<strong>HART</strong> Data- IOM Scanning and Data Cache<br />

1<br />

8<br />

Ch-0<br />

Ch-15<br />

<strong>HART</strong><br />

AI<br />

Analog PV: (250 ms update)<br />

4-20 mA input is scanned, converted<br />

and published to the C-200.<br />

1<br />

8<br />

Ch-0<br />

Ch-15<br />

<strong>HART</strong><br />

AO<br />

Analog OP: (25 ms update)<br />

0-100% value is received from the<br />

C-200 and then converted to the<br />

equivalent 4-20 mA value.<br />

The following <strong>HART</strong> device digital data can be cached on<br />

the AI and AO Module and will then available for use within<br />

the system:<br />

� Device ID information: (#)<br />

Tag, Manufacturer, Model, SW/HW Rev, SN, date,<br />

descriptor, Etc.<br />

� Dynamic variables: (+)<br />

Command 3 (PV, SV, TV, FV)<br />

� Device variables: (+)<br />

Command 33, Slot-0 through Slot-3<br />

� Range information: (#)<br />

Range Hi and Range Low<br />

� Device standard status: (+)<br />

General device condition, command and comm status<br />

� Device-Specific status: (*)<br />

Command 48, Device-Specific status<br />

(#) Scanned at start-up or loss of communication<br />

(+) Periodically scanned<br />

(*) Scanned whenever the device indicates an error<br />

26 HONEYWELL 26<br />