Interconnection<br />
CAUTION:<br />
• All wiring must be done in accordance with approved conduit, boxes, and<br />
fittings, and to procedures in accordance with all governing regulations.<br />
• Flexible conduit is recommended so excess stress is not applied to the<br />
shaft bearings<br />
• Interconnection between the speed sensor and the integrator should be<br />
made with 3-wire shielded, 18 AWG cable (Belden 8770 or equivalent).<br />
• Ground the shield at the integrator ONLY!<br />
<strong>MD</strong>-<strong>36</strong> <strong>Speed</strong> <strong>Sensor</strong>/Integrator Connection<br />
<strong>MD</strong>-<strong>36</strong> Compu III BW 100 BW 500<br />
Description Terminal TB1 TB1 TB1<br />
+ 15 V DC 1 30 8 19<br />
<strong>Speed</strong> Out<br />
(CW) 1 2<br />
(31) 2<br />
(7) (16)<br />
<strong>Speed</strong> Out<br />
(CCW)<br />
3<br />
(31) (7) (16)<br />
Common 4 32 6 17<br />
Ground G N/C3 N/C N/C<br />
1. To determine direction of rotation, see Front View mounting<br />
on page 14.<br />
2. Terminal positions in brackets denote that only one signal<br />
may be connected at one time.<br />
3. N/C = No Connection<br />
<strong>MD</strong>-<strong>36</strong> IS <strong>Speed</strong> <strong>Sensor</strong>/Isolator/Integrator Connection<br />
<strong>MD</strong>-<strong>36</strong> IS<br />
IS Switch Isolator<br />
(P&F #KFA5-S0T2-Ex2)<br />
BW 100 BW 500<br />
Terminal Terminal TB1 TB1<br />
3 1<br />
4 3<br />
7 7 16<br />
8 17 14<br />
7ML19985DB01 <strong>Milltronics</strong> <strong>MD</strong>-<strong>36</strong> <strong>Speed</strong> <strong>Sensor</strong> – INSTRUCTION MANUAL Page 15<br />