12 th International Conference on Urban Drainage, Por<strong>to</strong> Alegre/Brazil, 11-16 September 2011<br />

in this case GPRS cannot be used as <strong>the</strong> communication medium. This is why, in<br />

collaboration with <strong>the</strong> municipality of Hildesheim, SEGNO has used a DSL (broadband<br />

Internet) network. The result was that, in <strong>the</strong> case of Hildesheim, network <strong>control</strong> was<br />

additionally centralised because <strong>the</strong> cables <strong>to</strong> <strong>the</strong> treatment plant’s central PLC were already<br />

available (Peikert et al., 2010).<br />

In addition <strong>to</strong> having <strong>control</strong> and communication tasks, <strong>the</strong> RTC <strong>system</strong> box can - and should<br />

- also be responsible for data s<strong>to</strong>rage and data management in <strong>the</strong> sewer network. For <strong>the</strong> purpose<br />

of displaying, and inputting or outputting data on <strong>the</strong> spot, <strong>the</strong> box has been designed <strong>to</strong><br />

allow <strong>the</strong> data <strong>to</strong> be captured via an OPC interface <strong>to</strong> a visualisation <strong>system</strong> (InTouch made by<br />

Wonderware). An additional interface was created for <strong>the</strong> purpose of configuring <strong>the</strong> module<br />

from <strong>the</strong> visualisation <strong>system</strong> directly. In this form, even after <strong>system</strong> commissioning, <strong>the</strong><br />

opera<strong>to</strong>r has been provided with a <strong>to</strong>ol that facilitates adjustments <strong>to</strong> <strong>the</strong> parameter settings.<br />

Thus enables <strong>the</strong> module’s <strong>control</strong> behaviour <strong>to</strong> be directly influenced, while operating convenience<br />

is enhanced (Peikert et al., 2010).<br />

Moreover, an engineering <strong>to</strong>ol that supports <strong>the</strong> operation of <strong>the</strong> <strong>ADESBA</strong> box with his<strong>to</strong>rical<br />

data, <strong>to</strong>o, has been developed. Thus, it has been successfully verified that <strong>the</strong> behaviour of <strong>the</strong><br />

physical <strong>ADESBA</strong> <strong>control</strong> box is identical <strong>to</strong> that of <strong>the</strong> model blocks. This considerably simplifies<br />

<strong>the</strong> actual realisation of <strong>the</strong> <strong>control</strong> box and verification management of <strong>the</strong> linked <strong>control</strong><br />

<strong>system</strong>. Figure 3 shows <strong>the</strong> function of <strong>the</strong> engineering <strong>to</strong>ol.<br />

Figure 3. Engineering <strong>to</strong>ol - test setup with his<strong>to</strong>rical data (Peikert et al., 2010)<br />

Project execution covered not only development but also <strong>the</strong> testing of <strong>the</strong> RTC <strong>system</strong> box -<br />

i.e. ensuring intercommunication between all <strong>the</strong> modules involved and <strong>the</strong>ir interfaces.<br />

Ano<strong>the</strong>r question that is of considerable importance <strong>to</strong> sewage <strong>system</strong> opera<strong>to</strong>rs is how <strong>the</strong><br />

quality of <strong>the</strong> <strong>ADESBA</strong> RTC <strong>system</strong> box can be demonstrated. A fundamental problem when<br />

testing any RTC <strong>system</strong> for sewer <strong>system</strong>s is <strong>the</strong> non-reproducibility of rainfall events. That<br />

means <strong>control</strong> behaviour of <strong>control</strong> <strong>system</strong>s cannot be accurately assessed solely on <strong>the</strong> basis<br />

of simulation studies - SEGNO has developed an engineering <strong>to</strong>ol that compares data on<br />

actual events with data on <strong>control</strong>led events, thus permitting an assessment of <strong>ADESBA</strong>’s<br />

6 <strong>ADESBA</strong> - A <strong>new</strong> <strong>general</strong> <strong>global</strong> <strong>control</strong> <strong>system</strong>