SAG582140000 SYSTEM OVERVIEW - Emerson Network Power
SAG582140000 SYSTEM OVERVIEW - Emerson Network Power
SAG582140000 SYSTEM OVERVIEW - Emerson Network Power
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
System Application Guide <strong>SAG582140000</strong><br />
Spec. No. 582140000 (Model 802NLDB, 802NLEB, 802NL-B) Issue AL, April 12, 2010<br />
TPL Fuses and Fuseholder Assemblies<br />
Features<br />
♦ Each fuseholder assembly is equipped with a shunt for MCA load current measurements.<br />
♦ Bolts into bay's distribution device mounting positions.<br />
♦ Load lug adapter plate provides 3/8" clearance holes on 1" centers for installation of customer provided<br />
two-hole lugs. For load return lug requirements, refer to <strong>Power</strong>/Distribution Bay Internal and External<br />
Busbars and Distribution Only Bay External Busbars in this section.<br />
Restrictions<br />
Load should not exceed 80% of device rating.<br />
Refer to Table 2 for required distribution bus mounting positions.<br />
Each distribution bus is divided into half. Each half MUST be populated with distribution devices as shown in<br />
the illustrations at the beginning of this section, without skipping any distribution device mounting positions<br />
within each half.<br />
Refer to the illustrations in this section for lug and wire size restrictions.<br />
Ordering Notes<br />
1) Order fuses, the appropriate fuseholder assembly for each fuse, and load lug adapter kits per Table 2.<br />
2) For each fuse ordered, also order one (1) P/N 248610301 alarm fuse,<br />
and one (1) P/N 248898700 safety fuse cover.<br />
3) See Table 7 for recommended load distribution wire sizes and lugs.<br />
Ampere<br />
Rating<br />
Required Distribution Bus<br />
Mounting Positions<br />
<strong>Power</strong>/<br />
Distribution<br />
Bay<br />
Distribution<br />
Only Bay<br />
Fuse<br />
Page 37 of 107<br />
Part Number<br />
Fuseholder<br />
Assembly<br />
Lug Adapter Kit<br />
Part Number<br />
<strong>Power</strong>/<br />
Distribution<br />
Bay<br />
Distribution<br />
Only Bay<br />
70 4 2 248251500 514403 520892 529132<br />
80 4 2 248252000 514403 520892 529132<br />
100 4 2 248252600 514403 520892 529132<br />
150 4 2 248253300 514403 520892 529132<br />
200 4 2 248254000 514403 520892 529132<br />
225 4 2 248254500 514403 520892 529132<br />
250 4 2 248255000 514403 520892 529132<br />
300 4 2 248255700 514403 520892 529132<br />
400 4 2 248257000 514403 520892 529132<br />
500 4 2 248258000 514403 520892 529132<br />
600 4 2 248259000 514403 520892 529132<br />
800 6 3 102901 514404 520893 529131<br />
For each fuse ordered, also order: one (1) P/N 248610301 alarm fuse (GMT-18/100A), and<br />
one (1) P/N 248898700 safety fuse cover (GMT-X).<br />
See Table 7 for recommended load distribution wire sizes and lugs.<br />
Table 2<br />
TPL Fuses and Fuseholder Assemblies<br />
Home<br />
This document is property of <strong>Emerson</strong> <strong>Network</strong> <strong>Power</strong>, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by <strong>Emerson</strong> <strong>Network</strong> <strong>Power</strong>, Energy<br />
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of <strong>Emerson</strong> <strong>Network</strong> <strong>Power</strong>, Energy Systems, North America, Inc. is strictly prohibited.