Section 6 · Installation and Start-up
ACTION
– Switch on the line voltage (via the external circuit
breakers).
– Switch on the solar generator using the DC disconnector
(0 → 1).
The uppermost green LED (1) lights up if the generator voltage
is greater than 300 V. The display now shows the inverter
type for 4 seconds, followed by the current generator voltage:
“Start at 410 V meas.: xxx V”. If the measured voltage
is greater than 410 V, the unit begins feeding into the grid
after a country-specifi c time period (see section 4, Technical
Data). This country-specifi c start-up period is required in order
to ensure that the generator voltage is continuously above the
power delivery limit of 410 V. An quick start routine is provided
for start-up and test purposes. This routine circumvents
the start-up period. This quick start routine is found in the
confi guration mode menu (see Operating Instructions).
During the start-up procedure, the line power relay audibly
switches on and power delivery starts. This is signalled by the
green LED (2). The display now shows the power being fed
to the grid. Key “1” can now be used to display the various
measured values (see Operating Instructions).
If the inverter stops feeding into the grid because the power
is too low, it waits a country-specifi c length of time before
resuming power delivery (see section 4,Technical Data).
Quick start
The inverter can also be started up without any waiting period
for the purpose of testing or for the purpose of acceptance by
your power supply company.
6.8 Programming -
Configuration mode menu
Various operating mode parameters can be set in the confi guration
mode menu of Powador xi units.
WARNING
Incorrect parameter settings will lead to a loss of
function, render your Safety Certificate invalid,
and result in the loss of the safety functions.
Modifications may only be made in exceptional
cases and only after having consulted with the
manufacturer and the power supply company.
In order to switch to the confi guration mode menu, hold key
“2” pressed down for 15 seconds until the display changes
and displays the fi rst parameter.
Use key “1” to scroll through the various menu items. The
menu is continuous. When you reach the end, the display
automatically jumps back to the fi rst item.
The parameter menu is country-specific.
Details can be found in:
– Section 4
– Technical Data
– Country-specific parameters.
Figure 6.9: Configuration mode menu
ACTION
To do this, switch to the confi guration mode menu by
pressing both keys at the same time. Press key “1” to
move through the menu until you have reached the
“Quick start with key 2” menu item.
When you have reached this menu item, keep key “2”
pressed down for a short time until the inverter switches
on (relays switch audibly) and the green grid-feed LED (2)
lights up. If the solar generator voltage is too low, the
inverter switches off again.
ACTION
Use key “2” to change the parameter that is shown.
When doing so, the value increases or decreases, depending
on the parameter. The values here are also continuous,
i.e. after you reach the maximum value, they jump
back to the minimum value.
Page 18
Installation Instructions Powador 2500xi / 3600xi / 4000xi / 4500xi / 5000xi_EN