09.06.2021 Views

MNL_PW_2500xi-5000xi_02_en

KACO 2500xi-5000Xi Manual

KACO 2500xi-5000Xi Manual

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Section 4 · Operation

ok

!

1

2

3

Wait approx. 10 minutes to see if the fault is only temporary

in nature. If this is not the case, notify your authorised electrician.

If the fault is cleared, the grid feed begins once again after a

country-specifi c waiting period (see Installation Instructions,

Section 4, “Technical Data”).

Figure 4.2: LED displays

LED (1) (green):

The LED begins to light up beginning with a photovoltaic

module voltage of approx. 300 V and goes out again if the

module voltage is lower than 250 V.

The “OK” LED indicates that the inverter and the inverter control

are active. If this LED is not lit, the inverter cannot feed

into the grid.

In normal mode, the LED begins to light up in the morning

(if there is enough sunlight) and goes out as nightfall

approaches.

LED (2) (green):

The LED lights up every time the inverter feeds into the grid. For

this to happen, the photovoltaic module voltage must exceed

400 V (factory setting) and suffi cient power must be provided

by the PV generator. If the grid feed is interrupted because the

power is too low, the inverter waits for a country-specifi c length

of time before it begins feeding into the grid once again. LED (2)

can, therefore, light up only when LED (1) is already lit.

In a normal state, the inverter begins feeding into the grid

in the morning and stops feeding into the grid as it becomes

increasingly darker. On cloudy days and in the winter months,

the grid feed can - depending on the PV generator and the

current grid feed power - be temporarily interrupted and subsequently

re-started. This process can repeat itself several

times, especially in the morning and evening. This is in no way

an indication of defective operation, but instead constitutes

normal operating behaviour.

LED (3) (red):

The LED indicates that the grid feed was stopped due to a

fault.

The following faults activate the LED (3):

– Grid overvoltage or undervoltage on one of the three

phases

– Failure of one of the phases L2 or L3

– Generator power is too high

– Shutdown due to the temperature being too high

– Fault in the unit

– Leakage current is too high (RCD type B)

– Overfrequency or underfrequency

– Insulation fault

– Communication error

– Fault in the DC grid feed

– Fault in the voltage transformer

– Selftest fault

– Fault in the RCD type B module.

Check whether the fault in question relates to a general power

failure or whether the fuse between the meter and the inverter

has failed. If the fuse has failed, notify your authorised technician.

If there was a power failure, simply wait until the fault

has been cleared. The system automatically re-starts.

4.3 Keys “1” and “2”

IMPORTANT

If the grid feed phase fails (power failure on the public

grid), LED (3) does not light up. If this happens, all LEDs

and the display go out. The inverter is shut down completely.

The inverter can only resume its normal operation when

the grid feed phase is available once again.

Figure 4.3: Powador control keys

Key “1” is used to switch between the various displays for

measured values and data. With key “2”, settings such as

those relating to the shutdown value can be confi gured. Here,

menu navigation is divided into two levels. In level 1 (display

mode), measured values such as the solar generator voltage

and yields can be read. Here, only key “1” is activated. In confi

guration mode, key “1” is also used to navigate through the

individual displays, and settings are confi gured with key “2”.

ACTION

By pressing key “1” for approx. 1 second, you can choose

which measured value is to be displayed.

The menus are continuous, which means that when you

arrive at the last entry in a menu, the fi rst entry is displayed

once again the next time key “1” is pressed (see Figure

4.4).

Operating Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN Page 7

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!