Section 6 · Installation and Start-up

Connecting the PV generator using cable fittings

ATTENTION

To achieve protection class IP54, unused cable fi ttings

must be closed off by using the included blind caps.

ACTION

To do this, unscrew the cable fi ttings until you can insert

the cables through the fi tting, and screw the ends of the

cables into place in the connection terminals labelled

“PV+” and “PV-”. When doing this, ensure that the

polarity is correct. Tighten the cap of the cable fi tting.

Figure 6.4: Installing Tyco sockets

The assembly of the Tyco and MC plug connectors is shown in

fi gure 6.5 and fi gure 6.6 respectively.

Connecting the PV generator using MC or Tyco plug

connectors

As an option, MC and Tyco plug connectors can be delivered

with the inverter. These can be used instead of the cable fi t-

tings that were already installed upon delivery. These preinstalled

cable fi ttings must fi rst be removed before installing

the appropriate plug connectors.

WARNING

Figure 6.5: Assembly of the Tyco plug connectors

Always disconnect the inverter from the PV generator

by operating the integrated DC disconnector

before pulling apart the plug connector. Failure

to observe this may cause arcing, which can

result in a hazard to health and to the unit.

ACTION

Unscrew the cable fi ttings from the cut-outs in the base

plate of the inverter.

Insert the Tyco or MC sockets from the outside through

the cut-outs, and secure them from the inside using the

black plastic nut.

Figure 6.6: Assembly of the MC plug connectors

Page 16

Installation Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN