br />
—<br />
HRCII-C<br />
80 80K07CR 2.19 .88 3.75 .5 .06 2.88 .22 .31 .88 —<br />
100 100K07CR (56) (22) (95) (13) (1.2) (73) (5.6) (8) (22) —<br />
HRCII-MISC<br />
80 80L14C 2.38 .88 4.38 .56 .13 3.69 .34 .44 1 —<br />
100 100L14C (60) (21.4) (111) (14.3) (3.2) (94) (8.7) (11) (25.4) —<br />
HRCII-C<br />
125 125M14C<br />
150 150M14C<br />
200 200M14C<br />
2.56<br />
(65)<br />
1.5<br />
(38)<br />
4.38<br />
(111)<br />
.75<br />
(19)<br />
.09<br />
(2.4)<br />
3.69<br />
(94)<br />
.34<br />
(8.7)<br />
.44<br />
(11)<br />
—<br />
—<br />
—<br />
—<br />
HRCII-MISC<br />
80 80L09C 2.38 .88 5 .56 .13 4.38 .34 .44 — —<br />
100 100L09C (60) (21.4) (127) (14) (3.2) (111) (8.7) (11) — —<br />
HRCII-MISC<br />
125 125M09C<br />
150 150M09C<br />
200 200M09C<br />
2.56<br />
(65)<br />
1.5<br />
(38)<br />
5.38<br />
(136)<br />
.75<br />
(19)<br />
.13<br />
(3.2)<br />
4.38<br />
(111)<br />
.34<br />
(8.7)<br />
.56<br />
(14)<br />
—<br />
—<br />
—<br />
—<br />
HRCII-C<br />
250 250P09C<br />
300 300P09C 3.06 2.31 5.38 1 .19 4.38 .34 .5 — —<br />
350 350P09C (178) (59) (136) (25.4) (4.8) (111) (8.7) (13) — —<br />
HRCII-MISC<br />
400 400P09C<br />
250 250P11C<br />
300 300P11C 3.06 2.31 8.25 1 .19 5.25 .41 .63 — 1<br />
350 350P11C (178) (59) (210) (25.4) (5) (133) (10) (16) — 25<br />
HRCII-C<br />
400 400P11C<br />
450 450R11C<br />
500 500R11C<br />
600 600R11C<br />
3.19<br />
(81)<br />
2.88<br />
(73)<br />
8.25<br />
(210)<br />
1<br />
(25.4)<br />
.25<br />
(6.3)<br />
5.25<br />
(133)<br />
.41<br />
(10)<br />
.63<br />
(16)<br />
—<br />
—<br />
1<br />
25<br />
HRCII-C<br />
Data Sheet: 4131<br />
For complete specification data, call <strong>Bussmann</strong> Information Fax ~ 636.527.1450<br />
195