Section 6 · Installation and Start-up

ACTION

– Switch on the line voltage (via the external circuit

breakers).

– Switch on the solar generator using the DC disconnector

(0 → 1).

The uppermost green LED (1) lights up if the generator voltage

is greater than 300 V. The display now shows the inverter

type for 4 seconds, followed by the current generator voltage:

“Start at 410 V meas.: xxx V”. If the measured voltage

is greater than 410 V, the unit begins feeding into the grid

after a country-specifi c time period (see section 4, Technical

Data). This country-specifi c start-up period is required in order

to ensure that the generator voltage is continuously above the

power delivery limit of 410 V. An quick start routine is provided

for start-up and test purposes. This routine circumvents

the start-up period. This quick start routine is found in the

confi guration mode menu (see Operating Instructions).

During the start-up procedure, the line power relay audibly

switches on and power delivery starts. This is signalled by the

green LED (2). The display now shows the power being fed

to the grid. Key “1” can now be used to display the various

measured values (see Operating Instructions).

If the inverter stops feeding into the grid because the power

is too low, it waits a country-specifi c length of time before

resuming power delivery (see section 4,Technical Data).

Quick start

The inverter can also be started up without any waiting period

for the purpose of testing or for the purpose of acceptance by

your power supply company.

6.8 Programming -

Configuration mode menu

Various operating mode parameters can be set in the confi guration

mode menu of Powador xi units.

WARNING

Incorrect parameter settings will lead to a loss of

function, render your Safety Certificate invalid,

and result in the loss of the safety functions.

Modifications may only be made in exceptional

cases and only after having consulted with the

manufacturer and the power supply company.

In order to switch to the confi guration mode menu, hold key

“2” pressed down for 15 seconds until the display changes

and displays the fi rst parameter.

Use key “1” to scroll through the various menu items. The

menu is continuous. When you reach the end, the display

automatically jumps back to the fi rst item.

The parameter menu is country-specific.

Details can be found in:

– Section 4

– Technical Data

– Country-specific parameters.

Figure 6.9: Configuration mode menu

ACTION

To do this, switch to the confi guration mode menu by

pressing both keys at the same time. Press key “1” to

move through the menu until you have reached the

“Quick start with key 2” menu item.

When you have reached this menu item, keep key “2”

pressed down for a short time until the inverter switches

on (relays switch audibly) and the green grid-feed LED (2)

lights up. If the solar generator voltage is too low, the

inverter switches off again.

ACTION

Use key “2” to change the parameter that is shown.

When doing so, the value increases or decreases, depending

on the parameter. The values here are also continuous,

i.e. after you reach the maximum value, they jump

back to the minimum value.

Page 18

Installation Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN