20.12.2012 Views

SAG582140000 SYSTEM OVERVIEW - Emerson Network Power

SAG582140000 SYSTEM OVERVIEW - Emerson Network Power

SAG582140000 SYSTEM OVERVIEW - Emerson Network Power

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>SAG582140000</strong> System Application Guide<br />

Issue AL, April 12, 2010 Spec. No. 582140000 (Model 802NLDB, 802NLEB, 802NL-B)<br />

(C) Maximum input current at 100% of full load with output adjusted to 58 volts DC as<br />

measured at the output bus.<br />

Nominal<br />

Input<br />

Voltage<br />

Input<br />

Voltage<br />

480 408<br />

3.3 Input Ratings (208VAC – List 21)<br />

Number of<br />

Rectifiers<br />

Installed<br />

Page 80 of 107<br />

Input Current<br />

(Amperes)<br />

1 17.83<br />

2 35.67<br />

3 53.50<br />

4 71.34<br />

5 89.17<br />

6 107.00<br />

7 124.84<br />

8 142.67<br />

9 160.51<br />

10 178.34<br />

3.3.1 Voltage: Nominal 208 volts AC, three phase, 60 Hz, with an operating range of 176 to 264<br />

volts. Acceptable input frequency range is 47 to 63 Hz.<br />

3.3.2 Harmonic Content: Complies with IEEE-519-1992. Voltage harmonic distortion of less than<br />

5% when operating on a line impedance of 0.104 ohms or less.<br />

3.3.3 Inrush Current: Peak does not exceed 6 times the RMS input current at full load, under any<br />

conditions of input voltage within the rated input voltage range stated in Paragraph 3.2.1 and<br />

for any duration of AC input interrupts. Under the above conditions, standard AC distribution<br />

circuit breakers will not trip.<br />

3.3.4 Typical Input Data: 60 Hz input.<br />

Number<br />

of<br />

Rectifiers<br />

Installed<br />

(A) System output is initially adjusted to 54.48 volts DC as measured at the output bus at 50%<br />

of full load and nominal input.<br />

Nominal<br />

Input<br />

Voltage<br />

1 208<br />

Percent<br />

of Full<br />

Load<br />

Input<br />

Current<br />

(Amperes)<br />

This document is property of <strong>Emerson</strong> <strong>Network</strong> <strong>Power</strong>, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by <strong>Emerson</strong> <strong>Network</strong> <strong>Power</strong>, Energy<br />

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of <strong>Emerson</strong> <strong>Network</strong> <strong>Power</strong>, Energy Systems, North America, Inc. is strictly prohibited.<br />

Input<br />

VA<br />

Input<br />

Watts<br />

<strong>Power</strong><br />

Factor<br />

Efficiency<br />

%<br />

0 0.100 120 84 0.700 --<br />

25 8.720 3149 3078 0.977 88.30<br />

50 16.855 6075 6032 0.992 89.97<br />

75 25.720 9163 9132 0.996 89.03<br />

100 34.480 12398 12371 0.997 87.51<br />

Home

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!