DIRIS A80<br />

Multifunction meters - PMD + RCM<br />

monitoring energy and fault currents - dimensions 96 x 96 mm<br />

diris_876x_a_1_cat<br />

Front panel<br />

1. Backlit LCD display.<br />

2. Direct access key for the currents, RCM function<br />

and alarm reset.<br />

3. Direct access key for voltages and frequency.<br />

4. Direct access key for active, reactive, and apparent powers<br />

and power factor.<br />

5. Direct access key for maximum and average current, voltage<br />

and power values.<br />

6. Direct access key for harmonic values and the connection<br />

and RCM test functions.<br />

7. Direct access key for energies, hour meter<br />

and programming menu.<br />

Accessories<br />

Core balance transformer ∆IC<br />

See general catalogue.<br />

tore_046_a<br />

1 2 3 4 5 6 7<br />

DIRIS_878_a_2_cat<br />

Plug-in modules<br />

DIRIS ® A80<br />

diris_776_a_1_cat diris_777_a_1_cat diris_447_a_1_cat<br />

Communication MODBUS ®<br />

• RS485 link with MODBUS ® protocol<br />

(speed up to 38400 bauds).<br />

Ethernet communication<br />

• Ethernet connection with MODBUS TCP or MODBUS RTU over TCP<br />

protocol.<br />

• Embedded Webserver function (1) .<br />

Ethernet communication with RS485 MODBUS gateway<br />

• Ethernet connection with MODBUS TCP or MODBUS RTU over TCP protocol.<br />

• Connection of 1 to 247 RS485 MODBUS slaves.<br />

• Embedded Webserver function (1) .<br />

(1) See “Management softwares for DIRIS” page 140.<br />

diris_849_b_1_x_cat<br />

Terminals<br />

DIRIS A80<br />

V1<br />

V2<br />

DIRIS A80<br />

RCM module<br />

1 input / 1 output<br />

V3<br />

VN<br />

A U X<br />

S1 S2 S1 S2 S1 S2<br />

I1 I2 I3<br />

RCM module<br />

2 outputs<br />

S1<br />

IN<br />

S2<br />

S1 - S2: current inputs<br />

AUX: Auxiliary power supply U s<br />

V1- V2 - V3 - VN: voltage inputs<br />

Memory module<br />

diris_853_c_1_x_cat<br />

K<br />

L<br />

I ∆ N<br />

K L 33 34<br />

IPE<br />

OUT<br />

DIRIS A80<br />

K-L / I∆N : residual current<br />

K-L / IPE : ground fault current<br />

33-34 : relay outputs<br />

37-38 : opto inputs<br />

37<br />

IN<br />

38<br />

diris_871_a_1_x_cat<br />

K<br />

L<br />

I ∆ N<br />

K L 33 34<br />

IPE<br />

OUT 1<br />

DIRIS A80<br />

K-L / I∆N : residual current<br />

K-L / IPE : ground fault current<br />

33-34 : relay output n°1<br />

35-36 : relay output n°2<br />

35<br />

36<br />

OUT 2<br />

diris_872_a_1_x_cat<br />

DIRIS A80<br />

17 18<br />

+ -<br />

IN<br />

synchro<br />

Ethernet module<br />

Ethernet module + RS485 MODBUS gateway<br />

RS485 MODBUS module<br />

diris_851_b_1_x_cat<br />

10 BASE T<br />

100 BASE T<br />

RJ45<br />

DIRIS A80<br />

diris_852_c_1_gb_cat<br />

10 BASE T<br />

100 BASE T<br />

RJ45<br />

DIRIS A80<br />

0 V - +<br />

RS485<br />

gateway<br />

1<br />

0n<br />

R = 120Ω<br />

RS485 gateway resistor.<br />

R = 120 Ω: selectable internal resistance for RS485<br />

end of line termination.<br />

diris_850_c_1_x_cat<br />

0V - +<br />

RS485<br />

1<br />

0n<br />

R = 120Ω<br />

DIRIS A80<br />

RS485 link<br />

R = 120 Ω: selectable internal resistance<br />

for RS485 end of line termination.<br />

Catalogue 2017<br />