TECHNICAL INFORMATION<br />
WIRE SIZING<br />
REQUIRED INFORMATION<br />
Actual one-way length of wire between the controllers and the power source or the controllers and valves<br />
Allowable voltage loss along the wire circuit<br />
Accumulative current flowing through the wire section being sized in amperes<br />
RESISTANCE IS CALCULATED USING THIS FORMULA:<br />
R = 1000 x AVL<br />
2L x I<br />
R = Maximum Allowable Resistance of wire in ohms per 1,000'<br />
AV L = Allowable voltage loss<br />
L = Wire length (one way)<br />
I = Inrush current<br />
AVL for controller power wire sizing is calculated by subtracting the minimum operating voltage required by the controller from the minimum<br />
available voltage at the power source.<br />
AVL for valve wire sizing is calculated by subtracting minimum solenoid operating voltage from controller output voltage.<br />
This number will vary depending on the manufacturer and in some cases with line pressure.<br />
VALVE WIRE SIZING EXAMPLE<br />
Given: The distance from the controller to the valve is 1,800'. The controller output is 24 V. The valve has a minimum operating voltage of<br />
20 V and an inrush current of 370 mA (0.37 A).<br />
R = 1,000 x 4<br />
2 (1,800) x 0.37<br />
R = 4,000<br />
1,332<br />
TECHNICAL<br />
R = 3.00 ohms/1,000 ft.<br />
So, wire resistance cannot exceed 3.00 ohms per 1,000'. Now go to table #1 and select the proper wire size. Since 18 gauge wire has more<br />
resistance than 3.00 ohms per 1,000', choose 14 gauge wire.<br />
Table 2 is a quick reference and is set up to provide maximum wire runs given the information at the bottom of the table.<br />
TABLE 1 - RESISTANCE OF COPPER WIRE<br />
Wire Size<br />
(AWG)<br />
Resistance at 20° C (68° F)<br />
(ohms per 1,000')<br />
18 6.39<br />
16 4.02<br />
14 2.52<br />
12 1.59<br />
10 1<br />
8 0.63<br />
6 0.4<br />
4 0.25<br />
TABLE 2- VALVE WIRE SIZING<br />
Ground Wire<br />
Control Wire<br />
18 16 14 12 10 8 6<br />
18 850 1040 1210 1350 1460 1540 1590<br />
16 1040 1340 1650 1920 2150 2330 2440<br />
14 1210 1650 2150 2630 3080 3450 3700<br />
12 1350 1920 2630 3390 4170 4880 5400<br />
10 1460 2150 3080 4170 5400 6670 7690<br />
8 1540 2330 3450 4880 6670 8700 10530<br />
6 1590 2440 3700 5400 7690 10530 13330<br />
Notes:<br />
Maximum one-way distance in feet between controller and valve heavy-duty solenoid: 24 VAC, 350 mA<br />
inrush current, 190 mA holding current, 60 Hz; 370 mA inrush current, 210 mA holding current, 50 Hz.<br />