Bussmann
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
General Data — Selection Chart<br />
<strong>Bussmann</strong> ® 1<br />
200,000A or 300,000A Interrupting Rating (rms symmetrical)<br />
Current Limiting<br />
10,000–50,000 AIC<br />
Buss Fuse Selection Chart (600 Volts or Less)<br />
Circuit Load Ampere Fuse Symbol Voltage Interrupting Remarks<br />
Rating Type Rating (a-c) Class Rating Page<br />
(KA)<br />
Conventional Dimensions—Class RK1, RK5 (0-600A), L (601-6000A)<br />
All type loads 0-600A LOW-PEAK ® LPN-RK_SP 250V RK1†† 300 All-purpose fuses. 9-11<br />
(optimum (dual-element, LPS-RK_SP 600V Unequaled for combined<br />
overcurrent time-delay) short-circuit and<br />
protection). 601 to LOW-PEAK ® KRP-C_SP 600V L 300 overload protection. 6-7<br />
6000A (time-delay) (Specification grade product)<br />
Motors, welder, 0 FUSETRON ® FRN-R 250V RK5†† 200 Moderate degree of 12<br />
transformers, to (dual-element, FRS-R 600V current limitation. Time-delay 13<br />
capacitor banks 600A time-delay) passes surge currents.<br />
(circuits with heavy 0 DURA-LAG TM DLN-R 250V<br />
inrush currents). to (dual-element, DLS-R 600V<br />
RK5 200 14<br />
600A time-delay)<br />
601 to LIMITRON ® KLU 600V L 200 All-purpose fuse. Time- 8<br />
Main, 4000A (time-delay) delay passes surge-currents.<br />
Feeder Non-motor loads KTN-R 250V RK1†† 200 Same short-circuit protection 15<br />
and (circuits with no 0 KTS-R 600V as LOW-PEAK fuses but<br />
Branch heavy inrush to must be sized larger for<br />
currents).<br />
600A<br />
LIMITRON ®<br />
circuits with surge-currents;<br />
LIMITRON fuses _____ (fast-acting)<br />
i.e., up to 300%.<br />
particularly suited for 601 to KTU 600V L 200 A fast acting, high 8<br />
circuit breaker 6000A performance fuse.<br />
protection.<br />
Branch<br />
General<br />
Purpose<br />
(noncurrent<br />
limiting<br />
fuses)<br />
Reduced Dimensions For Installation in Restricted Space—Class J(0-600A), T(0-1200A), CC(0-30A), G(0-60A)<br />
All type loads LOW-PEAK ® LPJ_SP 600V J 300 All-purpose fuses. 17<br />
(optimum (dual-element Unequaled for combined<br />
overcurrent time-delay) short-circuit and overload<br />
protection).<br />
0<br />
protection. (Specification<br />
__________ to<br />
grade product)<br />
Non-motor loads 600A LIMITRON ® JKS 600V J 200 Very similar to KTS-R 18<br />
(circuits with no (quick acting) LIMITRON, but smaller.<br />
heavy inrush<br />
0 to T-TRON TM JJN 300V T 200 The space saver (⁄Ω£ the size<br />
currents).<br />
1200A JJS 600V of KTN-R/KTS-R).<br />
19<br />
Motor loads 0 to 30A LOW-PEAK ® LP-CC 600V CC 200 Rejection feature 21<br />
(circuits with<br />
(time-delay)<br />
heavy in-rush<br />
currents.)<br />
Non-motor loads 0 to 30A LIMITRON ® KTK-R 600V CC 200 Very compact (⁄‹Ω£∑ ≈ 1⁄Ω∑); 22<br />
(circuits with no (fast-acting) rejection feature.<br />
heavy in-rush<br />
currents.)<br />
Control transformer 0 to 30A TRON ® FNQ-R 600V CC 200 Excellent for control 22<br />
circuits and lighting (time-delay) transformer protection.<br />
ballasts; etc.<br />
General purpose; 1 to 20A SC SC 600V G 100 Current limiting; 20<br />
i.e., lighting<br />
⁄‹Ω£∑ dia. ≈ varying<br />
panel boards. 25 to 60A 480V lengths per amp rating.<br />
Miscellaneous 0 to ONE-TIME NON 250V H or K5† 10 Forerunners of 16<br />
600A NOS 600V the modern<br />
Plug fuses can 0 FUSTAT ® S 125V S 10 Base threads of Type S 26<br />
be used for to (dual-element, differ with amp ratings.<br />
branch circuits 30A time-delay) T and W have Edison base.<br />
and small FUSETRON ® T 125V ** 10<br />
T & S fuses recommended<br />
component (dual-element, for motor circuits. W not<br />
protection. time-delay) recommended for circuits<br />
26<br />
with motor loads.<br />
Buss Type W W 125V ** 10<br />
** UL Listed as Edison Base Plug Fuse.<br />
† Some ampere ratings are available as UL Class K5 with a 50,000A interrupting rating.<br />
†† RK1 and RK5 fuses fit standard switches, fuseblocks and holders; however, the rejection feature of class R switches and fuseblocks designed specifically for rejection type fuses<br />
(RK1 and RK5) prevent the insertion of the non-rejection fuses (K1, K5, and H).